What is the Pepperl Fuchs KFD2-SH-Ex1.T.OP?

1-channel isolated barrier

24 V DC supply (Power Rail)

Input for approved dry contacts or SN/S1N sensors

Active voltage output

Relay contact output

Fault indication output

Line fault detection (LFD)

Up to SIL 3 acc. to IEC/EN 61508

Up to PL d acc. to EN/ISO 13849

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for approved dry contacts or SN/S1N sensors, Active voltage output, Relay contact output, Fault indication output, Line fault detection (LFD), Up to SIL 3 acc. to IEC/EN 61508, Up to PL d acc. to EN/ISO 13849, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 20 ... 30 V DC, Field device: SN/S1N sensor, Field device [2]: volt-free contact

Specifications

General specifications

Order code (Pepperl+Fuchs part number)70100833
Signal typeDigital Input
LifecycleActive (current Pepperl+Fuchs product)

Functional safety related parameters

Safety Integrity Level (SIL)SIL 3
Systematic capability (SC)SC 3
Performance level (PL)PL d

Supply

ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 30 V DC Ur
Ripple≤ 10 %
Rated current≤ 100 mA Ir
Power dissipation1.5 W
Power consumptionmax. 1.7 W

Input

Connection sidefield side
Connectionterminals 4+, 6-
Open circuit voltage/short-circuit currentapprox. 8.4 V DC / approx. 11.7 mA
Lead resistancemax. 50 Ω , cable capacitances and inductances must be observed in hazardous areas
Switching point: Relay de-energizedI 5.9 mA , output switched off
Switching point: Relay energized2.8 mA < I < 5.3 mA , output switched on
Response delay≤ 1 ms

Output

Connection sidecontrol side
Connectionoutput I: terminals 7+, 8- ; output II: terminals 9, 10 ; output III: terminals 11, 12
Output Iactive voltage output, short-circuit proof 0-signal: 0 V 1-signal: 19 V DC at 15 mA ... 31 V DC at no-load fault: 0 V
Output IIrelay
Contact loading48 V AC/DC 250 mA
Mechanical life≤ 20 x 106 switching cycles
Output IIIrelay , fault signal
Contact loading48 V AC/DC 250 mA
Mechanical life≤ 20 x 106 switching cycles

Transfer characteristics

Switching frequency: Output I≤ 50 Hz
Switching frequency: Output II≤ 5 Hz
Switching frequency: Output III≤ 5 Hz

Indicators/settings

Display elementsLEDs
Labelingspace for labeling at the front

Directive conformity

Electromagnetic compatibility: Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Machinery Directive: Directive 2006/42/ECEN/ISO 13849-1:2015

Conformity

Electromagnetic compatibilityNE 21:2017 , EN 61326-3-2:2008
Degree of protectionIEC 60529:2001
SafetyIEC/EN 61508:2010

Ambient conditions

Ambient temperature-20 ... 70 °C (-4 ... 158 °F) extended ambient temperature range up to 70 °C (158 °F) , refer to manual and derating characteristics in the datasheet for necessary mounting conditions

Mechanical specifications

Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001

Data for application in connection with hazardous areas

EU-type examination certificatePTB 00 ATEX 2041
MarkingII (1)G [Ex ia Ga] IIC , [exsign] II (1)D [Ex ia Da] IIIC
InputEx ia
Voltage9.56 V Uo
Current16.8 mA Io
Power41 mW (linear characteristic) Po
Supply: Maximum safe voltage40 V AC/DC (Attention! The rated voltage can be lower.) Um
Output: Contact loading48 V AC/DC 250 mA
Output: Maximum safe voltage60 V AC/DC (Attention! The rated voltage can be lower.) Um
CertificateTÜV 99 ATEX 1493 X
MarkingII 3G Ex ec nC IIC T4 Gc
Galvanic isolation: Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019

International approvals

IECEx approval: IECEx certificateIECEx PTB 21.0010 IECEx TUN 19.0013X
IECEx approval: IECEx marking[Ex ia Ga] IIC [Ex ia Da] IIIC Ex ec nC IIC T4 Gc

General information

Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

KFD2-SH-Ex1.T.OP: frequently asked questions

When can KFD2-SH-Ex1.T.OP be shipped?

KFD2-SH-Ex1.T.OP is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up KFD2-SH-Ex1.T.OP in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for KFD2-SH-Ex1.T.OP and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-SH-Ex1.T.OP, subject to availability and destination.

More Pepperl Fuchs parts

Pepperl Fuchs KFD2-SH-Ex1 – Switch Amplifier
Pepperl Fuchs
KFD2-SH-Ex1

Switch Amplifier

Pepperl Fuchs KFD2-SL-4 – Solenoid Driver, Power Amplifier
Pepperl Fuchs
KFD2-SL-4

Solenoid Driver, Power Amplifier

Pepperl Fuchs KFD2-SH-Ex1.T.OPPrice and lead time confirmed within 1 business day
Request a Quote