
Pepperl Fuchs VAA-4E4A-KE5-ZEJQ/E2L
AS-Interface sensor/actuator module
- MPN
- VAA-4E4A-KE5-ZEJQ/E2L
- Category
- Modules
Request a Quote
- 1We check stock, condition and lead time
- 2You get a written quote by email
- 3Approve it and we ship — in-stock parts within 1 business day
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- 100% positive eBay feedback
- Ships via
What is the Pepperl Fuchs VAA-4E4A-KE5-ZEJQ/E2L?
Housing with push-in connection technology and mechanically coded terminal blocks
Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
Selectable supply to the sensors: External or from the module
Function display for bus, external auxiliary voltage, internal sensor supply, inputs, and outputs
Red LED per channel, lights up in the event of output overload
Cabinet module, 4 inputs and 4 outputs
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 269779 |
| Node type | Standard node |
| AS-Interface specification | V3.0 |
| Required gateway specification | ≥ V2.0 |
| UL File Number | E223772 |
| MTBF | 141 a |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Indicators/operating means
| LED FAULT | Error display; red LED red: communication error, i.e. address is 0 red flashing: overload internal input supply, i.e. overload or lead interruption outputs |
| LED INT | Internal input supply active; LED green |
| LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
| LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| LED IN | switching state (input); 4 LED yellow |
| LED OUT | switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption |
Electrical specifications
| Auxiliary voltage (input) | 12 ... 30 V DC PELV UEXT |
| Auxiliary voltage (output) | 20 ... 30 V DC PELV UAUX |
| Rated operating voltage | 26.5 ... 31.6 V from AS-Interface Ue |
| Rated operating current | ≤ 35 mA (without sensors) / max. 190 mA Ie |
| Protection class | III |
| Surge protection | UEXT, UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) Overvoltage category of the power supplies (primary): III |
| Rated insulation voltage | 92 V |
| Pulse withstand voltage | 0.8 kV |
Input
| Number/Type | 4 inputs for 3-wire sensors (PNP), DC |
| Supply | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) |
| Voltage | 21 ... 31 V DC (INT) |
| Current loading capacity | ≤ 150 mA, overload- and short-circuit protected (INT) |
| Input current | ≤ 5.6 mA (max.) |
| Switching point | according to DIN EN 61131-2 (type 1) |
| 0 (unattenuated) | ≤ 0.5 mA |
| 1 (attenuated) | ≥ 2 mA |
| Signal delay | < 1 ms (input/AS-Interface) |
Output
| Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
| Supply | from external auxiliary voltage UAUX |
| Voltage | ≥ (UAUX - 0.5 V) |
| Current | 2 A Per output, total 4 A (TB ≤ 60 °C) 1 A Per output, total 4 A (TB ≤ 70 °C) |
| Usage category | DC-13 |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Machinery Directive: Directive 2006/42/EC | EN ISO 13849-1:2008 , EN ISO 13849-2:2012 |
Standard conformity
| Degree of protection | EN 60529:2000 |
| Fieldbus standard | EN 62026-2:2013 |
| Electrical safety | IEC 61140:2009 |
| Input | EN 61131-2:2004 |
| Emitted interference | EN 61000-6-4:2007 |
| AS-Interface | EN 62026-2:2013 |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026:2013 |
| Functional safety | EN ISO 13849-1:2008 EN ISO 13849-2:2012 |
Programming instructions
| Profile | S-7.0 |
| IO code | 7 |
| ID code | 0 |
| ID1 code | F |
| ID2 code | E |
| Data bits (function via AS-Interface) | InputOutput |
| D0 | IN1 O1 |
| D1 | IN2 O2 |
| D2 | IN3 O3 |
| D3 | IN4 O4 |
| Parameter bits (programmable via AS-i) | function |
| P0 | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
| P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
| P2 | Lead breakage outputs P2 = 0 lead breakage on P2 = 1 lead breakage off (default settings) |
| P3 | not used |
Ambient conditions
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity | 85 % , non-condensing |
| Climatic conditions | For indoor use only |
| Altitude | ≤ 2000 m above MSL |
| Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
| Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Pollution degree | 2 |
Mechanical specifications
| Degree of protection | IP20 For safety applications: Installation in an enclosure with a minimum protection class of IP54 required |
| Connection | Removable push-in terminalsrated connection capacity:rigid: 0.20 mm2 ... 1.5 mm2flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 |
| Material: Housing | PA 66-FR |
| Mass | 110 g |
| Dimensions: Height | 100 mm |
| Dimensions: Width | 18.9 mm |
| Dimensions: Length | 124 mm |
| Mounting | DIN mounting rail |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
VAA-4E4A-KE5-ZEJQ/E2L: frequently asked questions
When can VAA-4E4A-KE5-ZEJQ/E2L be shipped?
VAA-4E4A-KE5-ZEJQ/E2L is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up VAA-4E4A-KE5-ZEJQ/E2L in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for VAA-4E4A-KE5-ZEJQ/E2L and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for VAA-4E4A-KE5-ZEJQ/E2L, subject to availability and destination.
More Pepperl Fuchs parts











