Quick facts
| Availability | Confirmed on request |
| Category | Bus receivers and transmitters |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can X20BT9400 be shipped?
X20BT9400 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up X20BT9400 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for X20BT9400 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for X20BT9400, subject to availability and destination.
X2X Link bus transmitterFor seamless expansion of the systemUp to 100 m segment lengthSupply for internal I/O power supplyIntegrated X2X Link power supply of the X67 systemOperation only on the rightmost slot To connect an X20 system to an X67 system, a bus transmitter is simply connected to the end of the X20 block so that the X2X Link cable can be clamped. The bus transmitter also provides the X2X Link supply voltage of the X67 system. The X67 system power supply module that was previously always necessary can be omitted.The bus transmitter module is only permitted to be operated with a bus module where the internal I/O power supply is connected through (e.g. X20BM11). If the supply is used for the internal I/O power supply, this potential group is not permitted to be supplied by any other module. An I/O module with bus module X20BM01 must be used to isolate the potential group.
Specifications
Specifications
| Bus transmitter | X2X Link bus transmitter with supply for I/O and integrated X67 system power supply |
| B&R ID code | 0xA238 |
| Status indicators | X2X bus function, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| X2X bus function | Yes, using LED status indicator |
| Power consumption for X2X Link power supply | 1.38 W |
| Bus | 0.5 W |
| As bus transmitter | 0.1 W |
| Additionally as supply module | 0.6 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| KC | Yes |
| Input voltage | 24 VDC -15% / +20% |
| Input current | Max. 0.5 A |
| Fuse | Required line fuse: Max. 10 A, slow-blow |
| Reverse polarity protection | No |
| Parallel connection with X67PS1300 | Yes |
| Overload characteristics | Temporarily short-circuit and overload-proof Observe the corresponding status message (LED "I") or evaluate the software status. |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Nominal output voltage | 24 VDC |
| Behavior on short circuit | Required line fuse |
| Permissible contact load | 10 A |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Derating | - |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 or 1x bus module X20BM15 separately. |
| Pitch | 12.5+0.2 mm |