Pepperl Fuchs KFD2-HLC-Ex1.D.2W
HART Loop Converter
- MPN
- KFD2-HLC-Ex1.D.2W
- Category
- K-System
Request a Quote
- 1We check stock, condition and lead time
- 2You get a written quote by email
- 3Approve it and we ship — in-stock parts within 1 business day
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- 100% positive eBay feedback
- Ships via
What is the Pepperl Fuchs KFD2-HLC-Ex1.D.2W?
1-channel isolated barrier
24 V DC supply (Power Rail)
HART field device input with transmitter power supply
Usable as signal splitter (1 input and several outputs)
2 relay contact outputs (change-over contacts)
3 analog outputs 4 mA ... 20 mA
Sink and source mode output
Configurable by keypad
1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 2 relay contact outputs (change-over contacts), 3 analog outputs 4 mA ... 20 mA, Sink and source mode output, Configurable by keypad, Housing width: 40 mm, Number of channels: 1-channel, HART communication, Trip relay, Rated voltage: 19 ... 30 V DC, Function: transmitter supply, Field device: 3-wire transmitter
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 261918 |
| Signal type | Analog input |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Supply
| Connection | Power Rail or terminals 23+, 24- |
| Rated voltage | 19 ... 30 V DC Ur |
| Rated current | approx. 130 mA at 24 V DC Ir |
| Power dissipation | 2.5 W |
| Power consumption | 3.1 W |
HART signal channels (intrinsically safe)
| Conformity | HART field device input (revision 5 to 7) |
Interface
| Programming interface | programming socket |
Input
| Connection side | field side |
| Connection | terminals 1, 2, 3, 4, 5, 6 |
| Open circuit voltage/short-circuit current | typ. 24 V / 28 mA |
| Input resistance | 250 Ω , 5 % (terminals 2, 3 and with jumper on 5, 6) |
| Available voltage | ≥ 15.5 V at 20 mA, short-circuit protected |
Output
| Connection side | control side |
| Connection | output I: terminals 10, 11, 12, output II: terminals 16, 17, 18 output III: terminals 7, 8, 9, output IV: terminals 13, 14, 15, output V: terminals 19, 20, 21 |
| Output I, II: Output signal | relay and LED yellow |
| Output I, II: Mechanical life | 107 switching cycles |
| Output I, II: Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Output III, IV, V: Output signal | analog |
| Output III, IV, V: Current range | 4 ... 20 mA , (source or sink mode) |
| Output III, IV, V: Load | max. 650 Ω , source mode |
| Output III, IV, V: Voltage range | 5 ... 30 V , sink mode from external supply |
| Output III, IV, V: Fault signal | downscale I ≤ 2 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) or hold measurement value |
| Other outputs | HART communicator on terminals 22, 24 |
| Collective error message | Power Rail and LED red |
Transfer characteristics
| Output III, IV, V: Resolution | max. 2 µA |
| Output III, IV, V: Accuracy | < 20 µA, 10 µA typ. |
| Output III, IV, V: Influence of ambient temperature | < ± 2 µA/K |
| Output III, IV, V: Duration of measurement/Response delay | HART message acquisition time plus 100 ms |
| Relay | programmable either for fault or trip value (with direction, hysteresis and delay) |
Galvanic isolation
| Output I/II | functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff |
| Output I, II/other circuits | reinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms |
| Output III/IV/V/power supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Indicators/settings
| Display elements | LEDs , display |
| Control elements | Control panel |
| Configuration | via operating buttons via PACTware |
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Low voltage: Directive 2014/35/EU | EN 61010-1:2010 |
Conformity
| Electromagnetic compatibility | NE 21:2006 |
| Degree of protection | IEC 60529:2001 |
Ambient conditions
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | 300 g |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 |
| Height | 119 mm |
| Width | 40 mm |
| Depth | 115 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| EU-type examination certificate | BASEEFA 07 ATEX 0174 |
| Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC |
| Supply: Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) Um |
| Equipment | terminals 1, 4/3 (with link between terminals 4 and 5) |
| Voltage | 25.2 V Uo |
| Current | 104.9 mA Io |
| Power | 0.661 W Po |
| Internal capacitance | 1.1 nF Ci |
| Internal inductance | 0 mH Li |
| Equipment | terminals 2, 5/3 |
| Voltage | < 28 V Ui |
| Power | < 1.33 W Pi |
| Voltage | 1.1 V Uo |
| Current | 11.9 mA Io |
| Power | 4 mW Po |
| Internal capacitance | 0 µF Ci |
| Internal inductance | 0 mH Li |
| Output I, II | terminals 10, 11, 12; 16, 17, 18 , non-intrinsically safe |
| Maximum safe voltage | 253 V (Attention! Um is no rated voltage.) Um |
| Contact loading | 253 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (BASEEFA 07 ATEX 0174) 50 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (Pepperl+Fuchs self-declaration) |
| Output III, IV, V | terminals 7, 8, 9; 13, 14, 15; 19, 20, 21 , non-intrinsically safe |
| Maximum safe voltage | 253 V (Attention! Um is no rated voltage.) Um |
| Certificate | PF 07 CERT 1141 X |
| Marking | II 3G Ex nA nC IIC T4 Gc |
| Galvanic isolation: Input/Other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals
| FM approval: Control drawing | 116-0129 |
| IECEx approval: IECEx certificate | IECEx BAS 07.0047 |
| IECEx approval: IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
Certificates (8)
- Canada FM (FM22CA0014X)
- China SITIIAS CCC Ex Certificate (2021322316004122 (Singapore))
- Brasil TUV Rheinland Brazil (TÜV 13.2090)
- EU Declaration of Conformity (Pepperl+Fuchs)
- South Africa MASC (MASC S/17-0873)
- United Kingdom UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G (CML 21UKEX21103)
- Europe Baseefa ATEX Category (1) D ATEX Category (1) G (Baseefa 07 ATEX 0174)
- Europe Pepperl+Fuchs ATEX Category 3 ATEX Category 3 G Certificate of Compliance (PF 07 CERT 1141X)
KFD2-HLC-Ex1.D.2W: frequently asked questions
When can KFD2-HLC-Ex1.D.2W be shipped?
KFD2-HLC-Ex1.D.2W is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KFD2-HLC-Ex1.D.2W in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KFD2-HLC-Ex1.D.2W and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-HLC-Ex1.D.2W, subject to availability and destination.
More Pepperl Fuchs parts