Isolation amplifier; Current and voltage input signal; Supply voltage: 24 VDC; 6 mm module width
Frequency signal conditioner; Current and voltage output signal; Configuration via software; Supply voltage: 24 VDC; 6 mm module width
Short description:
WAGO's frequency signal conditioner collects 0.1 … 120 kHz signals from NAMUR, NPN or PNP sensors and converts them into a standard analog signal.
Features:
PC configuration interface
Signal acquisition from NAMUR, NPN or PNP sensors
Calibrated measurement range switching
3-way electrical isolation with 2.5 kV test voltage
| Safety Information | Input and output must be safely isolated from any hazardous live parts! |
| Note | Use shielded cables for data and signal lines.Electromagnetic interference is reduced and signal quality increased. Measurement errors, data transmission faults and interference due to excessive voltage can be prevented!, Additional setting options via the WAGO Interface Configuration Software |
| Configuration options | DIP switch, WAGO Interface Configuration Software |
| Input signal type | Frequency generators, NAMUR sensors, NPN/PNP transistor outputs, Mechanical contact (dry contact) |
| Sensor type 1 | frequency generator, NPN/PNP transistor output with pull-up or pull-down resistor |
| Measurement range (frequency) 1 | 0.1 Hz … 120 kHz |
| Pulse length 1 | ≥ 1 µs |
| Measurement span 1 (min.) | 10 Hz |
| Signal level | 1.5 V; 10 V; 20 V (switchable) |
| Input voltage (max.) | ± 31.2 VDC |
| Signal form | Any |
| Coupling | AC/DC (adjustable; AC above 10 Hz) |
| Input resistance | 10 kΩ |
| Sensor type 2 | NAMUR sensor per DIN EN 50227 |
| Measurement range (frequency) 2 | 0.1 Hz … 1 kHz |
| Pulse length 2 | ≥ 500 µs |
| Measurement span 2 (min.) | 10 Hz |
| Sensor supply | 8.2 VDC |
| Signal current (0) | ≤ 1.2 mA |
| Signal current (1) | ≥ 2.1 mA |
| Hysteresis | 0.45 mA |
| Short-circuit current (max.) | 14 mA |
| Short circuit monitoring | ≥ 4.7 mA |
| Wire break monitoring | ≤ 0.2 mA |
| Input resistance 2 | ≤ 600 Ω |
| Sensor type 3 | NPN/PNP transistor output without pull-up or pull-down resistor, mechanical contact (dry contact) |
| Measurement range (frequency) 3 | 0.1 Hz … 20 kHz |
| Pulse length 3 | ≥ 25 µs |
| Measurement span 3 (min.) | 100 Hz |
| Open-circuit voltage | 5 VDC |
| NPN residual voltage | ≤ 1.5 V |
| PNP switching voltage | ≥ 7.5 V (+ residual voltage UCE sat) |
| Output signal type | Current, Voltage |
| Output signal (voltage) | 0 … 5 V, 1 … 5 V, 0 … 10 V, 2 … 10 V |
| Output signal (current) | 0 … 10 mA, 2 … 10 mA, 0 … 20 mA, 4 … 20 mA |
| Load impedance (voltage output) | ≥ 2 kΩ |
| Load impedance (current output) | ≤ 600 Ω |
| Conversion time | Peak-time measurement method (> 400 Hz): < 20 ms; Pulse time measurement method (< 400 Hz): < 200 μs + TCycle duration |
| Transmission error (typ.) | ≤ 0.1 % of upper-range value |
| Temperature coefficient | ≤ 0.01 %/K |
| Power supply type | 24 VDC (SELV) |
| Nominal supply voltage U<sub>S</sub> | 24 VDC |
| Supply voltage range | ±30 % |
| Current consumption at nominal supply voltage | ≤ 50 mA |
| Rated voltage | 300 V |
| Protection type | IP20 |
| Test voltage (input/output/supply) | 2.5 kVAC; 50 Hz; 1 min |
| Overvoltage category | II |
| Pollution degree | 2 |
| Insulation type (input/analog output/supply) | Functional insulation |
| Insulation type (adjacent devices) | Reinforced insulation (safe isolation) |
| Connection technology | Push-in CAGE CLAMP® |
| Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
| Fine-stranded conductor | 0.34 … 2.5 mm² / 22 … 14 AWG |
| Strip length | 9 … 10 mm / 0.35 … 0.39 inches |
| Width | 6 mm / 0.236 inches |
| Height | 94 mm / 3.701 inches |
| Depth from upper-edge of DIN-rail | 97.8 mm / 3.85 inches |
| Mounting type | DIN-35 rail |
| Insulation material (main housing) | Polyamide (PA66) |
