Pepperl Fuchs HiC2822

Switch Amplifier

MPN
HiC2822
Price and lead time confirmed within 1 business day
Request a Quote

A real person replies, typically within 1 business day — see our privacy policy.

What happens next
  1. We check stock, condition and lead time
  2. You get a written quote by email
  3. Approve it and we ship — in-stock parts within 1 business day
  • 12-month warranty (new) · 3-month (used/refurbished)
  • 30-day returns, no restocking fee on unused parts
  • Ships via
  • 100% positive eBay feedback

Have spare Pepperl Fuchs parts? We buy surplus →

What is the Pepperl Fuchs HiC2822?

2-channel isolated barrier

24 V DC supply (bus powered)

Dry contact or NAMUR inputs

2 relay contact outputs

Line fault detection (LFD)

Reversible mode of operation

Up to SIL 2 acc. to IEC/EN 61508

2-channel isolated barrier, 24 V DC supply (bus powered), Dry contact or NAMUR inputs, 2 relay contact outputs, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (NO contact), Fault indication output

Specifications

General specifications

Order code (Pepperl+Fuchs part number)216690
Signal typeDigital Input
LifecycleActive (current Pepperl+Fuchs product)

Functional safety related parameters

Safety Integrity Level (SIL)SIL 2

Supply

ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage19 ... 30 V DC bus powered via Termination Board Ur
Ripple≤ 10 %
Rated current≤ 30 mA Ir
Power dissipation≤ 600 mW
Power consumption≤ 600 mW

Input

Connection sidefield side
ConnectionSL2: 5a(+), 5b(-); 1a(+), 1b(-)
Rated valuesacc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I ≥ 6.7 mA
Pulse/Pause ratiomin. 20 ms / min. 20 ms

Output

Connection sidecontrol side
ConnectionSL1: 8a, 7a; 10a, 9a
Output Isignal ; relay
Output IIsignal ; relay
Contact loading50 V DC / 0.5 A
Minimum switch current2 mA / 24 V DC
Energized/De-energized delay≤ 20 ms / ≤ 20 ms
Mechanical life107 switching cycles

Fault indication output

ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)

Transfer characteristics

Switching frequency≤ 10 Hz

Galvanic isolation

Output/power supplybasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Output/Outputbasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC

Indicators/settings

Display elementsLEDs
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front

Directive conformity

Electromagnetic compatibility: Directive 2014/30/EUEN 61326-1:2013 (industrial locations)

Conformity

Galvanic isolationEN 50178:1997
Electromagnetic compatibilityEN IEC 61326-3-2:2018 , NE 21:2012 For further information see system description.
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000

Ambient conditions

Ambient temperature-20 ... 60 °C (-4 ... 140 °F)

Mechanical specifications

Degree of protectionIP20
Massapprox. 110 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Height106 mm
Width12.5 mm
Depth128 mm
Mountingon termination board
Codingpin 1 and 2 trimmed For further information see system description.

Data for application in connection with hazardous areas

EU-type examination certificateBASEEFA 06 ATEX 0093 X
MarkingII (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage10.5 V Uo
Current17.1 mA Io
Power45 mW (linear characteristic) Po
Supply: Maximum safe voltage253 V AC (Attention! Um is no rated voltage.) Um
Output: Contact loading50 V DC / 0.5 A
Output: Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.) Um
CertificatePF 08 CERT 1047 X
MarkingII 3G Ex nA nC IIC T4 Gc
Galvanic isolation: Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010

International approvals

FM approval: Control drawing16-534FM-12 (cFMus)
UL approvalE106378
Control drawing116-0434
IECEx approval: IECEx certificateIECEx BAS 06.0026X
IECEx approval: IECEx marking[Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I

General information

Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

HiC2822: frequently asked questions

When can HiC2822 be shipped?

HiC2822 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up HiC2822 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for HiC2822 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for HiC2822, subject to availability and destination.

More Pepperl Fuchs parts

Pepperl Fuchs HiC2081 – Temperature Converter
Pepperl Fuchs
HiC2081

Temperature Converter

Pepperl Fuchs HiC2422 – SMART Transmitter Power Supply/SMART Current Driver
Pepperl Fuchs
HiC2422

SMART Transmitter Power Supply/SMART Current Driver

Pepperl Fuchs HiC2441 – SMART Universal Barrier
Pepperl Fuchs
HiC2441

SMART Universal Barrier

Pepperl Fuchs HiC2821 – Switch Amplifier
Pepperl Fuchs
HiC2821

Switch Amplifier

Pepperl Fuchs HiC2831 – Switch Amplifier
Pepperl Fuchs
HiC2831

Switch Amplifier

Pepperl Fuchs HiC2831R1 – Switch Amplifier
Pepperl Fuchs
HiC2831R1

Switch Amplifier

Pepperl Fuchs HiC2831R2 – Switch Amplifier
Pepperl Fuchs
HiC2831R2

Switch Amplifier

Pepperl Fuchs HiC2831R3 – Switch Amplifier
Pepperl Fuchs
HiC2831R3

Switch Amplifier

Pepperl Fuchs HiC2822Price and lead time confirmed within 1 business day
Request a Quote