Pepperl Fuchs ICA-16DI-G60A-IO

I/O hub

MPN
ICA-16DI-G60A-IO
Price and lead time confirmed within 1 business day
Request a Quote
  1. 1We check stock, condition and lead time
  2. 2You get a written quote by email
  3. 3Approve it and we ship — in-stock parts within 1 business day

A real person replies, typically within 1 business day — see our privacy policy.

  • 12-month warranty (new) · 3-month (used/refurbished)
  • 30-day returns, no restocking fee on unused parts
  • 100% positive eBay feedback
  • Ships via

Have spare Pepperl Fuchs parts? We buy surplus →

What is the Pepperl Fuchs ICA-16DI-G60A-IO?

Sturdy metallic housing

IO-Link interface for service and process data

16 digital inputs

Logic level can be configured per port

Filter time can be configured per port

Pulse extension can be configured per port

I/O hub with IO-Link interface for 16 digital inputs

Specifications

General specifications

Order code (Pepperl+Fuchs part number)313335
UL File NumberE223772
LifecycleActive (current Pepperl+Fuchs product)

Functional safety related parameters

MTTFd2111 a

Indicators/operating means

LED IO-LinkGreen: module is switched on, no communication Flashing green: communication OK Red: signal line overload
LED AOrange: status indicator channel A Red: peripheral error
LED BWhite: status indicator channel B Red: peripheral error
LED USGreen: system/sensor supply voltage OK Red: system/sensor supply voltage < 18 V Flashing red: sensor supply voltage overload

Electrical specifications

Rated operating voltage18 ... 30 V Ue
Nominal voltage24 V DC
Nominal current4 A
Current consumptiontyp. 80 mA

Interface

Interface typeIO-Link
IO-Link revision1.1
Device profileIdentification and Diagnosis - I&D
Device ID0x0F0201 (983553)
Transfer rateCOM3 (230.4 kbits/s)
Min. cycle time2 ms
Process data widthInput 4 Byte Output 4 Byte
SIO mode supportno
Compatible master port typeA

Input

Number/Type16 digital inputs 5-wire PNP, DC, supply from US Type 1 according to IEC 61131-2
Sensor supplyDepending on the IO-Link master, max. 500 mA per module

Directive conformity

Electromagnetic compatibility: Directive 2014/30/EUEN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011

Standard conformity

Degree of protectionEN 60529:2000
Fieldbus standardType 1 according to IEC 61131-2
Emitted interferenceEN 61000-6-2:2005
Noise immunityEN 61000-6-4:2007+A1:2011
Shock resistanceEN 61131-2:2004

Ambient conditions

Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Relative humiditymax. 95 %
Altitude0 ... 2000 m
Shock and impact resistance50 g, 11 ms, all axes
Vibration resistance15 g / 5 ... 500 Hz
Pollution degree3

Mechanical specifications

Degree of protectionIP65 / IP67 / IP69K
ConnectionPower supply/IO-Link M12, A-coded Inputs/Outputs M12, A-coded
Material: ContactsCuSn, gold-plated CuNi, gold-plated
Material: HousingDiecast zinc
Material: Plastic partsPA
Material: SealFKM
Mass390 g
Dimensions: Height200 mm
Dimensions: Width59.6 mm
Dimensions: Length21 mm
Construction typeField housing

ICA-16DI-G60A-IO: frequently asked questions

When can ICA-16DI-G60A-IO be shipped?

ICA-16DI-G60A-IO is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up ICA-16DI-G60A-IO in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for ICA-16DI-G60A-IO and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for ICA-16DI-G60A-IO, subject to availability and destination.

More Pepperl Fuchs parts

Pepperl Fuchs ICA-16DI-G60A-IOPrice and lead time confirmed within 1 business day
Request a Quote