Temperature signal conditioner; Current and voltage output signal; Configuration via software; Supply voltage: 24 VDC
3-Phase Power Measurement Module; 3x277/480 V/RC; Modbus RTU; Digital output; Configuration via software; Supply voltage: 24 VDC
Short description:
WAGO's 3-phase power measurement module in a DIN-rail-mount enclosure measures electrical data in three-phase supply networks – remotely from the control level.
Measured variables such as active/apparent/reactive power, energy consumption, power factor, phase angle and frequency can be accessed via Modbus ® interface. In addition, the measured variables can be stored on a microSD card.
Features:
Current measurement via Rogowski Coils RC xxx
Mobile measurement and storage of measured values on microSD card
Configuration and display of measured values during operation via configuration interface
Compact device in DIN-rail-mount enclosure saves space used for building technology
Communication of measured values via Modbus ® interface
Configurable digital signal output as pulse output
| Note | Additional setting options via the WAGO Interface Configuration Software |
| Configuration options | WAGO Interface Configuration Software |
| Input signal type | Voltage, Current, RTD sensors |
| Network configuration | 3-phase power measurement with N-conductor (4-conductor), 3-phase power measurement without N-conductor (3-conductor) |
| Sensitivity | 22.5 mV/kA (WAGO Rogowski Coils RC xxx) |
| Measured variable | Voltage, Current, Electrical output, Power factor, RTD |
| Input signal (voltage) | 277 VAC (ULN), 480 VAC (ULL), 90 mVAC (WAGO Rogowski Coils RC xxx) |
| Measurement range (current) | 4 x AC 4000 A (WAGO Rogowski Coils RC xxx) |
| Frequency range | 50 … 60 Hz (Harmonic analysis: 0 … 3.3 kHz) |
| Number of devices (max.) | 32 |
| Addressing | Via interface configuration software |
| Connector | 2 x RJ-45 (daisy chain configuration) |
| Configurable functions (DO) | Threshold Value Switch, Pulse output (S0 interface) |
| Switching voltage (DO) max. | Supply voltage applied |
| Continuous current (DO) max. | 100 mA (no internal restriction) |
| Communications | Modbus RTU |
| Interface | RS-485 (2-wire) via RJ-45 |
| Number of devices (max.) | 32 |
| Addressing | Via interface configuration software |
| Measurement method | True RMS measurement (measured value acquisition with 8 kHz) |
| Measured variables (calculated) | Line-to-line voltage, Outputs, Energy sources, Power factors, Mains frequency, Harmonics analysis (up to 41st harmonic), Total Harmonic Distortion (THD) |
| Signal form | Any periodic signals (considering the threshold frequencies) |
| Type of memory card | WAGO 758-879/000-3102 (microSD; 2 GB) |
| Limit frequency | 15.9 kHz |
| Transmission error (max.) | ≤ 0.5 % for current and voltage (of the full scale value) |
| Power supply type | 24 VDC |
| Nominal supply voltage U<sub>S</sub> | 24 VDC (SELV) |
| Supply voltage range | ±30 % |
| Current consumption at nominal supply voltage | ≤ 50 mA (+ IDO) |
| Rated voltage | 600 V |
| Overvoltage category | III |
| Pollution degree | 2 |
| Safe isolation | Input/supply and communication per EN 61010-1 |
| Requirement (N input) | Neutral conductors that are part of the mains circuit are considered dangerous voltage. |
| IL<sub>x</sub> input requirement | Coils/converters with basic insulation |
| Protection type | IP20 |
| Test voltage (input/output/supply) | 3.51 kVAC; 50 Hz; 1 min |
| Connector | 2 x RJ-45 (daisy chain configuration) |
| Connection type | Voltage |
| Connection technology | Push-in CAGE CLAMP® |
| WAGO connector | WAGO 804 Series |
| Strip length | 10 … 11 mm / 0.39 … 0.43 inches |
| Solid conductor | 0.25 … 2.5 mm² / 24 … 14 AWG |
