B&R X20AT6402

I/O module, 6 inputs for thermocouples

MPN
X20AT6402
Price and lead time confirmed within 1 business day
Request a Quote

A real person replies, typically within 1 business day — see our privacy policy.

  • 12-month warranty (new) · 3-month (used/refurbished)
  • 30-day returns, no restocking fee on unused parts
  • Ships via

What is the B&R X20AT6402?

6 inputs for thermocouples

For sensor types J, K, N, S, B, R

Additional direct raw value measurement

Integrated terminal temperature compensation

Configurable filter time

Configurable resolution

The module is equipped with 6 inputs for J, K, N, S, B and R thermocouple sensors. The module has an integrated terminal temperature compensation.

Specifications

Short description

I/O module6 inputs for thermocouples

General information

Diagnostics – Module run/errorYes, using LED status indicator and software
Diagnostics – InputsYes, using LED status indicator and software
Power consumption – Bus0.01 W
Power consumption – Internal I/O0.91 W
Certifications – CEYes
Certifications – UKCAYes
Certifications – CRA (Cyber Resilience Act)In preparation
Certifications – ATEXZone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X
Certifications – ULcULus E115267; Industrial control equipment
Certifications – HazLoccCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5
Certifications – DNVTemperature: B (0 to 55°C); Humidity: B (up to 100%); Vibration: B (4 g); EMC: B (bridge and open deck)
Certifications – CCSYes
Certifications – LRENV1
Certifications – KRYes
Certifications – ABSYes
Certifications – BVEC33B ; Temperature: 5 - 55°C; Vibration: 4 g; EMC: Bridge and open deck
Certifications – KCYes
B&R ID code0x1BA9
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]-

Thermocouple temperature inputs

Conversion time – 1 channel80.4 ms with 50 Hz filter
Conversion time – N channels(n + 1) x 40.2 ms with 50 Hz filter
Measurement range – Type J: Fe-CuNi-210 to 1200°C
Measurement range – Type K: NiCr-Ni-270 to 1372°C
Measurement range – Type N: NiCrSi-NiSi-270 to 1300°C (Rev. ≥D0)
Measurement range – Type S: PtRh10-Pt-50 to 1768°C
Measurement range – Type B: PtRh30-PtRh60 to 1820°C
Measurement range – Type R: PtRh13-Pt-50 to 1664°C
Measurement range – Terminal temperature-25 to 85°C
Measurement range – Raw value±65.534 mV
Resolution – Sensor temperature1 LSB = 0.1°C or 0.01°C
Resolution – Terminal temperature1 LSB = 0.1°C
Resolution – Raw value output with respect to gain1 LSB = 1 µV or 2 µV
Normalization – Type J: Fe-CuNi-210.0 to 1200.0°C or -210.00 to 1200.00°C
Normalization – Type K: NiCr-Ni-270.0 to 1372.0°C or -270.00 to 1372.00°C
Normalization – Type N (Rev. ≥D0)-270.0 to 1300.0°C or -270.00 to 1300.00°C
Normalization – Type S: PtRh10-Pt-50.0 to 1768.0°C or -50.00 to 1768.00°C
Normalization – Type B: PtRh30-PtRh60 to 1820.0°C or 0 to 1820.00°C
Normalization – Type R: PtRh13-Pt-50.0 to 1664.0°C or -50.00 to 1664.00°C
Normalization – Terminal temperature-25.0 to 85.0°C or -25.00 to 85.00°C
Monitoring – Range undershoot0x8001
Monitoring – Range overshoot0x7FFF
Monitoring – Open circuit0x7FFF
Monitoring – Open inputs0x7FFF
Monitoring – General fault0x8000
Max. error at 25°C – Type J: Fe-CuNi±0.04% (note: Based on the entire measurement range.)
Max. error at 25°C – Type K: NiCr-Ni±0.05% (note: Based on the entire measurement range.)
Max. error at 25°C – Type N (Rev. ≥D0)±0.05% (note: Based on the entire measurement range.)
Max. error at 25°C – Type S: PtRh10-Pt±0.11% (note: Based on the entire measurement range.)
Max. error at 25°C – Type B: PtRh30-PtRh6±0.13% (note: Based on the entire measurement range.)
Max. error at 25°C – Type R: PtRh13-Pt±0.09% (note: Based on the entire measurement range.)
Max. error at 25°C – Gain±0.06% (note: Based on the current measured value.)
Max. offset drift – Type J: Fe-CuNi±0.0019%/°C (note: Based on the entire measurement range.)
Max. offset drift – Type K: NiCr-Ni±0.0024%/°C (note: Based on the entire measurement range.)
Max. offset drift – Type N (Rev. ≥D0)±0.0029%/°C (note: Based on the entire measurement range.)
Max. offset drift – Type S: PtRh10-Pt±0.0079%/°C (note: Based on the entire measurement range.)
Max. offset drift – Type B: PtRh30-PtRh6±0.0114%/°C (note: Based on the entire measurement range.)
Max. offset drift – Type R: PtRh13-Pt±0.0074%/°C (note: Based on the entire measurement range.)
Common-mode rejection – DC>70 dB
Common-mode rejection – 50 Hz>70 dB
Insulation voltage – Between channel and bus500 V eff
Terminal temperature compensation precision – With artificial convection±4°C after 10 min
Terminal temperature compensation precision – With natural convection±2°C after 10 min
InputThermocouple
Digital converter resolution16-bit
Filter timeConfigurable between 1 ms and 66.7 ms
Output formatINT
Terminal temperature compensationInternal
Sensor standardEN 60584
Conversion procedureSigma-delta
Linearization methodInternal
Permissible input signalMax. ±5 V
Input filterFirst-order low-pass filter / cutoff frequency 500 Hz
Max. gain drift±0.01%/°C (note: Based on the current measured value.)
Nonlinearity±0.001% (note: Based on the entire measurement range.)
Common-mode range±15 V
Crosstalk between channels<-70 dB

