Relay module; Nominal input voltage: 24 V AC/DC; 1 changeover contact; Limiting continuous current: 6 A; with gold contacts; Yellow status indicator; Module width: 6 mm
Isolation amplifier; Current and voltage input signal; Current and voltage output signal; Zero/span adjustment; Configuration via DIP switch; Supply voltage: 24 VDC; 6 mm module width; 2,50 m
Short description:
WAGO's configurable signal conditioner converts, amplifies, filters and electrically isolates standard analog signals.
Features:
Calibrated measurement range switching
Switchable limit frequency
| Safety Information | Input and output must be safely isolated from any hazardous live parts! |
| Note | Use shielded signal cables!Only use shielded signal cables for analog input and output signals.This ensures the device maintains its specified accuracy and immunity to interference, even when external disturbances affect the signal cable., The 3 (Us+), 7 (Us+), 4 (GND 3) and 8 (GND 3) connections are internally commoned.Current carrying capacity between 3/4 and 7/8 connections: 1 A (max.) |
| Configuration options | DIP switch, Potentiometer |
| Input signal type | Voltage, Current |
| Input signal (voltage) | 0 … 5 V, 1 … 5 V, 0 … 10 V, 2 … 10 V (calibrated, switchable) |
| Input signal (current) | 0 … 20 mA, 4 … 20 mA (calibrated, switchable) |
| Input resistance (current input) | ≤ 50 Ω |
| Input resistance (voltage input) | ≥ 100 kΩ |
| Input current (max.) | 50 mA |
| Input voltage (max.) | 30 V |
| Zero/span adjustment | ±3 % of upper range value |
| Output signal type | Current, Voltage |
| Output signal (voltage) | 0 … 5 V, 1 … 5 V, 0 … 10 V, 2 … 10 V (calibrated (as delivered), switchable) |
| Output signal (current) | 0 … 20 mA, 4 … 20 mA, 0 … 10 mA, 2 … 10 mA (calibrated (as delivered), switchable) |
| Load impedance (voltage output) | ≥ 2 kΩ |
| Load impedance (current output) | ≤ 600 Ω |
| Limit frequency | 100 Hz / 5 kHz (configurable via DIP switch) |
| Step response (typ.) | 3.5 ms (100 Hz), 100 µs (5 kHz) |
| Transmission error (typ.) | ≤ 0.1 % of upper-range value |
| Transmission error (max.) | ≤ 0.2 % of upper-range value |
| Transmission error (under interference) | ≤ 15 % of upper-range value |
| Temperature coefficient | ≤ 0.01 %/K |
| Power supply type | 24 VDC (SELV) |
| Nominal supply voltage U<sub>S</sub> | 24 VDC |
| Supply voltage range | ±30 % |
| Current consumption (default) | ≤ 30 mA |
| Current consumption (max.) | ≤ 40 mA (Iout 20 mA; Load impedance: 600 Ω; Us: 16.8 V) |
| Rated voltage | 300 V |
| Protection type | IP20 |
| Test voltage (input/output/supply) | 3 kVAC; 50 Hz; 1 min |
| Overvoltage category | II |
| Pollution degree | 2 |
| Insulation type (input/analog output/supply) | Functional insulation |
| Insulation type (adjacent devices) | Reinforced insulation (safe isolation) |
| Connection technology | Push-in CAGE CLAMP® |
| Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
| Fine-stranded conductor | 0.34 … 2.5 mm² / 22 … 14 AWG |
| Strip length | 9 … 10 mm / 0.35 … 0.39 inches |
| Width | 6 mm / 0.236 inches |
| Height | 94 mm / 3.701 inches |
| Depth from upper-edge of DIN-rail | 97.8 mm / 3.85 inches |
| Mounting type | DIN-35 rail |
| Insulation material (main housing) | Polyamide (PA66) |
| Flammability class per UL94 | V0 |
| Fire load | 0.363 MJ |
| Weight | 43 g |
| Ambient temperature (operation) | -25 … +70 °C |
| Ambient temperature (storage) | -40 … +85 °C |
| Processing temperature | -25 … +50 °C |
| Temperature range of connection cable | ≥ (Tambient + 25 K) |
| Relative humidity | 5 … 95 % (no condensation permissible) |
| Operating altitude (max.) | 2000 m |
| Conformity marking | CE |
| EMC immunity to interference | EN 61000-6-2 |
| EMC emission of interference | EN 61000-6-4 |
| Standards/specifications | EN 61010-1, DNV, UL 508 |
| Product Group | 6 (INTERFACE ELECTRONIC) |
| PU (SPU) | 1 pcs |
| Packaging type | bag |
| Country of origin | DE |
| GTIN | 4045454471293 |
| Customs tariff number | 85437090300 |
| UNSPSC | 39121008 |
| eCl@ss 10.0 | 27-21-01-20 |
| eCl@ss 9.0 | 27-21-01-20 |
| ETIM 9.0 | EC002653 |
| ETIM 10.0 | EC002653 |
| ECCN | NO US CLASSIFICATION |
| CAS-No. | 1303-86-2, 1317-36-8, 7439-92-1, 75980-60-8 |
| REACH Candidate List Substance | Diboron trioxide, Lead, Lead monoxide, Phosphine oxide, diphenyl(2,4,6-trimethylbenzoyl)- |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 6(c), 7(a), 7(c)-I, 7(c)-II |
| SCIP notification number (Austria) | 61dc3753-5e53-4bb5-9a50-f5aa17855efd |
| SCIP notification number (Belgium) | c0cac427-821b-4fee-853d-e625623f7640 |
| SCIP notification number (Bulgaria) | b870ee7e-96a6-4693-a71e-ca604ee0becd |
| SCIP notification number (Czech Republic) | e7e38323-7816-4bca-823d-3b7279f03a44 |
| SCIP notification number (Denmark) | 6601305f-f71c-49d0-b0a8-1bb00e9b10a9 |
| SCIP notification number (Finland) | f0f87a08-b417-4804-bef3-c3544e6ec13a |
| SCIP notification number (France) | 7fece020-0230-4fff-8cee-bf52a792d4d6 |
| SCIP notification number (Germany) | 197024b5-9ab4-47ce-ad91-4e9856e8eff0 |
| SCIP notification number (Hungary) | 32b8cc06-78ff-4b21-86dd-dbc709b88954 |
| SCIP notification number (Italy) | 1a3b35dc-ce7d-420c-9c23-318120ddc4e0 |
| SCIP notification number (Netherlands) | b772c60e-9cbe-49e9-8f7d-522704ecfa81 |
| SCIP notification number (Poland) | dd653e15-62aa-4136-bfb4-6c245822ff06 |
| SCIP notification number (Romania) | 7347c6f8-21e0-4fd4-ab8f-e32d7983d5cc |
| SCIP notification number (Sweden) | dd90bd68-e44b-432d-98d3-fe7c80da2930 |
No matching specifications
857-400 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 857-400 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 857-400, subject to availability and destination.

