B&R 8B0F0160H000.000-1
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Passive line filter |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
| Weight | 0.85 kg |
Shipping & availability
When can 8B0F0160H000.000-1 be shipped?
8B0F0160H000.000-1 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 8B0F0160H000.000-1 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 8B0F0160H000.000-1 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 8B0F0160H000.000-1, subject to availability and destination.
Wide mains input voltage rangeOptimized for ACOPOSmulti 8B0P power supply modules and ACOPOS P3Compliance with limit values per CISPR11, group 2, class AIn order to conform to the EMC limit values, all 8BVI inverter modules in the drive system connected to the 8B0F line filter must be operated at the nominal switching frequency (5 kHz). The total length of all motor cables on each drive system (and for each 8B0F line filter) is not permitted to exceed 250 m. The cable length between the 8B0F line filter and the 8B0P power supply module is not permitted to exceed 5 m. The maximum permissible motor cable length per motor connection must also be taken into account (see 8BVI inverter modules). Line filter, passive, 16 A, 3x 528 VAC, 50/60 Hz, IP20
Specifications
Specifications
| Cooling and mounting type | Wall mounting |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | Not applicable |
| UL | cULus E225616Power conversion equipment |
| Permissible network configurations | TT, TN |
| Mains input voltage | Max. 3x 528 VAC |
| Frequency | Max. 60 Hz |
| Continuous current | 16 Aeff |
| Peak current | 24 Aeff (<1 min), 1x/h |
| Starting at 50°C | 0.164 A/K |
| Starting at 2000 m above sea level | 15 A up to 3000 m14.2 A up to 4000 m |
| Power dissipation | 6.1 W |
| Line filter per EN 61800-3, category C3 | Yes |
| L1, L2, L3 and L1´, L2´, L3´ | Terminals |
| PE | M5 threaded bolt |
| On mains | No |
| On device | No |
| With wire end sleeve | 0.25 to 6 mm² |
| UL/C-UL-US | 28 to 8 AWG |
| CSA | 28 to 8 AWG |
| Discharge capacitance | 0.4 µF |
| Leakage current | 33 mA |
| Hanging vertically | Yes |
| Horizontal, face up | Yes |
| Standing horizontally | Yes |
| Nominal | 5 to 40°C |
| Maximum | 55°C |
| Pollution degree per EN 61800-5-1 | PD 3 per EN 61800-5-1 and IEC 60664-1 |
| Overvoltage category per IEC 60950 | III |
| Overvoltage category per EN 61800-5-1 | III per EN 60664-1 |
| Degree of protection per EN 60529 | IP20 |
| Storage | 5 to 95% |
| Transport | Max. 95% at 40°C |
| Operation | 5 to 85% |
| Vibration and shock | 3M4 per IEC 60721-3-3 |
| Width | 45 mm |
| Height | 263.8 mm |
| Depth | 70 mm |
| Weight | 0.85 kg |
More B&R parts
UsedB&R 5C5001.01 IPC 5000 5D5500.06 Used
UsedB&R 5PC720.1505-K07 - 5P62:0A-03 Used