Siemens 6ES7212-1BG50-0XB0
SIMATIC S7-1200 G2: compact CPU 1212C AC/DC/RLY; power supply: AC 85-264 V AC at 47-63 Hz
- MPN
- 6ES7212-1BG50-0XB0
- Category
- CPU 1212C
Request a Quote
- 1We check stock, condition and lead time
- 2You get a written quote by email
- 3Approve it and we ship — in-stock parts within 1 business day
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- 100% positive eBay feedback
- Ships via
What is the Siemens 6ES7212-1BG50-0XB0?
SIMATIC S7-1200 G2: compact CPU 1212C AC/DC/RLY; power supply: AC 85-264 V AC at 47-63 Hz; onboard I/O: 8x DI 24 V DC; 6 DO relay 2 A; memory: program 150 KB data: 500 KB, retentivity: 20 KB
Specifications
General information
| Product type designation | CPU 1212C AC/DC/relay |
| Firmware version | V4.1 |
| Firmware version — FW update possible | Yes |
| Product function — I&M data | Yes; I&M0 to I&M3 |
| Product function — Isochronous mode | Yes; For PROFINET only |
| Product function — SysLog | Yes |
| Engineering with — Programming package | STEP 7 V21 or higher |
Supply voltage
| Rated value (AC) — 120 V AC | Yes |
| Rated value (AC) — 230 V AC | Yes |
| permissible range, lower limit (AC) | 85 V |
| permissible range, upper limit (AC) | 264 V |
| Line frequency — permissible range, lower limit | 47 Hz |
| Line frequency — permissible range, upper limit | 63 Hz |
Input current
| Current consumption (rated value) | 70 mA at 120 V AC; 38 mA at 240 V AC |
| Current consumption, max. | 330 mA at 120 V AC; 200 mA at 240 V AC |
| Inrush current, max. | 20 A; at 264 V |
| I²t | 0.8 A²·s |
Output current
| for backplane bus (5 V DC), max. | 1 000 mA; Max. 5 V DC for SM and CM |
Encoder supply
| 24 V encoder supply — 24 V | Yes; 20.4 to 28.8V |
| 24 V encoder supply — Short-circuit protection | Yes |
| 24 V encoder supply — Output current, max. | 300 mA |
Power loss
| Power loss, typ. | 4 W |
Storage
| Work memory — Integrated | 650 kbyte |
| Work memory — integrated (for program) | 150 kbyte |
| Work memory — integrated (for data) | 500 kbyte |
| Load memory — Integrated | 8 Mbyte |
| Load memory — Plug-in (SIMATIC Memory Card), max. | 32 Gbyte; with SIMATIC memory card |
| Backup — present | Yes |
| Backup — maintenance-free | Yes |
| Backup — Without battery | Yes |
CPU processing times
| for bit operations, typ. | 37 ns; / instruction |
| for word operations, typ. | 30 ns; / instruction |
| for floating point arithmetic, typ. | 74 ns; / instruction |
CPU-blocks
| Number of elements (total) | 4 000; Blocks (OB, FB, FC, DB) and UDTs |
| OB — Number of free cycle OBs | 100 |
| OB — Number of time alarm OBs | 20 |
| OB — Number of delay alarm OBs | 20 |
| OB — Number of cyclic interrupt OBs | 20; with minimum OB 3x cycle of 1 ms |
| OB — Number of process alarm OBs | 50 |
| OB — Number of DPV1 alarm OBs | 3 |
| OB — Number of isochronous mode OBs | 1 |
| OB — Number of startup OBs | 100 |
| OB — Number of asynchronous error OBs | 4 |
| OB — Number of synchronous error OBs | 2 |
| OB — Number of diagnostic alarm OBs | 1 |
Data areas and their retentivity
| Retentive data area (incl. timers, counters, flags), max. | 20 kbyte |
| Flag — Size, max. | 8 kbyte; Size of bit memory address area |
| Local data — per priority class, max. | 64 kbyte; max. 16 KB per block |
Address area
| I/O address area — Inputs | 1 kbyte; All inputs are in the process image |
| I/O address area — Outputs | 1 kbyte; All outputs are in the process image |
| Process image — Inputs, adjustable | 1 kbyte |
| Process image — Outputs, adjustable | 1 kbyte |
Hardware configuration
| Number of modules per system, max. | 6 |
| Number of modules per system, max. — number of expansion boards (SB, CB, BB) | 1 |
| Number of modules per system, max. — number of signal modules (SM) | 6; depends on the number of CMs |
| Number of modules per system, max. — number of communications modules (CM) | 3 |
Time of day
| Clock — Hardware clock (real-time) | Yes |
| Clock — Backup time | 480 h; Typical |
| Clock — Deviation per day, max. | 2 s; at 25 °C |