Relay module; Nominal input voltage: 24 V AC/DC; 1 changeover contact; Limiting continuous current: 6 A; with gold contacts; Yellow status indicator; Module width: 6 mm

Relay module; Nominal input voltage: 230 V AC/DC; 1 changeover contact; Limiting continuous current: 6 A; with gold contacts; Yellow status indicator; Module width: 6 mm; 2,50 mm²; gray

Relay module; Nominal input voltage: 230 VAC; 1 changeover contact; Limiting continuous current: 6 A; with gold contacts; with integrated base load module; Yellow status indicator; Module wid

Relay module; Nominal input voltage: 24 … 230 V AC/DC; 1 changeover contact; Limiting continuous current: 6 A; with gold contacts; Yellow status indicator; Module width: 6 mm

Isolation amplifier; Current and voltage input signal; Current and voltage output signal; Digital output; Supply voltage: 24 VDC; 6 mm module width; 2,50 mm²

Isolation amplifier; Current and voltage input signal; Bipolar current and voltage output signal; Configuration via DIP switch; Supply voltage: 24 VDC; 6 mm module width; 2,50 mm²

Isolation amplifier; Bipolar current and voltage input signal; Bipolar current and voltage output signal; Zero/span adjustment; Configuration via DIP switch; Supply voltage: 24 VDC; 6 mm modu

Isolation amplifier; Current input signal; Current output signal; Supply voltage: 24 VDC; 6 mm module width; 2,50 mm²