What is the Pepperl Fuchs KFD0-HMS-16?
16-channel
No external power required
HART field device input (revision 5 to 7)
Used with HART MUX primary module KFD2-HMM-16
Up to SIL 3 acc. to IEC/EN 61508
16-channel, No external power required, HART field device input (revision 5 to 7), Used with HART MUX primary module KFD2-HMM-16, Up to SIL 3 acc. to IEC/EN 61508
Specifications
Functional safety related parameters
| Order code (Pepperl+Fuchs part number) | 231291 |
| Safety Integrity Level (SIL) | SIL 3 |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Supply
| Connection | via 14-channel flat cable from the KFD2-HMM-16 primary module |
HART signal channels (non-intrinsically safe)
| Conformity | HART field device input (revision 5 to 7) |
| Connection | 26-pin flat cable for analog connections 14-pin flat cable for primary module/secondary module connection between KFD2-HMM-16 and KFD0-HMS-16 |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) |
| Terminating resistor | external 230 ... 500 Ω standard (up to 1000 Ω possible) |
| Output voltage | ≥ 400 mV ss (with the terminator resistance specified above) |
| Output resistance | 100 Ω or smaller, capacitive coupling |
| Input impedance | according to HART specification |
| Input voltage range | 0.08 ... 4 V ss ; typ. ± 5.2 V as local reference |
Indicators/settings
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity
| Degree of protection | IEC 60529:2001 |
Ambient conditions
| Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Mass | approx. 100 g |
| Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) (W x H x D) , housing type B1 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| Certificate | PF 07 CERT 1143 X |
| Marking | II 3G Ex nA IIC T4 Gc |
| Directive conformity: Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
KFD0-HMS-16: frequently asked questions
When can KFD0-HMS-16 be shipped?
KFD0-HMS-16 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KFD0-HMS-16 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KFD0-HMS-16 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD0-HMS-16, subject to availability and destination.
More Pepperl Fuchs parts