| Clock synchronization — on Ethernet via NTP | Yes |
Digital inputs
| Number of digital inputs | 8; Integrated |
| Number of digital inputs — of which inputs usable for technological functions | 8; HSC (High Speed Counting) |
| Sourcing/sinking input | Yes |
| Number of simultaneously controllable inputs — all mounting positions — up to 40 °C, max. | 8 |
| Input voltage — Rated value (DC) | 24 V |
| Input voltage — for signal "0" | 5 V DC or 0.5 mA |
| Input voltage — for signal "1" | 15 V DC at 2.5 mA |
| Input delay (for rated value of input voltage) — for standard inputs — Parameterizable | 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms |
| Input delay (for rated value of input voltage) — for standard inputs — at "0" to "1", min. | 0.1 µs |
| Input delay (for rated value of input voltage) — for standard inputs — at "0" to "1", max. | 20 µs |
| Input delay (for rated value of input voltage) — for interrupt inputs — Parameterizable | Yes |
| Input delay (for rated value of input voltage) — for technological functions — Parameterizable | single phase: 6 HSCs @ 100 kHz & 2 standard @ 30 kHz, quadrature phase: 6 HSCs @ 80 kHz & 2 standard @ 20 kHz |
| Cable length — shielded, max. | 500 m; 50 m for technological functions |
| Cable length — unshielded, max. | 300 m; for technological functions: No |
Digital outputs
| Number of digital outputs | 6; Relays |
| Switching capacity of the outputs — with resistive load, max. | 2 A |
| Switching capacity of the outputs — on lamp load, max. | 30 W with DC, 200 W with AC |
| Output delay with resistive load — "0" to "1", max. | 10 ms; max. |
| Output delay with resistive load — "1" to "0", max. | 10 ms; max. |
| Switching frequency — of the pulse outputs, with resistive load, max. | Not recommended |
| Relay outputs — Number of relay outputs | 6 |
| Relay outputs — Number of operating cycles, max. | mechanically 10 million, at rated load voltage 100 000 |
| Cable length — shielded, max. | 500 m |
| Cable length — unshielded, max. | 150 m |
Analog inputs
| Number of analog inputs | 0 |
Analog outputs
| Number of analog outputs | 0 |
Encoder
| Connectable encoders — 2-wire sensor | Yes |
Interfaces
| Number of PROFINET interfaces | 1 |
1. Interface
| Interface type | PROFINET |
| Isolated | Yes |
| automatic detection of transmission rate | Yes |
| Autonegotiation | Yes |
| Autocrossing | Yes |
| Interface types — RJ 45 (Ethernet) | Yes; X1 |
| Interface types — RJ 45 (Ethernet) — Transmission rate, max. | 100 Mbit/s |
| Interface types — Number of ports | 2 |
| Interface types — integrated switch | Yes |
| Protocols — IP protocol | Yes; IPv4 |
| Protocols — PROFINET IO Controller | Yes |
| Protocols — PROFINET IO Device | Yes |
| Protocols — SIMATIC communication | Yes |
| Protocols — Open IE communication | Yes; Optionally also encrypted |
| Protocols — Web server | Yes |
| Protocols — Media redundancy | Yes |
| PROFINET IO Controller — Transmission rate, max. | 100 Mbit/s |
| PROFINET IO Controller — Services — PG/OP communication | Yes; encryption with TLS V1.3 pre-selected |
| PROFINET IO Controller — Services — Isochronous mode | Yes |
| PROFINET IO Controller — Services — IRT | Yes |
| PROFINET IO Controller — Services — Dynamic Frame Packing (DFP) | Yes |
| PROFINET IO Controller — Services — PROFIenergy | Yes; per user program |
| PROFINET IO Controller — Services — Prioritized startup | Yes |
| PROFINET IO Controller — Services — Number of IO devices with prioritized startup, max. | 16 |
| PROFINET IO Controller — Services — Number of connectable IO Devices, max. | 31 |
| PROFINET IO Controller — Services — Of which IO devices with IRT, max. | 31 |
| PROFINET IO Controller — Services — Number of connectable IO Devices for RT, max. | 31 |
| PROFINET IO Controller — Services — of which in line, max. | 31 |
| PROFINET IO Controller — Services — Number of IO Devices that can be simultaneously activated/deactivated, max. | 8 |
