What is the Siemens 6ES7144-4JF00-0AB0?

SIMATIC DP, Electronic modules for ET 200 PRO 4 AI RTD High Feature, Pt100; PT200; PT500; Pt1000; NI100; NI200; NI500; NI1000; Channel diagnostics; incl. bus module, Connection module IO 6ES7194-4..00-0AA0 order separately

Specifications

Supply voltage

Rated value (DC)24 V
Reverse polarity protectionYes; against destruction

Input current

from supply voltage 1L+, max.27 mA; Typical
from backplane bus 3.3 V DC, max.10 mA; Typical

Power loss

Power loss, typ.0.7 W

Address area

Address space per module — Address space per module, max.8 byte

Analog inputs

Number of analog inputs4
Constant measurement current for resistance-type transmitter, typ.1.25 mA; 1.25 / 0.5 mA depending on measuring range
Cycle time (all channels) max.83 ms; 83 ms at 50 Hz; 69 ms at 60 Hz
Technical unit for temperature measurement adjustableYes; Degrees Celsius/degrees Fahrenheit
Input ranges (rated values), resistance thermometer — Cu 10No
Input ranges (rated values), resistance thermometer — Ni 100Yes
Input ranges (rated values), resistance thermometer — Ni 100 — Input resistance (Ni 100)10 000 kΩ
Input ranges (rated values), resistance thermometer — Ni 1000Yes
Input ranges (rated values), resistance thermometer — Ni 1000 — Input resistance (Ni 1000)10 000 kΩ
Input ranges (rated values), resistance thermometer — Ni 120Yes
Input ranges (rated values), resistance thermometer — Ni 120 — Input resistance (Ni 120)10 000 kΩ
Input ranges (rated values), resistance thermometer — Ni 200Yes
Input ranges (rated values), resistance thermometer — Ni 200 — Input resistance (Ni 200)10 000 kΩ
Input ranges (rated values), resistance thermometer — Ni 500Yes
Input ranges (rated values), resistance thermometer — Ni 500 — Input resistance (Ni 500)10 000 kΩ
Input ranges (rated values), resistance thermometer — Pt 100Yes
Input ranges (rated values), resistance thermometer — Pt 100 — Input resistance (Pt 100)10 000 kΩ
Input ranges (rated values), resistance thermometer — Pt 1000Yes
Input ranges (rated values), resistance thermometer — Pt 1000 — Input resistance (Pt 1000)10 000 kΩ
Input ranges (rated values), resistance thermometer — Pt 200Yes
Input ranges (rated values), resistance thermometer — Pt 200 — Input resistance (Pt 200)10 000 kΩ
Input ranges (rated values), resistance thermometer — Pt 500Yes
Input ranges (rated values), resistance thermometer — Pt 500 — Input resistance (Pt 500)10 000 kΩ
Input ranges (rated values), resistors — 0 to 150 ohmsYes
Input ranges (rated values), resistors — 0 to 150 ohms — Input resistance (0 to 150 ohms)10 000 kΩ
Input ranges (rated values), resistors — 0 to 300 ohmsYes
Input ranges (rated values), resistors — 0 to 300 ohms — Input resistance (0 to 300 ohms)10 000 kΩ
Input ranges (rated values), resistors — 0 to 600 ohmsYes
Input ranges (rated values), resistors — 0 to 600 ohms — Input resistance (0 to 600 ohms)10 000 kΩ
Input ranges (rated values), resistors — 0 to 3000 ohmsYes
Input ranges (rated values), resistors — 0 to 3000 ohms — Input resistance (0 to 3000 ohms)10 000 kΩ
Input ranges (rated values), resistors — PTCYes
Input ranges (rated values), resistors — PTC — Input resistance (PTC)10 000 kΩ
Characteristic linearization — parameterizableYes
Characteristic linearization — parameterizable — for resistance thermometerPtxxx, Nixxx
Cable length — shielded, max.30 m

Analog value generation for the inputs

Measurement principleintegrating
Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max.15 bit; at 150, 300, 600 und 3 000 ohms; otherwise 15 bits + sign
Integration and conversion time/resolution per channel — Integration time (ms)20 / 16,667
Integration and conversion time/resolution per channel — Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Integration and conversion time/resolution per channel — Conversion time (per channel)20.625 ms; 20.625 ms at 50 Hz; 17.25 ms at 60 Hz
Smoothing of measured values — ParameterizableYes
Smoothing of measured values — Step: NoneYes; 1x cycle time
Smoothing of measured values — Step: lowYes; 4x cycle time
Smoothing of measured values — Step: MediumYes; 16x cycle time
Smoothing of measured values — Step: HighYes; 64x cycle time

Encoder

Connection of signal encoders — for resistance measurement with two-wire connectionYes; Line resistances are also measured
Connection of signal encoders — for resistance measurement with three-wire connectionYes
Connection of signal encoders — for resistance measurement with four-wire connectionYes

