What is the B&R 8B0F0160H000.100-1?

Passive line filter, 16 A, 3x 528 VAC, 50/60 Hz, IP20, specially designed also for operation at 2.5 kHz

Specifications

General information

Certifications – CEYes
Certifications – UKCAYes
Certifications – CRA (Cyber Resilience Act)Not applicable
Certifications – ULUL E225616; Power conversion equipment
Certifications – ULcULus E225616; Power conversion equipment
Cooling and mounting typeWall mounting

Mains connection

Reduction of continuous current depending on ambient temperature – Starting at 50°C0.164 A/K
Reduction of continuous current depending on installation elevation – Starting at 2000 m above sea level15 A up to 3000 m; 14.2 A up to 4000 m
Variant – On mainsNo
Variant – On deviceNo
Variant – L1, L2, L3 and L1´, L2´, L3´Terminals
Variant – PEM5 threaded bolt
Terminal connection cross section – With wire end sleeve0.25 to 6 mm²
Terminal connection cross section – UL/C-UL-US28 to 8 AWG
Terminal connection cross section – CSA28 to 8 AWG
Permissible network configurationsTT, TNDelta/Wye with grounded wye neutral" in the USA."> (note: TT and TN power systems are commonly referred to as)
Mains input voltageMax. 3x 528 VAC
FrequencyMax. 60 Hz
Continuous current16 A eff (note: Valid under the following conditions: 3x 528 VAC mains input voltage, 50°C ambient temperature, cos phi = 0.8. The exact value depends on the application.)
Peak current24 A eff (<1 min), 1x/h
Power dissipation6.1 W (note: Valid under the following conditions: 25°C ambient temperature, frequency 50 Hz.)
Line filter per EN 61800-3, category C3Yes (note: Limit values from EN 61800-3 C3 (second environment).)

Electrical properties

Discharge capacitance0.54 µF (note: To simplify the design, the converted capacity on the DC bus is specified here.)
Leakage current47.3 mA (note: Valid under the following conditions: 400 VAC mains input voltage, 50 Hz frequency. NOTE: If two phases are interrupted, the leakage current can be up to 5.4 times higher in extreme cases.)

Operating conditions

Permissible mounting orientations – Hanging verticallyYes
Permissible mounting orientations – Horizontal, face upYes
Permissible mounting orientations – Standing horizontallyYes
Installation elevation above sea level – Nominal0 to 2000 m
Installation elevation above sea level – Maximum4000 m (note: Continuous operation at an installation elevation of 2000 m to 4000 m above sea level is possible taking the specified reduction of continuous current into account. Requirements that go beyond this must be arranged with B&R.)
Pollution degree per EN 61800-5-1PD 3 per EN 61800-5-1 and IEC 60664-1
Overvoltage category per IEC 60950III
Overvoltage category per EN 61800-5-1III per EN 60664-1
Degree of protection per EN 60529IP20

Ambient conditions

Temperature – Nominal5 to 40°C
Temperature – Maximum55°C (note: Continuous operation at an ambient temperature of 50°C to max. 55°C is possible when taking the specified reduction of continuous torque into account, but this results in premature aging of components.)
Temperature – Storage-25 to 55°C
Temperature – Transport-25 to 70°C
Relative humidity – Operation5 to 85%
Relative humidity – Storage5 to 95%
Relative humidity – TransportMax. 95% at 40°C

Mechanical properties

Dimensions – Width45 mm
Dimensions – Height263.8 mm
Dimensions – Depth70 mm
Vibration and shock3M4 per IEC 60721-3-3
Weight0.87 kg

Downloads & documentation

Official documents from B&R, downloaded directly from the manufacturer.

Data sheets & manuals

Certificates (1)

8B0F0160H000.100-1: frequently asked questions

When can 8B0F0160H000.100-1 be shipped?

8B0F0160H000.100-1 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up 8B0F0160H000.100-1 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for 8B0F0160H000.100-1 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 8B0F0160H000.100-1, subject to availability and destination.

More B&R parts

B&R 8B0C0320HW00.00A-1 – Input for connecting an external 24 VDC source (e.g. UPS)
B&R
8B0C0320HW00.00A-1

Input for connecting an external 24 VDC source (e.g. UPS)

B&R 8B0F0160H000.100-1Price and lead time confirmed within 1 business day
Request a Quote