| PROFINET IO Controller — Services — Updating time | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. |
| PROFINET IO Controller — Update time for IRT — for send cycle of 1 ms | 1 ms to 16 ms |
| PROFINET IO Controller — Update time for IRT — for send cycle of 2 ms | 2 ms to 32 ms |
| PROFINET IO Controller — Update time for IRT — for send cycle of 4 ms | 4 ms to 64 ms |
| PROFINET IO Controller — Update time for RT — for send cycle of 1 ms | 1 ms to 512 ms |
| PROFINET IO Controller — Update time for RT — for send cycle of 2 ms | 2 ms to 512 ms |
| PROFINET IO Controller — Update time for RT — for send cycle of 4 ms | 4 ms to 512 ms |
| PROFINET IO Device — Services — PG/OP communication | Yes; encryption with TLS V1.3 pre-selected |
| PROFINET IO Device — Services — Isochronous mode | No |
| PROFINET IO Device — Services — IRT | Yes |
| PROFINET IO Device — Services — Dynamic Frame Packing (DFP) | No |
| PROFINET IO Device — Services — PROFIenergy | Yes; per user program |
| PROFINET IO Device — Services — Prioritized startup | Yes |
| PROFINET IO Device — Services — Shared device | Yes |
| PROFINET IO Device — Services — Number of IO Controllers with shared device, max. | 2 |
| PROFINET IO Device — Services — Asset management record | Yes |
Protocols
| PROFINET IO | Yes |
| PROFIsafe | No |
| PROFIBUS | No |
| OPC UA | Yes; OPC UA Server |
| AS-Interface | No |
| Protocols (Ethernet) — TCP/IP | Yes |
| Protocols (Ethernet) — DHCP | Yes |
| Protocols (Ethernet) — SNMP | Yes |
| Protocols (Ethernet) — DCP | Yes |
| Protocols (Ethernet) — LLDP | Yes |
| Number of connections — Number of connections, max. | 128; via integrated interfaces of the CPU and connected CPs / CMs |
| Number of connections — Number of connections reserved for ES/HMI/web | 10 |
| Number of connections — Number of connections via integrated interfaces | 88 |
| Number of connections — Number of S7 routing paths | 16 |
| Redundancy mode — PROFINET system redundancy (S2) | No |
| Redundancy mode — PROFINET system redundancy (R1) | No |
| Redundancy mode — Media redundancy — MRP | Yes; as MRP redundancy manager and/or MRP client |
| Redundancy mode — Media redundancy — MRP interconnection, supported | Yes |
| Redundancy mode — Media redundancy — MRPD | Yes; Requirement: IRT |
| Redundancy mode — Media redundancy — Number of stations in the ring, max. | 50 |
| SIMATIC communication — PG/OP communication | Yes; encryption with TLS V1.3 pre-selected |
| SIMATIC communication — S7 routing | Yes |
| SIMATIC communication — S7 communication, as server | Yes |
| SIMATIC communication — S7 communication, as client | Yes; only PUT/GET |
| SIMATIC communication — User data per job, max. | See online help (S7 communication, user data size) |
| Open IE communication — TCP/IP | Yes |
| Open IE communication — TCP/IP — Data length, max. | 64 kbyte |
| Open IE communication — TCP/IP — several passive connections per port, supported | Yes |
| Open IE communication — ISO-on-TCP (RFC1006) | Yes |
| Open IE communication — ISO-on-TCP (RFC1006) — Data length, max. | 64 kbyte |
| Open IE communication — UDP | Yes |
| Open IE communication — UDP — Data length, max. | 2 kbyte; 1 472 bytes for UDP broadcast |
| Open IE communication — DHCP | Yes |
| Open IE communication — DNS | Yes |
| Open IE communication — SNMP | Yes |
| Open IE communication — DCP | Yes |
| Open IE communication — LLDP | Yes |
| Open IE communication — Encryption | Yes; Optional |
| Web server — supported | Yes |
| Web server — HTTPS | Yes |
| Web server — web API | Yes |
| Web server — web API — Number of sessions, max. | 30 |
| Web server — web API — HTTP request body, max. | 131 072 byte |
| Web server — User-defined websites | Yes |
| OPC UA — Runtime license required | Yes; "Basic" license required |
| OPC UA — OPC UA Server | Yes; data access (read, write, subscribe), method call, runtime license required |
| OPC UA — OPC UA Server — Application authentication | Yes |
| OPC UA — OPC UA Server — Security policies | available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256, Aes128Sha256RsaOaep, Aes256Sha256RsaPss |
