Pepperl Fuchs VBA-4E2A-KE1-Z/E2

AS-Interface sensor/actuator module

MPN
VBA-4E2A-KE1-Z/E2
Category
Modules
Price and lead time confirmed within 1 business day
Request a Quote
  1. 1We check stock, condition and lead time
  2. 2You get a written quote by email
  3. 3Approve it and we ship — in-stock parts within 1 business day

A real person replies, typically within 1 business day — see our privacy policy.

  • 12-month warranty (new) · 3-month (used/refurbished)
  • 30-day returns, no restocking fee on unused parts
  • 100% positive eBay feedback
  • Ships via

Have spare Pepperl Fuchs parts? We buy surplus →

What is the Pepperl Fuchs VBA-4E2A-KE1-Z/E2?

A/B node with extended addressing possibility for up to 62 nodes

Housing with removable terminals

Communication monitoring

Inputs for 2-wire sensors and mechanical contacts

Addressing jack

Power supply of outputs from the external auxiliary voltage

Power supply of inputs from the module

Function display for bus, ext. auxiliary voltage, inputs and outputs

KE1 switch cabinet module, 4 inputs and 2 outputs

Specifications

General specifications

Order code (Pepperl+Fuchs part number)117993
Node typeA/B node
AS-Interface specificationV2.1
Required gateway specification≥ V2.1
ProfileS-7.A.0
IO code7
ID codeA
ID1 code7
ID2 code0
UL File NumberE223772
LifecycleActive (current Pepperl+Fuchs product)

Indicators/operating means

LED FAULTerror display; LED red red: communication error or address is 0 red flashing: overload of outputs
LED PWRAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 2 LED yellow

Electrical specifications

Auxiliary voltage (output)20 ... 30 V DC PELV UAUX
Rated operating voltage26.5 ... 31.6 V from AS-Interface Ue
Rated operating current≤ 25 mA (without sensors) / max. 60 mA Ie
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)

Input

Number/Type4 inputs for 2-wire sensors (PNP), DC or for mechanical contacts
Supplyfrom AS-Interface
Input current≤ 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 2 mA
1 (attenuated)≥ 4 mA
Signal delay< 2 ms (input/AS-Interface)
Signal frequency≤ 250 Hz

Output

Number/Type2 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Voltage≥ (UAUX - 0.5 V)
CurrentO1/O2 max. 1.5 A, total 3 A (TB ≤ 40 °C) O1/O2 max. 1 A, total 2 A (TB ≤ 70 °C)
Usage categoryDC-13

Directive conformity

Electromagnetic compatibility: Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001

Standard conformity

Degree of protectionEN 60529:2000
InputEN 61131-2:2007
Emitted interferenceEN 61000-6-4:2001
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2001

Ambient conditions

Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity90 % , non-condensing
Pollution degree2

Mechanical specifications

Degree of protectionIP20
Connectionremovable terminalsrated connection capacity:rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2for multiple-wire connection with two wires of equal cross-section:flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material: HousingPA 66-FR
Mass80 g
Dimensions: Height48.5 mm
Dimensions: Width22.5 mm
Dimensions: Length99.6 mm
MountingDIN mounting rail

VBA-4E2A-KE1-Z/E2: frequently asked questions

When can VBA-4E2A-KE1-Z/E2 be shipped?

VBA-4E2A-KE1-Z/E2 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up VBA-4E2A-KE1-Z/E2 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for VBA-4E2A-KE1-Z/E2 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for VBA-4E2A-KE1-Z/E2, subject to availability and destination.

More Pepperl Fuchs parts

Pepperl Fuchs VBA-4E-KE5-IL – AS-Interface analog module
Pepperl Fuchs
VBA-4E-KE5-IL

AS-Interface analog module

Pepperl Fuchs VBA-4E-KE5-ZEJQ – AS-Interface sensor/actuator module
Pepperl Fuchs
VBA-4E-KE5-ZEJQ

AS-Interface sensor/actuator module

Pepperl Fuchs VBA-4E2A-KE1-Z/E2Price and lead time confirmed within 1 business day
Request a Quote