Siemens 6EP1353-0AA00
- MPN
- 6EP1353-0AA00
- Category
- Power Supplies
Discontinued by Siemens — we can still source the original 6EP1353-0AA00 (new, used or refurbished, subject to availability). Request a quote below.
Request a Quote
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- Ships via
What is the Siemens 6EP1353-0AA00?
Siemens 6EP1353-0AA00. Sourced on request by PartnerPLC — new, surplus or refurbished, subject to availability. Request a quote for price, condition and lead time.
Specifications
General information
| Technical Product Detail Page | https://i.siemens.com/1P6EP1353-0AA00 |
| product brand name | SITOP dual |
| product designation | Power supply SITOP power |
| type of current supply | 2 x 15 V/3.5 A |
input
| type of the power supply network | 1-phase AC |
| phase number | 1 |
| voltage curve at input | AC |
| supply voltage at AC — minimum rated value | 120 V |
| supply voltage at AC — maximum rated value | 230 V |
| supply voltage at AC — initial value | 93 V |
| supply voltage at AC — full-scale value | 264 V |
| supply voltage — at 50 Hz | 230 V |
| supply voltage — at 60 Hz | 120 V |
| line frequency | 50/60 Hz |
| line frequency | 47 ... 63 Hz |
| wide range input | Yes |
| overvoltage overload capability | Surge voltage in accordance with EN 61000-6-2 Table 4 |
| buffering time for rated value of the output current in the event of power failure minimum | 10 ms |
| operating condition of the mains buffering | at Vin = 120 V, 40 ms at Vin = 187 V |
| input current — at rated input voltage 120 V | 1.9 A |
| input current — at rated input voltage 230 V | 1.15 A |
| current limitation of inrush current at 25 °C maximum | 30 A |
| duration of inrush current limiting at 25 °C — typical | 3 ms |
| I2t value maximum | 3 A²·s |
| fuse protection type | T 4 A/250 V (not accessible) |
| fuse protection type in the feeder | Recommended miniature circuit breaker: from 10 A characteristic C or from 16 A characteristic B |
output
| voltage curve at output | Controlled, isolated DC voltage |
| product function output voltage controlled | Yes |
| product function output voltage stabilized | Yes |
| output voltage at DC rated value | 15 V |
| formula for output voltage | 2 x 15 V DC |
| output voltage — at output 1 at DC rated value | 15 V |
| output voltage — at output 2 at DC rated value | 15 V |
| output voltage — at output 1 at DC | 15 V |
| output voltage adjustable | Yes; via potentiometer |
| adjustable output voltage | 14.5 ... 17 V |
| relative overall tolerance of the voltage | 2 % |
| relative control precision of the output voltage — on slow fluctuation of input voltage | 0.2 % |
| relative control precision of the output voltage — on slow fluctuation of ohm loading | 0.2 % |
| residual ripple — maximum | 50 mV |
| residual ripple — typical | 20 mV |
| voltage peak — maximum | 150 mV |
| display version for normal operation | Green LED grün for Vout >10 V (summation display) |
| type of signal at output | - |
| behavior of the output voltage when switching on | Overshoot of Vout < 3 % |
| response delay maximum | 1 s |
| output current — rated value | 3.5 A |
| output current — at output 1 rated value | 3.5 A |
| output current — at output 2 rated value | 3.5 A |
| output current — rated range | 0 ... 3.5 A; +45 ... +60 °C: Derating 2%/K |
| supplied active power typical | 105 W |
| bridging of equipment | Yes |
| number of parallel-switched equipment resources for increasing the power | 2 |
efficiency
| efficiency in percent | 80 % |
| power loss [W] — at rated output voltage for rated value of the output current typical | 27 W |
protection and monitoring
| design of the overvoltage protection | Yes, according to EN 60950-1 |
| property of the output short-circuit proof | Yes |
| design of short-circuit protection | Electronic shutdown, automatic restart |
| response value current limitation | 4.9 A |
| design of the current limitation | Limit point < 4.9 A; switch-off point < 6 A |
safety
| galvanic isolation between input and output | Yes |
| galvanic isolation | Safety extra low output voltage Vout according to EN 60950-1 |
| operating resource protection class | Class I |
| leakage current — maximum | 3.5 mA |
| protection class IP | IP20 |
EMC
| standard — for emitted interference | EN 55011 Class A |
| standard — for mains harmonics limitation | - |
| standard — for interference immunity | EN 61000-6-2 |
standards, specifications, approvals
| certificate of suitability — CE marking | Yes |
| certificate of suitability — UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E179336 |
| certificate of suitability — EAC approval | Yes |
| certificate of suitability — NEC Class 2 | No |
| type of certification — CB-certificate | No |
standards, specifications, approvals hazardous environments
| certificate of suitability — IECEx | No |
| certificate of suitability — ATEX | No |
| certificate of suitability — ULhazloc approval | No |
| certificate of suitability — FM registration | No |
standards, specifications, approvals marine classification
| shipbuilding approval | No |
| Marine classification association — American Bureau of Shipping Europe Ltd. (ABS) | No |
| Marine classification association — French marine classification society (BV) | No |
| Marine classification association — Det Norske Veritas (DNV) | No |
| Marine classification association — Lloyds Register of Shipping (LRS) | No |
ambient conditions
| ambient temperature — during operation | 0 ... 60 °C; with natural convection |
| ambient temperature — during transport | -40 ... +70 °C |
| ambient temperature — during storage | -40 ... +70 °C |
| environmental category according to IEC 60721 | Climate class 3K3, 5 ... 95% no condensation |
connection method
| type of electrical connection | screw terminal |
| at input | L1, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded |
| at output | P15_1, GND_1, GND_2: 1 screw terminal each for 0.5 ... 2.5 mm²; P15_2: 2 screw terminals for 0.5 ... 2.5 mm² |
| for auxiliary contacts | - |
mechanical data
| width × height × depth of the enclosure | 75 × 125 × 125 mm |
| installation width × mounting height | 75 mm × 325 mm |
| required spacing — top | 100 mm |
| required spacing — bottom | 100 mm |
| required spacing — left | 0 mm |
| required spacing — right | 0 mm |
| fastening method | Snaps onto DIN rail EN 60715 35x7.5/15 |
| DIN-rail mounting | Yes |
| S7 rail mounting | No |
| wall mounting | No |
| housing can be lined up | Yes |
| net weight | 0.75 kg |
further information internet links
| internet link — to website: Industry Mall | https://mall.industry.siemens.com |
| internet link — to web page: selection aid TIA Selection Tool | https://www.siemens.com/tstcloud |
| internet link — to website: CAx-Download-Manager | https://siemens.com/cax |
| internet link — to website: Industry Online Support | https://support.industry.siemens.com |
additional information
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
security information
| security information | Siemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under https://www.siemens.com/cert. (V4.7) |
Downloads & documentation
Official documents from Siemens, downloaded directly from the manufacturer.
Data sheets & manuals
6EP1353-0AA00: frequently asked questions
Can I still buy the 6EP1353-0AA00 now that it is discontinued?
Yes. Siemens has discontinued the 6EP1353-0AA00, but sourcing discontinued parts is what PartnerPLC specialises in — new old stock, used and refurbished units. Request a quote and we'll confirm availability, condition and lead time.
When can 6EP1353-0AA00 be shipped?
6EP1353-0AA00 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 6EP1353-0AA00 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 6EP1353-0AA00 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 6EP1353-0AA00, subject to availability and destination.