Quick facts

AvailabilityConfirmed on request
CategoryH-System (Termination Board Mounting)
Lifecycleactive
Warranty12-month (new) · 3-month (used/refurbished)

Shipping & availability

When can HiC2422 be shipped?

HiC2422 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up HiC2422 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for HiC2422 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for HiC2422, subject to availability and destination.

SMART Transmitter Power Supply/SMART Current Driver. 2-channel isolated barrier, 24 V DC supply (bus powered), Analog input (AI), Analog output (AO), Operates as transmitter power supply or current driver, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC via Termination Board. Signal type: Analog input/analog output. Safety Integrity Level (SIL): SIL 2. Systematic capability (SC): SC 3. Connection: SL1: 1a(-), 1b(-); 2a(+), 2b(+). Rated voltage: 19 ... 30 V DC via Termination Board. Ripple: max. 10 %. Rated current: max. 88 mA at 24 V. Power dissipation: max. 1.4 W. Power consumption: max. 2.1 W. Number of channels: 2. Suitable field devices: 2-wire SMART transmitters. Signal: 0/4 ... 20 mA , limited to approx. 30 mA. Field circuit: SL2: 5a(+), 5b(-); 1a(+), 1b(-). Available voltage: min. 15 V at 20 mA min. 18 V at 4 mA. Control circuit: SL1: 8a(+), 7a(-); 10a(+), 9a(-). Input voltage: Voltage across terminals 10 ... 30 V. If the current is supplied from a source > 24 V,series resistance of ≥ (V - 24)/0.02 Ω is needed, where V is the source voltage. The maximum value of the resistance is (V - 10)/0.02 Ω. (sink output). Load: max. 350 Ω (source output). Ripple: 20 mV eff. Number of channels: 2. Suitable field devices: SMART I/P converters (positioner), on-site-displays. Signal: 0/4 ... 20 mA , limited to approx. 30 mA. Field circuit: SL2: 5a(+), 5b(-); 1a(+), 1b(-). Load: max. 650 Ω. Voltage: min. 13 V at 20 mA. Ripple: 20 mV eff , on all signal terminals. Control circuit: SL1: 8a(+), 7a(-); 10a(+), 9a(-). Voltage drop: max. 6 V. Line fault detection: > 100 kΩ at max. 30 V, with field wiring open. Deviation: max. 20 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage. Influence of ambient temperature< 2 µA/K (-40 ... 70 °C (-40 ... 158 °F)): . Influence of ambient temperature: < 2 µA/K (-40 ... 70 °C (-40 ... 158 °F)). Frequency range: field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB). Settling time: max. 200 ms. Rise time/fall time: max. 100 ms (10 ... 90 %). Field circuit/control circuit: basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Control circuit/control circuit: channel I/channel II : functional isolation, rated voltage: 50 V. Field circuit/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Control circuit/power supply: basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff. Display elements: LED. Factory setting: analog input with source output. Configuration: via DIP switches. Labeling: space for labeling at the front. Electromagnetic compatibility: . Directive 2014/30/EUEN 61326-1:2013 (industrial locations): . Directive 2014/30/EU: EN 61326-1:2013 (industrial locations). Electromagnetic compatibility: NE 21:2017 EN 61326-3-2:2018 For further information see system description.. Degree of protection: IEC 60529:2001. Protection against electrical shock: UL 61010-1:2012. Functional safety: IEC 61508:2010. Ambient temperature: -40 ... 70 °C (-40 ... 158 °F). Storage temperature: -40 ... 85 °C (-40 ... 185 °F). Relative humidity: 95 % non-condensing. Degree of protection: IP20. Mass: approx. 100 g. Dimensions: 12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D). Height106 mmWidth12.5 mmDepth128 mm: . Height: 106 mm. Width: 12.5 mm. Depth: 128 mm. Mounting: on termination board. Coding: pin 1 and 3 trimmed For further information see system description.. EU-type examination certificate: UL 23 ATEX 3091 X. Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] IOutputEx ia, Ex iaDVoltageUo25.2 VCurrentIo100 mAPowerPo630 mWInternal capacitanceCi1.05 nFInternal inductanceLi 0: . Marking: II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I. Output: Ex ia, Ex iaD. Voltage: 25.2 V. Current: 100 mA. Power: 630 mW. Internal capacitance: 1.05 nF. Internal inductance: 0. Supply: . Maximum safe voltageUm250 V rms (Attention! The rated voltage can be lower.): Um. Maximum safe voltage: 250 V rms (Attention! The rated voltage can be lower.). Input: . Maximum safe voltageUm250 V rms (Attention! The rated voltage can be lower.): Um. Maximum safe voltage: 250 V rms (Attention! The rated voltage can be lower.). Certificate: UL 23 ATEX 3092 X. Marking II 3G Ex ec IIC T4 Gc: . Marking: II 3G Ex ec IIC T4 Gc. Galvanic isolation: . Field circuit/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V: . Field circuit/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V. Directive conformity: . Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018: . Directive 2014/34/EU: EN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018. UL approval: E106378. Control drawing116-0500 (cULus): . Control drawing: 116-0500 (cULus). IECEx approval: . IECEx certificateIECEx ULD 23.0026XIECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc: . IECEx certificate: IECEx ULD 23.0026X. IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc. Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Specifications

