Threshold value switches; RTD sensors; 1 make contact; Digital output; Configuration via software; Supply voltage: 24 VDC; 12.5 mm module width; Railway
Current signal conditioner; Current input signal; Current and voltage output signal; Digital and relay output; Configuration via software; Supply voltage: 24 VDC; 22.5 mm module width
Short description:
WAGO's current signal conditioner measures AC/DC currents up to 100 A, while converting the measured current into an analog standard signal at the output.
Features:
Both digital signal output and relay with changeover contact react to configured measurement range limits (on/off switching delay and threshold value switch function can be configured with up to two threshold values).
Clipping capability for analog signal limitation to output end values
Adjustable software filter
Safe 3-way isolation with 3 kV test voltage per EN 61010-1
| Note | This product is powered by 24 VDC, which can be bridged using lateral push-in type jumper bars: (6.1) US+ (BR) and (6.2) GND 2 (BR). With this variant, it is necessary to ensure that the maximum permissible total current of 6 A is not exceeded., Additional setting options via the WAGO Interface Configuration Software |
| Configuration options | DIP switch, WAGO Interface Configuration Software |
| Input signal type | Current |
| Input signal (current) | 0.5 … 100 AAC, ±100 ADC |
| Frequency range | 15 … 1000 Hz |
| Input current (max.) | 100 A AC/DC |
| Response threshold | 500 mA (AC); 250 mA (DC) |
| Resolution (current) | 10 mA, 10 mA |
| Output signal type | Current, Voltage |
| Output signal (voltage) | ±5 V, 0 … 5 V, 1 … 5 V, ±10 V, 0 … 10 V, 2 … 10 V |
| Output signal (current) | ±10 mA, 0 … 10 mA, 2 … 10 mA, ±20 mA, 0 … 20 mA, 4 … 20 mA |
| Load impedance (voltage output) | ≥ 1 kΩ |
| Load impedance (current output) | ≤ 600 Ω |
| Switching voltage (DO) max. | Applied supply voltage − 0.3 V |
| Continuous current (DO) max. | 100 mA (no internal restriction) |
| Number of switching thresholds (DO) | 1 or 2 (adjustable) |
| Configurable rise/fall delay time (DO) | 0 … 60 s (via software) |
| Dielectric strength (open contact) (AC, 1 min) | 1 kV<sub>eff</sub> |
| Number of changeover/switchover contacts | 1 |
| Contact material (relay) | AgNi + Au |
| Switching Voltage, Max. | 250 VAC |
| Dielectric strength (open contact) (AC, 1 min) | 1 kVrms |
| Pull-in time (typ.) | 8 ms |
| Drop-out time (typ.) | 4 ms |
| Bounce time (typ.) | 8 ms |
| Number of switching thresholds (relay) | 1 or 2 (adjustable) |
| Configurable rise/fall delay time (relay) | 0 … 60 s (via software) |
| Measurement method | True RMS measurement; Arithmetic mean value |
| Limit frequency | 3.3 kHz |
| Software filter (adjustable) | Moving average value (filter level: 30) |
| Step response (typ.) | 60 ms (DC; for software filter 3/default setting), 250 ms (AC), 1 ms (DC/AC for signals < 0.5 A) |
| Transmission error (max.) | ≤ 1 % (of the full scale value) |
| Temperature coefficient | ≤ 0.01 %/K |
| Power supply type | 24 VDC |
| Nominal supply voltage U<sub>S</sub> | 24 VDC |
| Supply voltage range | ±30 % |
| Current consumption at nominal supply voltage | ≤ 50 mA (+ IDO) |
| Rated voltage | 300 V |
| Rated voltage of the measurement circuit connections per EN 61010-2-030 | AC 300 V |
| Measurement category per EN/UL 61010-2-030 | CAT II (input) |
| Note on insulation parameters | The conductor carrying the measurement current must have at least basic insulation rated for the applied voltage. The test voltage of the conductor carrying the measurement current must be at least 1390 VAC rms or 1390 VDC. The digital output (DO) operates at the supply potential. |
| Protection type | IP20 |
| Test voltage (input/output/supply) | 3 kVAC; 50 Hz; 1 min |
| Test voltage (measurement circuit/relay output/supply/analog output) | 3 kVAC; 50 … 60 Hz; 1 min |
| Test voltage (measurement circuit/relay output/supply/service interface) | 3 kVAC; 50 … 60 Hz; 1 min |
| Test voltage (analog output/service interface) | 2 kVAC; 50 … 60 Hz; 1 min |
| Overvoltage category | II |
| Pollution degree | 2 |
| Insulation type (measurement circuit/relay output, supply, analog output and service interface) | Double insulation (safe isolation) |
