Measurement and evaluation of the ambient conditions in the control cabinet

Recording ambient conditions

Recording operating hours and power-on cycles

Saving user data directly on the module

Technology Guarding directly on the module

Supports blackout mode

2 inputs for PT1000 temperature sensors

2 digital inputs 24 VDC

1 digital output 24 VDC

The module is designed for measuring ambient conditions in the control cabinet as well as recording operating hours and power-on cycles. In addition, the module offers the option of storing user data directly on the module, is equipped with a Technology Guard as well as inputs/outputs and supports blackout mode.

Measuring and evaluating ambient conditions

The ambient conditions are continuously evaluated by the module. The duration in which individual parameters are within certain ranges is stored internally. This makes it possible, for example, to determine how long the system remained in a certain temperature range. The histograms recorded by the module can be read out by the user.

Internal module memory for user data

With 512 kB nonvolatile user memory (flash), data from the application can be saved directly on the module and also read back from the module. The data is therefore retained after the module or CPU is restarted and remains with the module in the event that the module is connected to another machine or system, for example . Data retention is maintenance-free – without batteries.

Technology Guarding

With the integrated Technology Guard, it is possible to implement license protection directly via the module instead of the USB dongle. The same functions can be used as with the USB dongle.

Inputs/Outputs

The module is equipped with 2 inputs for PT1000 temperature sensors, 2 digital inputs (24 VDC) and 1 digital output (24 VDC) .

Blackout mode

The integrated blackout mode ensures that module functionality is maintained even in the event of network failure.

Specifications

Short description

I/O moduleMeasurement of ambient conditions:; Temperature in the module, relative humidity, vibration, shock, position, operating hours, power-on cycles; 2 digital inputs, 1 digital output, 2 Pt1000 temperature inputs, Technology Guarding

General information

Diagnostics – Module run/errorYes, using LED status indicator and software
Diagnostics – OutputYes, using LED status indicator and software (output error status)
Blackout mode – ScopeModule
Blackout mode – FunctionModule functionality
Blackout mode – Standalone modeNo
Power consumption – Bus0.4 W
Power consumption – Internal I/O0.1 W
Application memory – Type512 kB flash memory
Application memory – Sectors8 sectors, 64 kB each
Application memory – Data retention20 years at 55°C
Application memory – Guaranteed erase/write cycles100,000 per sector
Application memory – Error-correcting code (ECC)No
Application memory – Write protectionNo
Technology Guard – Data retention10 years at room temperature
Technology Guard – Guaranteed erase/write cyclesUp to 10 million
Technology Guard – Application memory241 bytes customized data
Technology Guard – Coding128-bit AES, SHA-256, 2048-bit RSA, 224-bit ECC
Certifications – CEYes
Certifications – UKCAYes
Certifications – CRA (Cyber Resilience Act)In preparation
Certifications – ULcULus E115267; Industrial control equipment
Certifications – DNVTemperature: B (0 to 55°C); Humidity: B (up to 100%); Vibration: B (4 g); EMC: B (bridge and open deck)
Certifications – CCSYes
Certifications – LRENV1
Certifications – KRYes
Certifications – ABSYes
Certifications – BVEC33B ; Temperature: 5 - 55°C; Vibration: 4 g; EMC: Bridge and open deck
B&R ID code0xF1AE
Status indicatorsI/O function per channel, overload, memory access, TechGuard, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]+0.075

Digital inputs

Input filter – Hardware≤100 μs
Input filter – SoftwareDefault 1 ms, configurable between 0 and 25 ms in 0.2 ms increments
Switching threshold – Low<5 VDC
Switching threshold – High>15 VDC
Quantity2
Nominal voltage24 VDC
Input voltage24 VDC -15% / +20%
Input current at 24 VDCTyp. 3.75 mA
Input circuitSink
Connection type1-wire connections
Input resistanceTyp. 6.4 kΩ
Insulation voltage between channel and bus500 V eff

Resistance measurement temperature inputs

Sensor – Pt1000-40 to 125°C
Temperature sensor resolution – Pt10001 LSB = 0.1°C
Temperature measurement monitoring – Range undershoot0x8001
Temperature measurement monitoring – Range overshoot0x7FFF
Temperature measurement monitoring – Open circuit0x7FFF
Temperature measurement monitoring – General fault0x8000
Temperature measurement monitoring – Open inputs0x7FFF
Quantity2
InputResistance measurement for 2-wire connections
Digital converter resolution12-bit
Filter timeConfigurable
Conversion time1 ms for all inputs
Output formatINT
Input filterAveraging with clipping function
Linearization methodInternal
Permissible input signalShort-term ±15 V
Max. gain drift0.0003 %/°C
Max. offset drift0.06 %/°C
Nonlinearity<0.010%

