SIMATIC ET 200BL, analog output module, AQ 4xI, module diagnostics, 16 bit, packing unit: 1 unit, color code CC00
Specifications
General information
| Product type designation | AQ 4xI |
| HW functional status | from FS01 |
| Firmware version | V1.0.0 |
| Firmware version — FW update possible | Yes |
| Color code for module-specific color-coded label | CC00 |
| Product function — I&M data | Yes; I&M0 to I&M3 |
| Product function — Isochronous mode | No |
| Product function — Output range scalable | No |
| Engineering with — STEP 7 TIA Portal configurable/integrated from version | STEP 7 V18 or higher; MicroWin V3.0 or higher; Configuration in ES via GSDML; |
| Engineering with — PROFINET from GSD version/GSD revision | GSDML V2.45 |
| Operating mode — Oversampling | No |
Supply voltage
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| external protection for power supply lines | Yes; 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic |
Input current
| Current consumption (rated value) | 55 mA |
| Current consumption, max. | 170 mA; 4 channels activated with -20 mA per channel at 20.4 V |
Current carrying capacity
| For P1 and P2 bus, max. | 10 A |
Power loss
| Power loss, typ. | 1.2 W; rated voltage, 50 % load, 50 % active channels |
Address area
| Address space per module — Address space per module, max. | 8 byte |
| Address space per module — Outputs | 8 byte |
Hardware configuration
| Automatic encoding | No |
| Automatic encoding — Mechanical coding element | No |
| Formation of potential groups — support of potential groups | Yes |
Analog outputs
| Number of analog outputs | 4 |
| Cycle time (all channels), min. | 1 ms |
| Analog output with oversampling | No |
| Output ranges, current — 0 to 20 mA | Yes; 15 bit |
| Output ranges, current — 20 mA to +20 mA | Yes; 16 bit incl. sign |
| Output ranges, current — 4 mA to 20 mA | Yes; 14 bit |
| Connection of actuators — for voltage output two-wire connection | No |
| Connection of actuators — for voltage output four-wire connection | No |
| Connection of actuators — for current output two-wire connection | Yes |
| Load impedance (in rated range of output) — with current outputs, max. | 500 Ω |
| Load impedance (in rated range of output) — with current outputs, inductive load, max. | 1 mH |
| Cable length — shielded, max. | 1 000 m |
Analog value generation for the outputs
| Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max. | 16 bit |
| Settling time — for resistive load | 0.1 ms |
| Settling time — for inductive load | 0.5 ms |
Errors/accuracies
| Linearity error (relative to output range), (+/-) | 0.15 % |
| Temperature error (relative to output range), (+/-) | 0.005 %/K |
| Crosstalk between the outputs, min. | -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % |
| Operational error limit in overall temperature range — Current, relative to output range, (+/-) | 0.5 % |
| Basic error limit (operational limit at 25 °C) — Current, relative to output range, (+/-) | 0.3 % |
Interrupts/diagnostics/status information
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Alarms — Diagnostic alarm | Yes |
| Diagnoses — Monitoring the supply voltage | Yes |
| Diagnoses — Wire break | Yes; module-wise |
| Diagnoses — Short-circuit | No |
| Diagnoses — Group error | No |
| Diagnoses — Overflow/Underflow | Yes; module-wise |
| Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED — Channel status display | Yes; green LED |
| Diagnostics indication LED — for channel diagnostics | No |
| Diagnostics indication LED — for module diagnostics | Yes; green/red DIAG LED |
Potential separation
| between backplane bus and supply voltage | Yes |
| Potential separation analog outputs — between the channels | No |
| Potential separation analog outputs — between the channels and backplane bus | Yes |
| Potential separation analog outputs — between the channels and the power supply of the electronics | No |
Isolation
| Isolation tested with | 500 V AC/707 V DC, type test |
Standards, approvals, certificates
| Ecological footprint — environmental product declaration | Yes |
| Ecological footprint — Global warming potential — global warming potential, (total) [CO2 eq] | 28.8 kg |
| Ecological footprint — Global warming potential — global warming potential, (during production) [CO2 eq] | 4.52 kg |
| Ecological footprint — Global warming potential — global warming potential, (during operation) [CO2 eq] | 24.6 kg |
| Ecological footprint — Global warming potential — global warming potential, (after end of life cycle) [CO2 eq] | -0.373 kg |
| Use in hazardous areas — EAC Ex | No |
Ambient conditions
| Ambient temperature during operation — horizontal installation, min. | -30 °C |
| Ambient temperature during operation — horizontal installation, max. | 60 °C |
| Ambient temperature during operation — vertical installation, min. | -30 °C |
| Ambient temperature during operation — vertical installation, max. | 50 °C |
| Altitude during operation relating to sea level — Installation altitude above sea level, max. | 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200BL system manual |
Connection method
| Terminals — Conductor cross-section, min. | 0.14 mm²; follow detailed information in System manual of ET 200BL |
| Terminals — Conductor cross-section, max. | 2.5 mm²; follow detailed information in System manual of ET 200BL |
| Terminals — Number of process terminals to I/O module | 16 |
| Terminals — Number of terminals with connection to P1 and P2 bus | 2 |
Dimensions
| Width | 15 mm |
| Height | 117 mm |
| Depth | 74 mm |
Weights
| Weight, approx. | 81 g |
No matching specifications
Downloads & documentation
Official documents from Siemens, downloaded directly from the manufacturer.
Data sheets & manuals
6ES7135-8GD00-0AN0: frequently asked questions
When can 6ES7135-8GD00-0AN0 be shipped?
6ES7135-8GD00-0AN0 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 6ES7135-8GD00-0AN0 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 6ES7135-8GD00-0AN0 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 6ES7135-8GD00-0AN0, subject to availability and destination.
More Siemens parts