General specifications

Signal typeAnalog input/analog output

Functional safety related parameters

Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3

Supply

ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage19 ... 30 V DC via Termination Board Ur
Ripplemax. 10 %
Rated currentmax. 88 mA at 24 V Ir
Power dissipationmax. 1.4 W
Power consumptionmax. 2.1 W

Analog input

Number of channels2
Suitable field devices2-wire SMART transmitters
Signal0/4 ... 20 mA , limited to approx. 30 mA
Field circuitSL2: 5a(+), 5b(-); 1a(+), 1b(-)
Available voltagemin. 15 V at 20 mA min. 18 V at 4 mA
Control circuitSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Input voltageVoltage across terminals 10 ... 30 V. If the current is supplied from a source > 24 V,series resistance of ≥ (V - 24)/0.02 Ω is needed, where V is the source voltage. The maximum value of the resistance is (V - 10)/0.02 Ω. (sink output)
Loadmax. 350 Ω (source output)
Ripple20 mV eff

Analog output

Number of channels2
Suitable field devicesSMART I/P converters (positioner), on-site-displays
Signal0/4 ... 20 mA , limited to approx. 30 mA
Field circuitSL2: 5a(+), 5b(-); 1a(+), 1b(-)
Loadmax. 650 Ω
Voltagemin. 13 V at 20 mA
Ripple20 mV eff , on all signal terminals
Control circuitSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Voltage dropmax. 6 V
Line fault detection> 100 kΩ at max. 30 V, with field wiring open

Transfer characteristics

Deviationmax. 20 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Influence of ambient temperature< 2 µA/K (-40 ... 70 °C (-40 ... 158 °F)) Influence of ambient temperature
Influence of ambient temperature< 2 µA/K (-40 ... 70 °C (-40 ... 158 °F))
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Settling timemax. 200 ms
Rise time/fall timemax. 100 ms (10 ... 90 %)

Galvanic isolation

Field circuit/control circuitbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Control circuit/control circuitchannel I/channel II : functional isolation, rated voltage: 50 V
Field circuit/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Control circuit/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff

Indicators/settings

Display elementsLED
Factory settinganalog input with source output
Configurationvia DIP switches
Labelingspace for labeling at the front

Directive conformity

Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations) Directive 2014/30/EU
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)

Conformity

Electromagnetic compatibilityNE 21:2017 EN 61326-3-2:2018 For further information see system description.
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012
Functional safetyIEC 61508:2010

Ambient conditions

Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity95 % non-condensing

Mechanical specifications

Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Height106 mmWidth12.5 mmDepth128 mm Height
Height106 mm
Width12.5 mm
Depth128 mm
Mountingon termination board
Codingpin 1 and 3 trimmed For further information see system description.

Data for application in connection with hazardous areas

EU-type examination certificateUL 23 ATEX 3091 X
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] IOutputEx ia, Ex iaDVoltageUo25.2 VCurrentIo100 mAPowerPo630 mWInternal capacitanceCi1.05 nFInternal inductanceLi 0 Marking
MarkingII (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
OutputEx ia, Ex iaD
Voltage25.2 V Uo
Current100 mA Io
Power630 mW Po
Internal capacitance1.05 nF Ci
Internal inductance0 Li
Supply
Maximum safe voltageUm250 V rms (Attention! The rated voltage can be lower.)Um Maximum safe voltage
Maximum safe voltage250 V rms (Attention! The rated voltage can be lower.) Um
Input
Maximum safe voltageUm250 V rms (Attention! The rated voltage can be lower.)Um Maximum safe voltage
Maximum safe voltage250 V rms (Attention! The rated voltage can be lower.) Um
CertificateUL 23 ATEX 3092 X
Marking II 3G Ex ec IIC T4 Gc Marking
MarkingII 3G Ex ec IIC T4 Gc
Galvanic isolation
Field circuit/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V Field circuit/power supply
Field circuit/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018 Directive 2014/34/EU
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018

International approvals

UL approvalE106378
Control drawing116-0500 (cULus) Control drawing
Control drawing116-0500 (cULus)
IECEx approval
IECEx certificateIECEx ULD 23.0026XIECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc IECEx certificate
IECEx certificateIECEx ULD 23.0026X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc

General information

Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
12-month warrantyon all new stock
3-month warrantyon used & refurbished parts
30-day returnsno restocking fee on unused parts
Global shippingFast, tracked delivery worldwide

More Pepperl Fuchs parts

Pepperl + Fuchs KFD2-GUT-EX1.D New open boxNewPepperl + Fuchs KFD2-GUT-EX1.D New open box
MPN: KFD2-GUT-EX1.D · Pepperl Fuchs
€380.54
View details
50025-c21.1/2 - pepperl+fuchsUsed50025-c21.1/2 - pepperl+fuchs
MPN: 50025-c21.1/2 · Pepperl Fuchs
€10.60
View details
Pepperl Fuchs V19-W-BK15M-PUR-U-V19-GAvailable on requestPepperl Fuchs V19-W-BK15M-PUR-U-V19-G
MPN: V19-W-BK15M-PUR-U-V19-G · Pepperl Fuchs
Price on request
Request a quote
Pepperl Fuchs V1SD-G-GN65M-PUR-E1S-V45-GAvailable on requestPepperl Fuchs V1SD-G-GN65M-PUR-E1S-V45-G
MPN: V1SD-G-GN65M-PUR-E1S-V45-G · Pepperl Fuchs
Price on request
Request a quote