What is the Pepperl Fuchs KFD2-SR2-Ex2.W?
2-channel isolated barrier
24 V DC supply (Power Rail)
Dry contact or NAMUR inputs
Relay contact output
Line fault detection (LFD)
Reversible mode of operation
Up to SIL 2 (SC 3) acc. to IEC/EN 61508
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact)
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 203355 |
| Signal type | Digital Input |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Functional safety related parameters
| Safety Integrity Level (SIL) | SIL 2 |
| Systematic capability (SC) | SC 3 |
Supply
| Connection | Power Rail or terminals 14+, 15- |
| Rated voltage | 19 ... 30 V DC Ur |
| Ripple | ≤ 10 % |
| Rated current | ≤ 50 mA Ir |
| Power dissipation | ≤ 1 W |
| Power consumption | ≤ 1 W |
Input
| Connection side | field side |
| Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
| Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Output
| Connection side | control side |
| Connection | output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 |
| Output I, II | signal, relay |
| Contact loading | 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load |
| Minimum switch current | 2 mA / 24 V DC |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Mechanical life | 107 switching cycles |
| Collective error message | Power Rail |
Transfer characteristics
| Switching frequency | ≤ 10 Hz |
Galvanic isolation
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings
| Display elements | LEDs |
| Control elements | DIP switch |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Low voltage: Directive 2014/35/EU | EN 61010-1:2010+A1:2019+A1:2019/AC:2019 |
Conformity
| Electromagnetic compatibility | NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018 |
| Degree of protection | IEC 60529:1989+A1:1999+A2:2013 |
| Functional safety | IEC/EN 61508:2010 |
| Input | EN 60947-5-6:2000 |
Ambient conditions
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 150 g |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| EU-type examination certificate | PTB 00 ATEX 2080 |
| Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Input | Ex ia |
| Voltage | 10.5 V Uo |
| Current | 13 mA Io |
| Power | 34 mW (linear characteristic) Po |
| Supply: Maximum safe voltage | 253 V AC / 125 V DC (Attention! Um is no rated voltage.) Um |
| Output: Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) Um |
| Fault indication output: Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) Um |
| Certificate | PF 08 CERT 0803 |
| Marking | II (3)G [Ex ic Gc] IIC |
| Input | Ex ic |
| Voltage | 10.5 V Uo |
| Current | 13 mA Io |
| Power | 34 mW (linear characteristic) Po |
| Certificate | TÜV 99 ATEX 1493 X |
| Marking | II 3G Ex ec nC IIC T4 Gc |
| Galvanic isolation: Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Galvanic isolation: Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN IEC 60079-11:2024 , EN IEC 60079-15:2019 |
International approvals
| FM approval: FM certificate | FM19US0207X |
| FM approval: Control drawing | 116-0035 |
| UL approval | E106378 |
| Control drawing | 116-0473 (cULus) |
| Contact loading | 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load |
| IECEx approval: IECEx certificate | IECEx PTB 11.0034 , IECEx TUN 19.0013X |
| IECEx approval: IECEx marking | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
Certificates (10)
- Japan TIIS (TC16024)
- United Arab Emirates SGS Gulf Limited ECASEx (25-12-177291/E25-12-184403/NB0002)
- China SITIIAS CCC Ex Certificate (2020322316001439 (Bintan))
- Europe TUV II 3 G (TÜV 99 ATEX 1493X)
- Australia Test Safe (ANZEx 17.3006X)
- Brasil TUV Rheinland Brazil (TÜV 24.0794)
- EU Declaration of Conformity (Pepperl+Fuchs)
- South Africa MASC (MASC MS/17-0863)
- South Africa MASC (MASC S/22-8373X)
- DNV Marine (TAA00001WX)
KFD2-SR2-Ex2.W: frequently asked questions
When can KFD2-SR2-Ex2.W be shipped?
KFD2-SR2-Ex2.W is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KFD2-SR2-Ex2.W in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KFD2-SR2-Ex2.W and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-SR2-Ex2.W, subject to availability and destination.
More Pepperl Fuchs parts