Temperature and humidity sensor

Temperature measurement – Measurement range-25 to 125°C
Temperature measurement – Resolution0.1°C/LSB
Temperature measurement – Max. error±0.3°C
Humidity measurement – Measurement range5 to 95%
Humidity measurement – Resolution1%/LSB
Humidity measurement – Max. error±2% at 10 to 80% relative humidity; ±3% at <10 and >80% relative humidity
Sensor positionModule-internal
Sampling rate1 s

Acceleration and angle sensor

Acceleration measurement – Measurement range±16 g
Acceleration measurement – Resolution0.488 mg/LSB
Acceleration measurement – Linearity over temperature±1% at -40 to 85°C
Acceleration measurement – Offset calibration error±40 mg
Angular velocity measurement – Measurement range±2000 dps (note: dps: Degrees per second (°/s))
Angular velocity measurement – Resolution±70 mdps per LSB
Angular velocity measurement – Linearity over temperature±1.5% at -40 to 85°C
Angular velocity measurement – Offset calibration error±10 dps
Sensor positionModule-internal
Sampling rateTyp. 10 ms

Digital outputs

Switching delay – 0 → 1<300 µs
Switching delay – 1 → 0<300 µs
Switching frequency – Resistive loadMax. 100 Hz
Switching frequency – Inductive loadSee section "Switching inductive loads".
Protective measures – Short-circuit proofYes
Protective measures – Overload-proofTemporary overload
Quantity1
VariantCurrent-sourcing FET
Nominal voltage24 VDC
Switching voltage24 VDC -15% / +20%
Nominal output current0.5 A
Connection type1- or 2-wire connections
Output circuitSource
Diagnostic statusOutput monitoring with 10 ms delay
Leakage current when the output is switched off120 µA
R DS(on)300 mΩ
Insulation voltage between channel and bus500 V eff

Electrical properties

Electrical isolationAnalog channel not isolated from bus; Digital channel isolated from bus; Digital channel not isolated from digital channel

Operating conditions

Mounting orientation – HorizontalYes
Mounting orientation – VerticalYes
Installation elevation above sea level – 0 to 2000 mNo limitation
Installation elevation above sea level – >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20

Ambient conditions

Temperature – Horizontal mounting orientation-25 to 60°C
Temperature – Vertical mounting orientation-25 to 50°C
Temperature – Derating-
Temperature – Storage-40 to 85°C
Temperature – Transport-40 to 85°C
Relative humidity – Operation5 to 95%, non-condensing
Relative humidity – Storage5 to 95%, non-condensing
Relative humidity – Transport5 to 95%, non-condensing

Mechanical properties

NoteOrder 1x terminal block X20TB12 separately.; Order 1x bus module X20BM11 separately.
Pitch12.5 +0.2 mm

Accessories

Required accessories (order separately)

X20BM15Bus modules — The bus module is the base for all X20 24 VDC I/O modules; The internal I/O supply is interconnected; Manual node number assignment; Indepe…
X20BM11Bus modules — Bus module for 24 VDC I/O modules; The internal I/O power supply is connected through. The bus module is the base for all 24 VDC I/O module…
X20TB12Terminal blocks — Tool-free wiring with push-in technology; Simple wire release using lever; Ability to label each terminal; Plain text labeling also possibl…

X20CMR111: frequently asked questions

When can X20CMR111 be shipped?

X20CMR111 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up X20CMR111 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for X20CMR111 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for X20CMR111, subject to availability and destination.

More B&R parts

B&R X20cMM2436 – I/O module, 2-channel PWM motor bridge
B&R
X20cMM2436

I/O module, 2-channel PWM motor bridge

B&R X20CMR010 – I/O module, measurement of ambient conditions
B&R
X20CMR010

I/O module, measurement of ambient conditions

B&R X20CMR011 – I/O module, measurement of ambient conditions
B&R
X20CMR011

I/O module, measurement of ambient conditions

B&R X20CMR100 – I/O module, measurement of ambient conditions
B&R
X20CMR100

I/O module, measurement of ambient conditions

B&R X20CP0201 – System module, CPU
B&R
X20CP0201

System module, CPU

B&R X20CP0291 – Interfaces, 1x onboard Ethernet
B&R
X20CP0291

Interfaces, 1x onboard Ethernet

B&R X20CP0292 – Interfaces, 1x onboard Ethernet
B&R
X20CP0292

Interfaces, 1x onboard Ethernet

B&R X20CP0410 – Interfaces, 1x Ethernet, 2x USB, 1x X2X Link
B&R
X20CP0410

Interfaces, 1x Ethernet, 2x USB, 1x X2X Link

B&R X20CMR111Price and lead time confirmed within 1 business day
Request a Quote