Pepperl Fuchs KCD2-STC-Ex1.ES
SMART Transmitter Power Supply
- MPN
- KCD2-STC-Ex1.ES
- Category
- K-System (DIN Rail Mounting)
Request a Quote
- 1We check stock, condition and lead time
- 2You get a written quote by email
- 3Approve it and we ship — in-stock parts within 1 business day
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- 100% positive eBay feedback
- Ships via
What is the Pepperl Fuchs KCD2-STC-Ex1.ES?
1-channel isolated barrier
24 V DC supply (Power Rail)
Input for 2-wire SMART transmitters and current sources
Output for 4 mA ... 20 mA or 1 V ... 5 V
Sink or source mode
Line fault detection (LFD)
Housing width 12.5 mm
Up to SIL 3 acc. to IEC/EN 61508
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: 2-wire transmitter, Field device [2]: current source
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 322426 |
| Signal type | Analog input |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Functional safety related parameters
| Safety Integrity Level (SIL) | SIL 3 |
| Systematic capability (SC) | SC 3 |
Supply
| Connection | Power Rail or terminals 9+, 10- |
| Rated voltage | 19 ... 30 V DC Ur |
| Ripple | ≤ 10 % |
| Rated current | ≤ 50 mA Ir |
| Power dissipation | ≤ 800 mW |
| Power consumption | ≤ 1.2 W |
Input
| Connection side | field side |
| Connection | terminals 1+, 2-; 3+, 4- |
| Input signal | 4 ... 20 mA , limited to approx. 27 mA reverse polarity protected |
| Line fault detection | downscaling ≤ 3 mA ; upscaling ≥ 22 mA |
| Voltage drop | approx. 5 V on terminals 3+, 4- |
| Available voltage | ≥ 15 V at 20 mA terminals 1+, 2- |
Output
| Connection side | control side |
| Connection | terminals 5-, 6+ |
| Load | 0 ... 300 Ω (source mode) |
| Output signal | source mode: 4 ... 20 mA or 1 ... 5 V (internal resistor: 250 Ω, 0.1 %) sink mode: 4 ... 20 mA, operating voltage 16 ... 28 V For additional internal or external loads the voltage drop has to be considered, e. g. 250 Ω x 20 mA = 5 V. |
| Ripple | 20 mV rms |
Fault indication output
| Output type | fault bus signal , open collector transistor |
Transfer characteristics
| Deviation | at 20 °C (68 °F) ≤ ± 20 µA incl. calibration, linearity, hysteresis, loads and supply voltage fluctuations (source mode and sink mode 4 ... 20 mA) ≤ 10 mV incl. calibration, linearity, hysteresis and fluctuations of supply voltage (source mode 1 ... 5 V) |
| Influence of ambient temperature | < 0.5 mV/K (0 ... 70 °C (32 ... 158 °F)); < 1 mV/K (-20 ... 0 °C (-4 ... 32 °F)) (source mode 1 ... 5 V) |
| Frequency range | field side into the control side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) |
| Settling time | ≤ 200 ms |
| Rise time/fall time | ≤ 20 ms |
Galvanic isolation
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Output/power supply | Basic isolation acc. to EN 61010-1 rated insulation voltage ≤ 50 V |
Indicators/settings
| Display elements | LEDs |
| Control elements | DIP switch |
| Factory setting | output: current source |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity
| Electromagnetic compatibility | NE 21:2017 For further information see system description. |
| Degree of protection | IEC 60529:2001 |
Ambient conditions
| Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 100 g |
| Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2 |
| Height | 124 mm |
| Width | 12.5 mm |
| Depth | 114 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| EU-type examination certificate | CESI 10 ATEX 071 |
| Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Input | Ex ia |
| Supply: Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) Um |
| Equipment | terminals 1+, 2- |
| Voltage | 25.2 V Uo |
| Current | 100 mA Io |
| Power | 630 mW Po |
| Internal capacitance | 5.7 nF Ci |
| Internal inductance | negligible Li |
| Equipment | terminals 3+, 4- |
| Voltage | < 30 V Ui |
| Current | < 128 mA Ii |
| Voltage | 7.2 V Uo |
| Current | 100 mA Io |
| Power | 25 mW Po |
| Internal capacitance | 5.7 nF Ci |
| Internal inductance | negligible Li |
| Certificate | CESI 19 ATEX 005 X |
| Marking | II 3G Ex ec IIC T4 Gc |
| Directive conformity: Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015 |
International approvals
| UL approval | E106378 |
| Control drawing | 116-0378 (cULus) |
| IECEx approval: IECEx certificate | IECEx CES 11.0001X |
| IECEx approval: IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
Certificates (9)
- South Africa MASC (MASC MS/23-8149X)
- EU Declaration of Conformity (Pepperl+Fuchs)
- China SITIIAS CCC Ex Certificate (2020322316001399 (Singapore))
- China SITIIAS CCC Ex Certificate (2025322316006924 (Vietnam))
- DNV Marine (TAA00001WX)
- Europe CESI ATEX Category 3 G (CESI 19 ATEX 005X)
- Europe CESI ATEX Category I (M1) II (1) D II (1) G (CESI 10 ATEX 071)
- TÜV SÜD Functional Safety Certificate (C-IS-204399-01)
- Canada USA UL Certificate of Compliance Hazardous Location UL E106378 cULus (CoC E106378 RepRef E106378-20130719)
KCD2-STC-Ex1.ES: frequently asked questions
When can KCD2-STC-Ex1.ES be shipped?
KCD2-STC-Ex1.ES is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KCD2-STC-Ex1.ES in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KCD2-STC-Ex1.ES and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KCD2-STC-Ex1.ES, subject to availability and destination.
More Pepperl Fuchs parts