Electrical properties

Electrical isolationChannel isolated from bus; Channel not isolated from channel

Operating conditions

Mounting orientation – HorizontalYes
Mounting orientation – VerticalYes
Installation elevation above sea level – 0 to 2000 mNo limitation
Installation elevation above sea level – >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20

Ambient conditions

Temperature – Horizontal mounting orientation0 to 55°C
Temperature – Vertical mounting orientation0 to 50°C
Temperature – Derating-
Temperature – Storage-40 to 85°C
Temperature – Transport-40 to 85°C
Relative humidity – Operation5 to 95%, non-condensing
Relative humidity – Storage5 to 95%, non-condensing
Relative humidity – Transport5 to 95%, non-condensing

Mechanical properties

NoteOrder 1x terminal block X20TB12 separately.; Order 1x bus module X20BM11 separately.
Pitch12.5 +0.2 mm

Accessories

Required accessories (order separately)

X20BM15Bus modules — The bus module is the base for all X20 24 VDC I/O modules; The internal I/O supply is interconnected; Manual node number assignment; Indepe…
X20BM11Bus modules — Bus module for 24 VDC I/O modules; The internal I/O power supply is connected through. The bus module is the base for all 24 VDC I/O module…
X20TB12Terminal blocks — Tool-free wiring with push-in technology; Simple wire release using lever; Ability to label each terminal; Plain text labeling also possibl…

Downloads & documentation

Official documents from B&R, downloaded directly from the manufacturer.

Data sheets & manuals

CAD & dimension drawings

Certificates (16)

X20AT6402: frequently asked questions

When can X20AT6402 be shipped?

X20AT6402 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up X20AT6402 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for X20AT6402 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for X20AT6402, subject to availability and destination.

More B&R parts

B&R X20AT2311 – I/O module, 2 inputs for PT100 resistance temperature…
B&R
X20AT2311

I/O module, 2 inputs for PT100 resistance temperature…

B&R X20AT2402 – I/O module, 2 inputs for thermocouples
B&R
X20AT2402

I/O module, 2 inputs for thermocouples

B&R X20AT4222 – I/O module, 4 inputs for Pt100 or Pt1000 resistance…
B&R
X20AT4222

I/O module, 4 inputs for Pt100 or Pt1000 resistance…

B&R X20AT4232 – I/O module, 4 inputs for NTC (10 kΩ) resistance temperature…
B&R
X20AT4232

I/O module, 4 inputs for NTC (10 kΩ) resistance temperature…

B&R X20ATA312 – I/O module, 2 inputs for Pt100 resistance temperature…
B&R
X20ATA312

I/O module, 2 inputs for Pt100 resistance temperature…

B&R X20ATA492 – I/O module, 2 inputs for thermocouples
B&R
X20ATA492

I/O module, 2 inputs for thermocouples

B&R X20ATB312 – I/O module, 4 inputs for Pt100 resistance temperature…
B&R
X20ATB312

I/O module, 4 inputs for Pt100 resistance temperature…

B&R X20ATC402 – I/O module, 6 inputs for thermocouples
B&R
X20ATC402

I/O module, 6 inputs for thermocouples

B&R X20AT6402Price and lead time confirmed within 1 business day