Pepperl Fuchs KFD2-SR3-Ex2.2S
Switch Amplifier
- MPN
- KFD2-SR3-Ex2.2S
- Category
- K-System (DIN Rail Mounting)
Request a Quote
- 1We check stock, condition and lead time
- 2You get a written quote by email
- 3Approve it and we ship — in-stock parts within 1 business day
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- 100% positive eBay feedback
- Ships via
What is the Pepperl Fuchs KFD2-SR3-Ex2.2S?
2-channel isolated barrier
24 V DC supply (Power Rail)
Dry contact or NAMUR inputs
Usable as signal splitter (1 input and 2 outputs)
2 x 2 relay contact outputs with AND logic
Reversible mode of operation
Line fault detection (LFD)
Up to SIL 2 (SC 3) acc. to IEC/EN 61508
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Reversible mode of operation, Line fault detection (LFD), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 262112 |
| Signal type | Digital Input |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Functional safety related parameters
| Safety Integrity Level (SIL) | SIL 2 |
| Systematic capability (SC) | SC 3 |
Supply
| Connection | Power Rail or terminals 14+, 15- |
| Rated voltage | 19 ... 30 V DC Ur |
| Ripple | ≤ 10 % |
| Rated current | 30 ... 20 mA Ir |
| Power consumption | < 600 mW |
Input
| Connection side | field side |
| Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
| Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Output
| Connection side | control side |
| Connection | output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12 |
| Output I, II, III, IV | channel 1, 2; relay |
| Contact loading | 48 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive load |
| Minimum switch current | 1 mA / 24 V DC |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Mechanical life | 108 switching cycles |
| Collective error message | Power Rail |
Transfer characteristics
| Switching frequency | ≤ 10 Hz |
Galvanic isolation
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff |
| Output/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff |
Indicators/settings
| Display elements | LEDs |
| Control elements | DIP switch |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity
| Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 |
| Degree of protection | IEC 60529:2001 |
| Input | EN 60947-5-6:2000 |
Ambient conditions
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 150 g |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
| Height | 119 mm |
| Width | 20 mm |
| Depth | 115 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| EU-type examination certificate | EXA 16 ATEX 0001 X |
| Marking | II 3(1)G Ex nA nC [ia Ga] IIC T4 Gc [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Input | Ex ia |
| Voltage | 10.5 V Uo |
| Current | 17.1 mA Io |
| Power | 45 mW (linear characteristic) Po |
| Supply: Maximum safe voltage | 250 V AC (Attention! Um is no rated voltage.) Um |
| Output: Maximum safe voltage | 250 V AC (Attention! The rated voltage can be lower.) Um |
| Galvanic isolation: Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Galvanic isolation: Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals
| UL approval | E106378 |
| Control drawing | 116-0423 (cULus) |
| IECEx approval: IECEx certificate | IECEx EXA 16.0001X |
| IECEx approval: IECEx marking | Ex nA nC [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
Certificates (9)
- China SITIIAS CCC (2021322316003620 (Singapore))
- SITIIAS CCC Ex Certificate (2025322316006784 (Vietnam))
- Australia Test Safe (ANZEx 17.3006X)
- DNV Marine (TAA00001WX)
- Canada USA Certificate of Compliance UL cULus (CoC E106873 RepRef E106378-20190514)
- Europe EXA ATEX (EXA 16 ATEX 0001X)
- Worldwide exida Functional Safety Assessment (P+F 1408-047-C R039 Assessment Report V1 R1)
- United Kingdom CML UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G UKEX Category (M1) (CML 21UKEX21099X)
- EU Declaration of Conformity (Pepperl+Fuchs)
KFD2-SR3-Ex2.2S: frequently asked questions
When can KFD2-SR3-Ex2.2S be shipped?
KFD2-SR3-Ex2.2S is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KFD2-SR3-Ex2.2S in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KFD2-SR3-Ex2.2S and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-SR3-Ex2.2S, subject to availability and destination.
More Pepperl Fuchs parts