What is the Pepperl Fuchs KCD2-STC-Ex1.2O.ES?

1-channel isolated barrier

24 V DC supply (Power Rail)

Input for 2-wire SMART transmitters and current sources

Signal splitter (1 input and 2 outputs)

Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V

Terminal blocks with test sockets

Up to SIL 3 acc. to IEC/EN 61508

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: 2-wire transmitter

Specifications

General specifications

Order code (Pepperl+Fuchs part number)286746
Signal typeAnalog input
LifecycleActive (current Pepperl+Fuchs product)

Functional safety related parameters

Safety Integrity Level (SIL)SIL 3
Systematic capability (SC)SC 3

Supply

ConnectionPower Rail or terminals 9+, 10-
Rated voltage19 ... 30 V DC Ur
Ripplewithin the supply tolerance
Power dissipationapprox. 1.4 W at 20 mA transfer current, 250 Ω in both outputs
Power consumption2 W

Input

Connection sidefield side
Connectionterminals 1+, 2- (sink); 3+, 4- (source)
Input signal0/4 ... 20 mA
Voltage dropterminals 3, 4: ≤ 6.1 V at 20 mA
Short-circuit currentterminals 1+, 2-: 25 mA
Input resistanceterminals 1+, 2-: max. 500 Ω (BRAIN) (250 Ω load)
Available voltageterminals 1+, 2-: ≥ 16 V at 20 mA , ≥ 18.5 V at 4 mA

Output

Connection sidecontrol side
Connectionsource: terminals 5-, 6+; 7-, 8+ sink: terminals 5+, 6-, 7+, 8-
Loadchannel 1: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V) channel 2: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)
Output signal0/4 ... 20 mA or 0/1 ... 5 V
Ripplemax. 50 µA rms

Transfer characteristics

DeviationIout < 20 µA (0.1 %); Vout < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V
Influence of ambient temperaturecurrent output: 0.25 µA/K voltage output: 80 µV/K
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 6 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 6 kHz (-3 dB)
Settling time6 ms
Rise time/fall time2 ms

Galvanic isolation

Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Output/Outputfunctional insulation, rated insulation voltage 50 V AC

Indicators/settings

Display elementsLED
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front

Directive conformity

Electromagnetic compatibility: Directive 2014/30/EUEN 61326-1:2013 (industrial locations)

Conformity

Electromagnetic compatibilityNE 21:2012 EN 61326-3-2:2008
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012

Ambient conditions

Ambient temperature-20 ... 60 °C (-4 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions

Mechanical specifications

Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001

Data for application in connection with hazardous areas

EU-type examination certificateBASEEFA 13 ATEX 0077 X
MarkingII (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Supply: Maximum safe voltage250 V (Attention! The rated voltage can be lower.) Um
Equipmentterminals 1+, 2-
Voltage25.2 V Uo
Voltage28.2 V Uq
Current93 mA Io
Power656 mW Po
Internal capacitance10 nF Ci
Internal inductance0 mH Li
Equipmentterminals 3+, 4-
Voltage30 V Ui
Current115 mA Ii
Power700 mW Pi
Voltage5 V Uo
Current6.8 mA Io
Power1.6 mW Po
Output: Maximum safe voltage250 V (Attention! The rated voltage can be lower.) Um
CertificateBASEEFA 13 ATEX 0078 X
MarkingII 3G Ex nA IIC T4 Gc
Galvanic isolation: Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN IEC 60079-11:2024 , EN 60079-15:2010

International approvals

UL approval: Control drawing116-0380 (cULus)
IECEx approval: IECEx certificateIECEx BAS 13.0043X
IECEx approval: IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I

General information

NoteBoth output loads must be connected to ensure complete and correct operation within the technical specification.
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

KCD2-STC-Ex1.2O.ES: frequently asked questions

When can KCD2-STC-Ex1.2O.ES be shipped?

KCD2-STC-Ex1.2O.ES is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up KCD2-STC-Ex1.2O.ES in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for KCD2-STC-Ex1.2O.ES and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KCD2-STC-Ex1.2O.ES, subject to availability and destination.

More Pepperl Fuchs parts

Pepperl Fuchs KCD2-STC-1.2O – SMART Transmitter Power Supply
Pepperl Fuchs
KCD2-STC-1.2O

SMART Transmitter Power Supply

Pepperl Fuchs KCD2-STC-1.SP – SMART Transmitter Power Supply
Pepperl Fuchs
KCD2-STC-1.SP

SMART Transmitter Power Supply

Pepperl Fuchs KCD2-STC-Ex1 – SMART Transmitter Power Supply
Pepperl Fuchs
KCD2-STC-Ex1

SMART Transmitter Power Supply

Pepperl Fuchs KCD2-UT2-1 – Universal Temperature Converter
Pepperl Fuchs
KCD2-UT2-1

Universal Temperature Converter

Pepperl Fuchs KCD2-STC-Ex1.2O.ESPrice and lead time confirmed within 1 business day
Request a Quote