Pepperl Fuchs KFD2-SRA-Ex4

Switch Amplifier

MPN
KFD2-SRA-Ex4
Price and lead time confirmed within 1 business day
Request a Quote
  1. 1We check stock, condition and lead time
  2. 2You get a written quote by email
  3. 3Approve it and we ship — in-stock parts within 1 business day

A real person replies, typically within 1 business day — see our privacy policy.

  • 12-month warranty (new) · 3-month (used/refurbished)
  • 30-day returns, no restocking fee on unused parts
  • 100% positive eBay feedback
  • Ships via

Have spare Pepperl Fuchs parts? We buy surplus →

What is the Pepperl Fuchs KFD2-SRA-Ex4?

4-channel isolated barrier

24 V DC supply (Power Rail)

Dry contact or NAMUR inputs

50 % less wiring, 2:1 technology

Relay contact output

Line fault detection (LFD)

Reversible mode of operation

4-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 50 % less wiring, 2:1 technology, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Housing width: 20 mm, Number of channels: 4-channel, 2:1 Method, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 4 x relay (NO contact), Reversible mode of operation

Specifications

General specifications

Order code (Pepperl+Fuchs part number)190176
Signal typeDigital Input
LifecycleActive (current Pepperl+Fuchs product)

Supply

ConnectionPower Rail or terminals 14+, 15-
Rated voltage19 ... 30 V DC Ur
Ripple≤ 10 %
Rated current45 ... 70 mA Ir
Power dissipation1.2 W

Input

Connection sidefield side
Connectionterminals 1-, 2+, 3-; 4-, 5+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Pulse/Pause ratiomin. 35 ms / min. 35 ms (non-AC operation) min. 70 ms / min. 70 ms (AC operation)
Line fault detectionbreakage I ≤ 0.15 mA , short-circuit I > 6 mA

Output

Connection sidecontrol side
Connectionoutput I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12
Output I ... IVSignal I ... Signal IV ; relay
Contact loading253 V AC/2 A /cos φ > 0.7; 40 V DC/2 A resistive load;
Energized/De-energized delayapprox. 30 ms / approx. 30 ms
Mechanical life5 x 106 switching cycles
Collective error messagePower Rail

Transfer characteristics

Switching frequency≤ 10 Hz (non-AC operation) ≤ 3 Hz (AC operation)

Galvanic isolation

Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Indicators/settings

Display elementsLEDs
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front

Directive conformity

Electromagnetic compatibility: Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EUEN 61010-1:2010

Conformity

Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000

Ambient conditions

Ambient temperature-20 ... 60 °C (-4 ... 140 °F)

Mechanical specifications

Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001

Data for application in connection with hazardous areas

EU-type examination certificateZELM 99 ATEX 0009
MarkingII (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
InputEx ia IIC
Voltage10 V Uo
Current14 mA Io
Power35 mW (linear characteristic) Po
Supply: Maximum safe voltage40 V DC (Attention! Um is no rated voltage.) Um
Output: Contact loading230 V AC + 10 % / 2 A / 100 VA / cos φ ≥ 0.7; 40 V DC / 2 A resistive load
Fault indication output: Maximum safe voltage40 V DC Um
Galvanic isolation: Input/inputnot available
Galvanic isolation: Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000

International approvals

UL approval: Control drawing116-0145
IECEx approval: IECEx certificateIECEx TUN 04.0003
IECEx approval: IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I

General information

Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

KFD2-SRA-Ex4: frequently asked questions

When can KFD2-SRA-Ex4 be shipped?

KFD2-SRA-Ex4 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up KFD2-SRA-Ex4 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for KFD2-SRA-Ex4 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-SRA-Ex4, subject to availability and destination.

More Pepperl Fuchs parts

Pepperl Fuchs KFD2-SR2-Ex2.W.SM – Standstill and Rotational Direction Monitor
Pepperl Fuchs
KFD2-SR2-Ex2.W.SM

Standstill and Rotational Direction Monitor

Pepperl Fuchs KFD2-STC4-Ex1 – SMART Transmitter Power Supply
Pepperl Fuchs
KFD2-STC4-Ex1

SMART Transmitter Power Supply

Pepperl Fuchs KFD2-STC5-1 – SMART Transmitter Power Supply
Pepperl Fuchs
KFD2-STC5-1

SMART Transmitter Power Supply

Pepperl Fuchs KFD2-SRA-Ex4Price and lead time confirmed within 1 business day
Request a Quote