| Fine-stranded conductor | 0.25 … 2.5 mm² / 24 … 14 AWG |
| Connection type | Current/power supply/DO |
| Connection technology | Push-in CAGE CLAMP® |
| WAGO connector | WAGO 805 Series |
| Strip length | 9 … 10 mm / 0.35 … 0.39 inches |
| Solid conductor | 0.2 … 1.5 mm² / 24 … 16 AWG |
| Fine-stranded conductor | 0.2 … 1.5 mm² / 24 … 16 AWG |
| Connection type | Modbus® communication |
| Width | 72 mm / 2.835 inches |
| Height | 90 mm / 3.54 inches |
| Depth from upper-edge of DIN-rail | 55 mm / 2.165 inches |
| Mounting type | DIN-35 rail |
| Housing design | DIN-rail-mount enclosure |
| Fire load | 0.044 MJ |
| Weight | 117.5 g |
| Ambient temperature (operation) | -40 … +70 °C |
| Ambient temperature (storage) | -40 … +85 °C |
| Relative humidity | 5 … 95 % (non-condensing) |
| Conformity marking | CE |
| EMC immunity to interference | EN 61000-6-2 |
| EMC emission of interference | EN 61000-6-3 |
| Standards/specifications | EN 61010-1 |
| PU (SPU) | 1 pcs |
| Packaging type | Box |
| Country of origin | DE |
| Customs tariff number | 85437090300 |
| UNSPSC | 41113630 |
| eCl@ss 10.0 | 27-21-01-24 |
| eCl@ss 9.0 | 27-21-01-24 |
| ETIM 9.0 | EC002476 |
| ETIM 10.0 | EC002476 |
| ECCN | NO US CLASSIFICATION |
| CAS-No. | 1303-86-2, 1317-36-8, 7439-92-1, 75980-60-8 |
| REACH Candidate List Substance | Diboron trioxide, Lead, Lead monoxide, Perfluorobutane sulfonic acid (PFBS) and its salts, Phosphine oxide, diphenyl(2,4,6-trimethylbenzoyl)- |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 6(c), 7(a), 7(c)-I, 7(c)-II |
| SCIP notification number (Austria) | 78e8d92e-925f-4c66-b5ec-68647b49b08e |
| SCIP notification number (Belgium) | 5047fac3-d43f-41fe-ba06-62402e444659 |
| SCIP notification number (Bulgaria) | 8ace76ff-9ff7-43dd-8e32-a90d93c662bb |
| SCIP notification number (Czech Republic) | bbb1092b-f055-47cc-9ffc-8150c89af982 |
| SCIP notification number (Denmark) | 696328c6-8188-44f1-9188-5088e10b58b1 |
| SCIP notification number (Finland) | a76678c6-ea13-4e70-b28a-454f210e86eb |
| SCIP notification number (France) | daf36ce5-9069-4b4c-994f-4b81ffa182e5 |
| SCIP notification number (Germany) | fc852d8b-7773-49b0-8506-f56b8608c3b6 |
| SCIP notification number (Hungary) | 8045ab8f-f923-4c8b-8231-7cace37df94b |
| SCIP notification number (Italy) | 96d37908-6129-4e61-a249-375845aff44e |
| SCIP notification number (Netherlands) | 5ae37208-cb12-4d14-8504-87b13da70942 |
| SCIP notification number (Poland) | 65a9d9e6-933c-4706-81f5-89349ec513c9 |
| SCIP notification number (Romania) | f5ea3c59-191c-45dd-8361-f6f0160fce4b |
| SCIP notification number (Sweden) | 02f5dcc2-dba4-42b1-a4a8-a27e20e427a0 |
No matching specifications
2857-570/024-000 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 2857-570/024-000 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 2857-570/024-000, subject to availability and destination.

Temperature signal conditioner; Current and voltage output signal; Configuration via software; Supply voltage: 24 VDC

Temperature signal conditioner; Configuration via software; Supply voltage: 24 VDC

Current signal conditioner; Current input signal; Current and voltage output signal; Digital and relay output; Configuration via software; Supply voltage: 24 VDC; 22.5 mm module width

Single-Phase Power Signal Conditioner; Current and voltage input signal; Current and voltage output signal; Digital output; Configuration via software; Supply voltage: 24 VDC

3-Phase Power Measurement Module; 3x277/480 V/1 A; Modbus RTU; Digital output; Configuration via software; Supply voltage: 24 VDC

3-Phase Power Measurement Module; 3x277/480 V/5 A; Modbus RTU; Digital output; Configuration via software; Supply voltage: 24 VDC