SIRIUS 3RV2 motor starter protectors Parts
Browse Subcategories
Available on requestSiemens 3RV2011-1KA15 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1KA15 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1JA15-Z W96 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1JA15-Z W96 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1JA15 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1JA15 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1JA10-0BA0 – Special type Circuit breaker size S00 for motor protectionMPN: 3RV2011-1JA10-0BA0 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1HA15 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1HA15 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1HA10-0BA0 – Special type Circuit breaker size S00 for motor protectionMPN: 3RV2011-1HA10-0BA0 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1HA10-Z X95 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1HA10-Z X95 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1HA10-Z W97 – Circuit breaker size S00 for motor protection CLASS 10…MPN: 3RV2011-1HA10-Z W97 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1HA10-Z W96 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1HA10-Z W96 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1HA10 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1HA10 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1BA10-Z X95 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1BA10-Z X95 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1BA10-Z W97 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1BA10-Z W97 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1BA10-Z W96 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1BA10-Z W96 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1BA10 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1BA10 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1AA25-Z X95 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1AA25-Z X95 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2011-1AA25-Z W97 – Circuit breaker size S00 for motor protectionMPN: 3RV2011-1AA25-Z W97 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2421-4BA10 – Circuit breaker size S0 for transformer protection…MPN: 3RV2421-4BA10 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2421-4AA20-0DA0 – Circuit breaker size S0 for transformer protection without…MPN: 3RV2421-4AA20-0DA0 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2421-4AA20 – Circuit breaker size S0 for transformer protection…MPN: 3RV2421-4AA20 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2421-4AA15 – Circuit breaker size S0 for transformer protection…MPN: 3RV2421-4AA15 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2421-4AA10-Z X95 – CIRCUIT-BREAKER SZ S0, FOR TRANSFORMER PROT. A-RELEASE…MPN: 3RV2421-4AA10-Z X95 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2421-4AA10 – Circuit breaker size S0 for transformer protection…MPN: 3RV2421-4AA10 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2811-0KD10 – Circuit breaker frame size S00 for transformer protection…MPN: 3RV2811-0KD10 · Siemens
Price on request
Request a quote
Available on requestSiemens 3RV2811-0JD10 – Circuit breaker frame size S00 for transformer protection…MPN: 3RV2811-0JD10 · Siemens
Price on request
Request a quoteCompare SIRIUS 3RV2 motor starter protectors
Key specifications of the parts listed on this page, taken from the manufacturer's data sheets.
| MPN | continuous current rated value | Net Weight | adjustable current response value current of the current-dependent overload release | operational current rated value | response value current of instantaneous short-circuit trip unit |
|---|---|---|---|---|---|
| 3RV2011-1KA15 | 12.5 A | 337.18 g | 9 ... 12.5 A | 12.5 A | 163 A |
| 3RV2011-1JA15-Z W96 | 10 A | 345.18 g | 7 ... 10 A | 10 A | 130 A |
| 3RV2011-1JA15 | 10 A | 345.18 g | 7 ... 10 A | 10 A | 130 A |
| 3RV2011-1JA10-0BA0 | 10 A | 325.6 g | 7 ... 10 A | 10 A | 130 A |
| 3RV2011-1HA15 | 8 A | 335.18 g | 5.5 ... 8 A | 8 A | 104 A |
| 3RV2011-1HA10-0BA0 | 8 A | 325.6 g | 5.5 ... 8 A | 8 A | 104 A |
| 3RV2011-1HA10-Z X95 | 8 A | 324.6 g | 5.5 ... 8 A | 8 A | 104 A |
| 3RV2011-1HA10-Z W97 | 8 A | 324.6 g | 5.5 ... 8 A | 8 A | 104 A |
| 3RV2011-1HA10-Z W96 | 8 A | 324.6 g | 5.5 ... 8 A | 8 A | 104 A |
| 3RV2011-1HA10 | 8 A | 324.6 g | 5.5 ... 8 A | 8 A | 104 A |
| 3RV2011-1BA10-Z X95 | 2 A | 321.6 g | 1.4 ... 2 A | 2 A | 26 A |
| 3RV2011-1BA10-Z W97 | 2 A | 321.6 g | 1.4 ... 2 A | 2 A | 26 A |
| 3RV2011-1BA10-Z W96 | 2 A | 321.6 g | 1.4 ... 2 A | 2 A | 26 A |
| 3RV2011-1BA10 | 2 A | 321.6 g | 1.4 ... 2 A | 2 A | 26 A |
| 3RV2011-1AA25-Z X95 | 1.6 A | 0.358 kg | 1.1 ... 1.6 A | 1.6 A | 21 A |
| 3RV2011-1AA25-Z W97 | 1.6 A | 0.358 kg | 1.1 ... 1.6 A | 1.6 A | 21 A |
| 3RV2421-4BA10 | 20 A | 335.6 g | 13 ... 20 A | 20 A | 325 A |
| 3RV2421-4AA20-0DA0 | 16 A | 0.389 kg | 10 ... 16 A | 16 A | 286 A |
| 3RV2421-4AA20 | 16 A | 389.6 g | 10 ... 16 A | 16 A | 286 A |
| 3RV2421-4AA15 | 16 A | 0.35 kg | 10 ... 16 A | 16 A | 286 A |
| 3RV2421-4AA10-Z X95 | 16 A | 339.6 g | 10 ... 16 A | 16 A | 286 A |
| 3RV2421-4AA10 | 16 A | 339.6 g | 10 ... 16 A | 16 A | 286 A |
| 3RV2811-0KD10 | 1.25 A | 462.08 g | — | 1.25 A | 26 A |
| 3RV2811-0JD10 | 1 A | 461.08 g | — | 1 A | 21 A |
Common to all listed parts
| Product equipment of circuit breaker for motor protection complete unit with protection device | Yes |
| product function disconnector functionality | Yes |
| product extension auxiliary switch | Yes |
| type of calculation of power loss current-dependent | quadratic |
| insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| surge voltage resistance rated value | 6 kV |
| reference code according to IEC 81346-2 | Q |
| Substance Prohibitance (day/month/year) | 10/01/2009 |