| OPC UA — OPC UA Server — User authentication | "anonymous" or by user name & password |
| OPC UA — OPC UA Server — Number of sessions, max. | 10 |
| OPC UA — OPC UA Server — Number of subscriptions per session, max. | 5 |
| OPC UA — OPC UA Server — Sampling interval, min. | 100 ms |
| OPC UA — OPC UA Server — Publishing interval, min. | 200 ms |
| OPC UA — OPC UA Server — Number of server methods, max. | 20 |
| OPC UA — OPC UA Server — Number of monitored items, recommended max. | 1 000 |
| OPC UA — OPC UA Server — Number of server interfaces, max. | 2 |
| OPC UA — OPC UA Server — Number of nodes for user-defined server interfaces, max. | 2 000 |
| Further protocols — MODBUS | Yes; MODBUS RTU/TCP |
Communication functions
| S7 communication — supported | Yes |
| S7 communication — as server | Yes |
| S7 communication — As client | Yes |
| S7 communication — User data per job, max. | See online help (S7 communication, user data size) |
| Number of connections — overall | PG Connections: 4 reserved; HMI Connections: 4 reserved / 82 max; S7 Connections: 78 max; Open User Connections: 78 max; Web Connections: 2 reserved / 80 max; Total Connections: 10 reserved / 88 max |
S7 message functions
| Number of login stations for message functions, max. | 32 |
| number of subscriptions, max. | 250 |
| number of tags/attributes for subscriptions, max. | 2 000 |
| Program alarms | Yes |
| Number of configurable program messages, max. | 5 000 |
| Number of loadable program messages in RUN, max. | 2 500 |
| Number of simultaneously active program alarms — Number of program alarms | 600 |
| Number of simultaneously active program alarms — Number of alarms for system diagnostics | 100 |
| Number of simultaneously active program alarms — Number of alarms for motion technology objects | 160 |
Test commissioning functions
| Status block | Yes; Up to 8 simultaneously (in total across all ES clients) |
| Single step | No |
| Profiling | Yes |
| Status/control — Status/control variable | Yes |
| Status/control — Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
| Status/control — Number of variables, max. — of which status variables, max. | 200; per job |
| Status/control — Number of variables, max. — of which control variables, max. | 200; per job |
| Forcing — Forcing | Yes |
| Forcing — Forcing, variables | Peripheral inputs/outputs |
| Forcing — Number of variables, max. | 200 |
| Diagnostic buffer — present | Yes |
| Diagnostic buffer — Number of entries, max. | 500 |
| Diagnostic buffer — Number of entries, max. — of which powerfail-proof | 100 |
| Traces — Number of configurable Traces | 4 |
| Traces — Memory size per trace, max. | 512 kbyte |
Interrupts/diagnostics/status information
| Diagnostics indication LED — RUN/STOP LED | Yes |
| Diagnostics indication LED — ERROR LED | Yes |
| Diagnostics indication LED — MAINT LED | Yes |
Supported technology objects
| Motion Control | Yes |
| Motion Control — Number of available Motion Control resources for technology objects | 800 |
| Motion Control — Required Motion Control resources — per speed-controlled axis | 40 |
| Motion Control — Required Motion Control resources — per positioning axis | 80 |
| Motion Control — Required Motion Control resources — per synchronous axis | 160 |
| Motion Control — Required Motion Control resources — per external encoder | 80 |
| Motion Control — Required Motion Control resources — per output cam | 20 |
| Motion Control — Required Motion Control resources — per cam track | 160 |
| Motion Control — Required Motion Control resources — per probe | 40 |
| Motion Control — Number of available Extended Motion Control resources for technology objects | 40 |
| Motion Control — Required Extended Motion Control resources — per cam (1 000 points and 50 segments) | 2 |
| Motion Control — Required Extended Motion Control resources — for each set of kinematics | 30 |
