Pepperl Fuchs KFD2-ST3-Ex2
Switch Amplifier
- MPN
- KFD2-ST3-Ex2
- Category
- K-System (DIN Rail Mounting)
Request a Quote
- 1We check stock, condition and lead time
- 2You get a written quote by email
- 3Approve it and we ship — in-stock parts within 1 business day
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- 100% positive eBay feedback
- Ships via
What is the Pepperl Fuchs KFD2-ST3-Ex2?
2-channel isolated barrier
24 V DC supply (Power Rail)
Dry contact or NAMUR inputs
Active transistor output
Line fault detection (LFD)
Reversible mode of operation
Up to SIL 2 (SC 3) acc. to IEC/EN 61508
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Active transistor output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (active)
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 262111 |
| Signal type | Digital Input |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Functional safety related parameters
| Safety Integrity Level (SIL) | SIL 2 |
| Systematic capability (SC) | SC 3 |
Supply
| Connection | Power Rail or terminals 14+, 15- |
| Rated voltage | 19 ... 30 V DC Ur |
| Ripple | ≤ 10 % |
| Rated current | 20 ... 15 mA + Iout Ir |
| Power dissipation | ≤ 900 mW including maximum power dissipation in the output |
Input
| Connection side | field side |
| Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
| Pulse/Pause ratio | min. 100 µs / min. 100 µs |
Output
| Connection side | control side |
| Connection | output I: terminal 7+ ; output II: terminal 9+ |
| Rated voltage | 30 V DC Ur |
| Rated current | 100 mA Ir |
| Response time | ≤ 200 µs |
| Signal level | 1-signal: (supply voltage) - 3 V max. for 100 mA 0-signal: blocked output (off-state current ≤ 10 µA) |
| Output I | signal ; Transistor |
| Output II | signal ; Transistor |
| Collective error message | Power Rail |
Transfer characteristics
| Switching frequency | ≤ 5 kHz |
Galvanic isolation
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings
| Display elements | LEDs |
| Control elements | DIP switch |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity
| Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 |
| Degree of protection | IEC 60529:2001 |
| Input | EN 60947-5-6:2000 |
Ambient conditions
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 150 g |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
| Height | 119 mm |
| Width | 20 mm |
| Depth | 115 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| EU-type examination certificate | EXA 16 ATEX 0016 X |
| Marking | II 3(1)G Ex nA [ia Ga] IIC T4 Gc [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Input | Ex ia |
| Voltage | 10.5 V Uo |
| Current | 17.1 mA Io |
| Power | 45 mW (linear characteristic) Po |
| Supply: Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) Um |
| Output: Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) Um |
| Galvanic isolation: Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Galvanic isolation: Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals
| UL approval | E106378 |
| Control drawing | 116-0424 (cULus) |
| IECEx approval: IECEx certificate | IECEx EXA 16.0009X |
| IECEx approval: IECEx marking | Ex nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
Certificates (10)
- Brasil TUV Rheinland Brazil (TÜV 23.1089 X (Vietnam))
- EU Declaration of Conformity (Pepperl+Fuchs)
- China SITIIAS CCC Ex Certificate (2020322316002751 (Singapore))
- Korea KOSHA (25-AV4BO-0124X)
- Australia Test Safe (ANZEx 22.3001)
- China SITIIAS CCC Ex Certificate (2025322316006411 (Vietnam))
- South Africa MASC (MASC MS/24-8467X)
- DNV Marine (TAA00001WX)
- Korea KOSHA (20-AV4BO-0492)
- Korea KOSHA (20-AV4BO-0493)
KFD2-ST3-Ex2: frequently asked questions
When can KFD2-ST3-Ex2 be shipped?
KFD2-ST3-Ex2 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KFD2-ST3-Ex2 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KFD2-ST3-Ex2 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-ST3-Ex2, subject to availability and destination.
More Pepperl Fuchs parts