| Insulation type (analog output/service interface) | Basic insulation |
| Insulation type (relay output/supply/analog output and service interface) | Reinforced insulation (safe isolation) |
| Connection technology | Push-in CAGE CLAMP® |
| WAGO connector | picoMAX® 5.0 |
| Solid conductor | 0.2 … 2.5 mm² / 24 … 12 AWG |
| Fine-stranded conductor | 0.2 … 2.5 mm² / 24 … 12 AWG |
| Strip length | 9 … 10 mm / 0.35 … 0.39 inches |
| Feedthrough for measurement conductor | Ø 9.5 mm |
| Width | 22.5 mm / 0.886 inches |
| Height | 105 mm / 4.134 inches |
| Depth from upper-edge of DIN-rail | 107 mm / 4.213 inches |
| Mounting type | DIN-35 rail |
| Fire load | 1.787 MJ |
| Weight | 102.8 g |
| Ambient temperature (operation) | -40 … +70 °C |
| Ambient temperature (storage) | -40 … +85 °C |
| Temperature range of connection cable | ≥ (Tambient + 10 K) |
| Temperature range of the connection cable (UL) | 80 °C |
| Conformity marking | CE |
| EMC immunity to interference | EN 61000-6-2; EN 61326-2-3; EN 50121-3-2 |
| EMC emission of interference | EN 61000-6-4; EN 61326-2-3; EN 50121-3-2 |
| Standards/specifications | EN 61010-1, EN 61373, EN 50121-3-2 |
| Product Group | 6 (INTERFACE ELECTRONIC) |
| PU (SPU) | 1 pcs |
| Packaging type | bag |
| Country of origin | DE |
| GTIN | 4050821676997 |
| Customs tariff number | 85437090300 |
| UNSPSC | 41113630 |
| eCl@ss 10.0 | 27-21-01-23 |
| eCl@ss 9.0 | 27-21-01-23 |
| ETIM 9.0 | EC002475 |
| ETIM 10.0 | EC002475 |
| ECCN | NO US CLASSIFICATION |
| CAS-No. | 1303-86-2, 1317-36-8, 7439-92-1, 75980-60-8, 79-94-7 |
| REACH Candidate List Substance | 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol, Diboron trioxide, Lead, Lead monoxide, Perfluorobutane sulfonic acid (PFBS) and its salts, Phosphine oxide, diphenyl(2,4,6-trimethylbenzoyl)- |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 6(c), 7(a), 7(c)-I, 7(c)-II |
| SCIP notification number (Austria) | a9da4d7e-c362-48c9-b365-16c96b3e1576 |
| SCIP notification number (Belgium) | 4903aab4-ec9d-422a-b0b2-73c8b611cfcd |
| SCIP notification number (Bulgaria) | 722fa4c0-c880-415e-8c2a-dd365342643d |
| SCIP notification number (Czech Republic) | aa9f0fda-b2e1-4639-b6fb-061687397b29 |
| SCIP notification number (Denmark) | e9c7dbc7-1077-47de-a91a-bc7b222707ed |
| SCIP notification number (Finland) | f90327c8-eee8-4ea0-ad4e-55438db00e5f |
| SCIP notification number (France) | 89eb3d4b-04a5-4aee-ba79-125fca3d022f |
| SCIP notification number (Germany) | 61796aa8-692d-4b07-b95e-a4e98c7cad2f |
| SCIP notification number (Hungary) | ad4fafc5-8aaa-4d10-a4d5-3846aa90e8a4 |
| SCIP notification number (Italy) | 8890fdc6-2a54-4720-a239-1e68e0fe8c12 |
| SCIP notification number (Netherlands) | 604da37d-2e98-4406-945e-8a36338b1f40 |
| SCIP notification number (Poland) | dff5a515-3b9b-4b48-8f82-f04002ca852b |
| SCIP notification number (Romania) | 681d533f-f33c-4c20-9062-7107db671054 |
| SCIP notification number (Sweden) | e2864b11-4440-44bc-835b-1dc8cf6550e0 |
No matching specifications
2857-550 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 2857-550 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 2857-550, subject to availability and destination.

Threshold value switches; RTD sensors; 1 make contact; Digital output; Configuration via software; Supply voltage: 24 VDC; 12.5 mm module width; Railway

Threshold value switches; Thermocouples; 1 make contact; Digital output; Configuration via software; Supply voltage: 24 VDC; 12.5 mm module width

Temperature signal conditioner; Current and voltage output signal; Configuration via software; Supply voltage: 24 VDC

Temperature signal conditioner; Configuration via software; Supply voltage: 24 VDC

Single-Phase Power Signal Conditioner; Current and voltage input signal; Current and voltage output signal; Digital output; Configuration via software; Supply voltage: 24 VDC

3-Phase Power Measurement Module; 3x277/480 V/RC; Modbus RTU; Digital output; Configuration via software; Supply voltage: 24 VDC

3-Phase Power Measurement Module; 3x277/480 V/1 A; Modbus RTU; Digital output; Configuration via software; Supply voltage: 24 VDC

3-Phase Power Measurement Module; 3x277/480 V/5 A; Modbus RTU; Digital output; Configuration via software; Supply voltage: 24 VDC