What is the Pepperl Fuchs KFD2-VR-Ex1.18?
1-channel isolated barrier
24 V DC supply (Power Rail)
Voltage input 0 V ... 12 V
Voltage output 0 V ... 12 V
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... 12 V, Voltage output 0 V ... 12 V, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 20 ... 35 V DC, Signal: 1 x 0 ... 12 V, Signal: 1 x 0 ... 12 V, Cut-off frequency: 1.2 kHz (-3 dB)
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 072036 |
| Signal type | Analog input |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Supply
| Connection | Power Rail or terminals 11+, 12- |
| Rated voltage | 20 ... 35 V DC Ur |
| Ripple | within the supply tolerance |
| Rated current | < 20 mA Ir |
Input
| Connection side | field side |
| Connection | terminals 4+, 5- |
| Input resistance | min. 10 MΩ |
| Transmission range | 0 ... 12 V |
| Offset voltage/current | < 2 mV / < 7 nA |
Output
| Connection side | control side |
| Connection | terminals 7-, 8+ |
| Voltage | 0 ... 12 V |
| Output resistance | max. 20 Ω |
Transfer characteristics
| Cut-off frequency | 1.2 kHz (-3 dB) |
| Deviation: After calibration | ± 5 mV at 20 °C (68 °F) |
| Deviation: Influence of ambient temperature | ≤ 0.005 % of range per K |
| Rise time | ≤ 0.4 ms |
Galvanic isolation
| Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Indicators/settings
| Display elements | LED |
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity
| Electromagnetic compatibility | NE 21 |
| Degree of protection | IEC 60529 |
Ambient conditions
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 100 g |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1 |
| Height | 107 mm |
| Width | 20 mm |
| Depth | 115 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| EU-type examination certificate | BAS 01 ATEX 7262 |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) , [circuit(s) in zone 0/1/2] |
| Voltage | 18 V Uo |
| Current | 4.2 mA Io |
| Power | 19 mW Po |
| Supply: Maximum safe voltage | 250 V (Attention! The rated voltage is lower.) Um |
| Output: Maximum safe voltage | 250 V (Attention! The rated voltage is lower.) Um |
| Certificate | BASEEFA 10 ATEX 0079X |
| Marking | II 3G Ex ec IIC T4 Gc [device in zone 2] |
| Galvanic isolation: Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Galvanic isolation: Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018 |
International approvals
| FM approval: Control drawing | 116-0129 |
| UL approval: Control drawing | 116-0173 (cULus) |
| CSA approval: Control drawing | 116-0132 |
| IECEx approval: IECEx certificate | IECEx BAS 10.0040X |
| IECEx approval: IECEx marking | Ex ec IIC T4 Gc |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
Certificates (7)
- USA FM (FM 17 US 0334X)
- EU Declaration of Conformity (Pepperl+Fuchs)
- Canada USA UL Certificate of Compliance Hazardous Location UL E106378 cULus (CoC 20140902 - E106378 RepRef 20011030)
- Europe Baseefa II 3 G (Baseefa 10 ATEX 0079X)
- Korea KOSHA (11-AV4BO-0074X)
- United Kingdom CML UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G UKEX Category (M1) (CML 21UKEX2897)
- Europe Baseefa I (M1) II (1) D II (1) G (BAS 01 ATEX 7262)
KFD2-VR-Ex1.18: frequently asked questions
When can KFD2-VR-Ex1.18 be shipped?
KFD2-VR-Ex1.18 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KFD2-VR-Ex1.18 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KFD2-VR-Ex1.18 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-VR-Ex1.18, subject to availability and destination.
More Pepperl Fuchs parts