What is the Pepperl Fuchs VBA-4E-KE5-IL?
Housing with push-in connection technology and mechanically coded terminal blocks
Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
Sensors supplied from the external auxiliary voltage
Function display for bus, external auxiliary voltage and inputs
Switch cabinet module, 4 analog Inputs
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 288594 |
| Node type | Standard node |
| AS-Interface specification | V3.0 |
| Required gateway specification | ≥ V2.1 |
| UL File Number | E223772 |
| MTBF | 173 a |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Indicators/operating means
| LED FAULT | Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault |
| LED PWR | AS-Interface voltage; green LED Green: voltage OK Flashing green: address 0 or peripheral error |
| LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| LED IN | status of input signal; LED yellow off: not active on: signal within measuring range flashing: signal outside of measuring range |
Electrical specifications
| Auxiliary voltage (output) | 20 ... 30 V DC PELV UAUX |
| Rated operating voltage | 26.5 ... 31.6 V from AS-Interface Ue |
| Rated operating current | ≤ 70 mA Ie |
| Protection class | III |
| Current consumption | IAUX ≤ 650 mA |
| Surge protection | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) |
Input
| Number/Type | 4 analog inputsCurrent: 0 mA ... 20 mA/4 mA ... 20 mA |
| Supply | From auxiliary voltage UAUX |
| Current loading capacity | ≤ 600 mA From auxiliary voltage UAUX ; overload and short-circuit resistant |
| Input resistance | current input: max. 70 Ω |
| Accuracy | 0.1 % of input signal range at 25 °C (298 K) |
| Resolution | 15 Bit |
| Temperature influence | 0.0025 %/K of input signal range |
Output
| Temperature influence | 1 µA/K or 0,3 mV/K |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 62026-2:2013 |
Standard conformity
| Degree of protection | EN 60529:2000 |
| Fieldbus standard | EN 62026-2:2013 |
| Emitted interference | EN 61000-6-4:2007 |
| AS-Interface | EN 62026-2:2013 |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
Programming instructions
| Profile | S-7.3.E |
| IO code | 7 |
| ID code | 3 |
| ID1 code | F |
| ID2 code | E |
| Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. |
| Parameter bits (programmable via AS-i) | function |
| P0 | 50/60 Hz filterP0=1, enabledP0=0, disabled |
| P1 | not used |
| P2 | Indication of the peripheral fault by exceeding measuring rangeP2=1, peripheral fault is reportedP2=0, peripheral fault is not reported |
| P3 | P3=1, wire break detection activeP3=0, wire break detection disabled |
Ambient conditions
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity | 85 % , non-condensing |
| Climatic conditions | For indoor use only |
| Altitude | ≤ 2000 m above MSL |
| Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
| Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Pollution degree | 2 |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | Removable push-in terminalsrated connection capacity:rigid: 0.20 mm2 ... 1.5 mm2flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 |
| Material: Housing | PA 66-FR |
| Mass | 110 g |
| Dimensions: Height | 100 mm |
| Dimensions: Width | 18.9 mm |
| Dimensions: Length | 124 mm |
| Mounting | DIN mounting rail |
| Note | Max. length of jumpers = 5 cm |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
VBA-4E-KE5-IL: frequently asked questions
When can VBA-4E-KE5-IL be shipped?
VBA-4E-KE5-IL is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up VBA-4E-KE5-IL in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for VBA-4E-KE5-IL and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for VBA-4E-KE5-IL, subject to availability and destination.
More Pepperl Fuchs parts