Errors/accuracies

Linearity error (relative to input range), (+/-)0.05 %
Temperature error (relative to input range), (+/-)0.002 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.015 %
Operational error limit in overall temperature range — Resistance thermometer, relative to input range, (+/-)0.175 %
Basic error limit (operational limit at 25 °C) — Resistance thermometer, relative to input range, (+/-)0.125 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency — Series mode interference (peak value of interference < rated value of input range), min.50 dB
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency — Common mode interference (USS < 2.5 V), min.70 dB; Interference voltage < 5 V
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency — Common mode interference (USS < 2.5 V), min.70 dB; Interference voltage < 5 V

Interrupts/diagnostics/status information

Diagnostics functionYes
Alarms — Diagnostic alarmYes; Parameterizable
Alarms — Hardware interruptNo
Diagnoses — Diagnostic information readableYes
Diagnoses — Wire breakYes
Diagnoses — Overflow/UnderflowYes
Diagnostics indication LED — Group error SF (red)Yes

Potential separation

Potential separation analog inputs — between the channelsNo
Potential separation analog inputs — between the channels and backplane busYes

Permissible potential difference

between the inputs (UCM)5 Vpp AC

Isolation

Isolation tested with707 V DC (type test)

Dimensions

Width45 mm
Height130 mm
Depth35 mm

Weights

Weight, approx.150 g

Downloads & documentation

Official documents from Siemens, downloaded directly from the manufacturer.

Data sheets & manuals

6ES7144-4JF00-0AB0: frequently asked questions

When can 6ES7144-4JF00-0AB0 be shipped?

6ES7144-4JF00-0AB0 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up 6ES7144-4JF00-0AB0 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for 6ES7144-4JF00-0AB0 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 6ES7144-4JF00-0AB0, subject to availability and destination.

More Siemens parts

Siemens 6ES7143-6BH00-0BB0 – SIMATIC ET 200eco PN, DIQ 16x 24 V DC/0.5 A/2 A, M12-L, 8x M12, double assignment, input type 3 (IEC 61131)
Siemens
6ES7143-6BH00-0BB0

SIMATIC ET 200eco PN, DIQ 16x 24 V DC/0.5 A/2 A, M12-L

Siemens 6ES7143-7BH00-0BB0 – SIMATIC ET 200clean, DIQ 16x 24 V DC/0.5 A, 8x M12, double assignment, input type 3 (IEC 61131)
Siemens
6ES7143-7BH00-0BB0

SIMATIC ET 200clean, DIQ 16x 24 V DC/0.5 A, 8x M12

Siemens 6ES7144-4FF01-0AB0 – SIMATIC DP, Electronic module for ET 200 PRO 4 AI U High Feature, +-10 V; 0...10 V; +-5 V; 1...5V
Siemens
6ES7144-4FF01-0AB0

SIMATIC DP, Electronic module for ET 200 PRO 4 AI U High…

Siemens 6ES7144-4GF01-0AB0 – SIMATIC DP, Electronic module for ET 200 PRO 4 AI I High Feature, +-20 mA; 0...20 mA; 4-20mA
Siemens
6ES7144-4GF01-0AB0

SIMATIC DP, Electronic module for ET 200 PRO 4 AI I High…

Siemens 6ES7145-4GF00-0AB0 – SIMATIC DP, Electronic modules for ET 200 PRO 4 AO I High Feature, +-20 mA; 0...20 mA; 4-20mA
Siemens
6ES7145-4GF00-0AB0

SIMATIC DP, Electronic modules for ET 200 PRO 4 AO I High…

Siemens 6ES7145-5ND00-0BA0 – SIMATIC ET 200AL, AQ 4xU/I, 4xM12, Degree of protection IP67
Siemens
6ES7145-5ND00-0BA0

SIMATIC ET 200AL, AQ 4xU/I, 4xM12, Degree of protection IP67

Siemens 6ES7146-5FF00-0BA0 – SIMATIC DP, ET 200AL, F-DI 4+F-DQ 2x24 V DC/2 A, 4xM12, PROFIsafe, up to PL e (ISO 13849)
Siemens
6ES7146-5FF00-0BA0

SIMATIC DP, ET 200AL, F-DI 4+F-DQ 2x24 V DC/2 A, 4xM12

Siemens 6ES7147-4BB00-0AA0 – SIMATIC DP, electronic modules for ET 200pro EM 2 SSI position detection for 2 SSI absolute encoders incl.…
Siemens
6ES7147-4BB00-0AA0

SIMATIC DP, electronic modules for ET 200pro EM 2 SSI…

Siemens 6ES7144-4JF00-0AB0Price and lead time confirmed within 1 business day
Request a Quote