| Flammability class per UL94 | V0 |
| Fire load | 0.418 MJ |
| Weight | 27.2 g |
| Ambient temperature (operation) | -25 … +70 °C |
| Ambient temperature (storage) | -40 … +85 °C |
| Processing temperature | -25 … +50 °C |
| Temperature range of connection cable | ≥ (Tambient + 25 K) |
| Temperature range of the connection cable (UL) | 75 °C |
| Relative humidity | 5 … 95 % (no condensation permissible) |
| Operating altitude (max.) | 2000 m |
| Conformity marking | CE |
| EMC immunity to interference | EN 61000-6-2 |
| EMC emission of interference | EN 61000-6-3; EN 61000-6-4 |
| Standards/specifications | EN 61373, EN 61010-2-201 |
| Product Group | 6 (INTERFACE ELECTRONIC) |
| PU (SPU) | 1 pcs |
| Packaging type | bag |
| Country of origin | DE |
| GTIN | 4066966279931 |
| Customs tariff number | 85437090300 |
| UNSPSC | 41113630 |
| eCl@ss 10.0 | 27-21-01-28 |
| eCl@ss 9.0 | 27-21-01-28 |
| ETIM 9.0 | EC002918 |
| ETIM 10.0 | EC002918 |
| ECCN | NO US CLASSIFICATION |
| CAS-No. | 1303-86-2, 1317-36-8, 7439-92-1, 79-94-7, 80-05-7 |
| REACH Candidate List Substance | 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol, 4,4'-isopropylidenediphenol, Diboron trioxide, Lead, Lead monoxide |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 6(c), 7(a), 7(c)-I, 7(c)-II |
| SCIP notification number (Austria) | 6d73a011-84c6-4de8-9203-d6ba0a4a08c8 |
| SCIP notification number (Belgium) | 6cd3b3c9-9745-4390-aa1a-ac93ba1da332 |
| SCIP notification number (Bulgaria) | b01c1302-d9c2-438c-9217-730bfdfae0f7 |
| SCIP notification number (Czech Republic) | e8fd4d44-e267-4bd8-b97b-1fcb8247f4fd |
| SCIP notification number (Denmark) | 4da2ee18-6d67-44d0-9743-ad112597583e |
| SCIP notification number (Finland) | d0fa661d-f8f9-44c9-878c-daf953ee7c3a |
| SCIP notification number (France) | b6021de5-253c-45e8-9fd6-fea69eda5701 |
| SCIP notification number (Germany) | 07e3e21f-4fb2-4986-8866-7a14b9699500 |
| SCIP notification number (Hungary) | 0606f24e-06bf-4ebc-a260-31eab59b8e88 |
| SCIP notification number (Italy) | 6fc50000-c684-468e-973f-e70a3fb7bf3b |
| SCIP notification number (Netherlands) | 0de14568-55e9-47a7-877e-b1bb752ffa03 |
| SCIP notification number (Poland) | 37c59afc-3304-41ef-b57e-b4af0981cd37 |
| SCIP notification number (Romania) | b23ce25d-4008-47ae-b458-9cacfbfae760 |
| SCIP notification number (Sweden) | 721e6b08-10d7-4ada-96af-c2849dd874af |
No matching specifications
857-500 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 857-500 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 857-500, subject to availability and destination.

Isolation amplifier; Current and voltage input signal; Supply voltage: 24 VDC; 6 mm module width

Loop-powered isolation amplifier; Bipolar current and voltage input signal; Current output signal; Configuration via DIP switch; Power supply via output; 6 mm module width; 2,50 mm²

Passive isolator, 1-channel; Current input signal; Current output signal; Power via input; 6 mm module width; 2,50 mm²

Passive isolator, 2-channel; 2 x current input signal; 2 x current output signal; Power via input; 6 mm module width; 2,50 mm²

Threshold value switches; Analog values; 1 changeover contact; Digital output; Configuration via software; Supply voltage: 24 VDC; 6 mm module width; 2,50 mm²

Current signal conditioner; Current input signal; Current and voltage output signal; Digital output; Configuration via software; Supply voltage: 24 VDC; 6 mm module width; 2,50 mm²

Current signal conditioner; Current input signal; Current and voltage output signal; Digital output; Configuration via software; Supply voltage: 24 VDC; 6 mm module width

Current signal conditioner; Input for Rogowski coils; Current and voltage output signal; Digital output; Configuration via software; Supply voltage: 24 VDC; 6 mm module width; 2,50 mm²