| Motion Control — kinematics functions — kinematics with up to 4 interpolating axes | Yes |
| Motion Control — kinematics functions — kinematics with 5 or more interpolating axes | No |
| Motion Control — kinematics functions — user-defined kinematics | No |
| Motion Control — kinematics functions — SIMATIC Safe Kinematics | No |
| Motion Control — Positioning axis — Number of positioning axes at motion control cycle of 4 ms (typical value) | 10 |
| Motion Control — Positioning axis — Number of positioning axes at motion control cycle of 8 ms (typical value) | 10 |
Integrated Functions
| Counter | Yes |
| Counter — Number of counters | 8 |
| Counter — Counting frequency, max. | 100 kHz; Ia.0 to Ia.5: 100 kHz (80 kHz in quadrature mode), Ia.6 to Ia.7: 30 kHz (20 kHz in quadrature mode) |
| Frequency measurement | Yes |
| controlled positioning | Yes |
| Number of position-controlled positioning axes, max. | 8 |
| Number of positioning axes via pulse-direction interface | Up to 4 with SB 1222 |
| PID controller | Yes |
| Number of pulse outputs | 8; individually assigned to CPU and Signal Board |
| Limit frequency (pulse) | 100 kHz |
Potential separation
| Potential separation digital inputs — Potential separation digital inputs | Yes; field side to logic: 707 V DC (type test) |
| Potential separation digital inputs — between the channels | No |
| Potential separation digital inputs — Number of potential groups | 1 |
| Potential separation digital outputs — Potential separation digital outputs | Relays |
| Potential separation digital outputs — between the channels | No |
| Potential separation digital outputs — Number of potential groups | 1 |
EMC
| Interference immunity against discharge of static electricity — Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 | Yes |
| Interference immunity against discharge of static electricity — Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 — Test voltage at air discharge | 8 kV |
| Interference immunity against discharge of static electricity — Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 — Test voltage at contact discharge | 6 kV |
| Interference immunity to cable-borne interference — Interference immunity on supply lines acc. to IEC 61000-4-4 | Yes |
| Interference immunity to cable-borne interference — Interference immunity on signal cables acc. to IEC 61000-4-4 | Yes |
| Interference immunity against voltage surge — Interference immunity on supply lines acc. to IEC 61000-4-5 | Yes |
| Interference immunity against conducted variable disturbance induced by high-frequency fields — Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 | Yes |
| Emission of radio interference acc. to EN 55 011 — Limit class A, for use in industrial areas | Yes; Group 1 |
| Emission of radio interference acc. to EN 55 011 — Limit class B, for use in residential areas | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 |
Degree and class of protection
| IP degree of protection | IP20 |
Standards, approvals, certificates
| Siemens Eco Profile (SEP) | Siemens EcoTech |
| CE mark | Yes |
| UL approval | Yes |
| cULus | Yes |
| FM approval | No |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| Marine approval | Yes |
| Ecological footprint — environmental product declaration | Yes; type 2 acc. to ISO 14021 |
| Ecological footprint — Global warming potential — global warming potential, (total) [CO2 eq] | 61.1 kg |
| Ecological footprint — Global warming potential — global warming potential, (during production) [CO2 eq] | 12.4 kg |
| Ecological footprint — Global warming potential — global warming potential, (during operation) [CO2 eq] | 49.2 kg |
| Ecological footprint — Global warming potential — global warming potential, (after end of life cycle) [CO2 eq] | -0.63 kg |
Security
| PROFINET Security Class | 1 |
| signed firmware update | Yes |
| Secure Boot | Yes |
Ambient conditions
| Free fall — Fall height, max. | 0.3 m; five times, in product package |
| Ambient temperature during operation — min. | -20 °C; No condensation |
| Ambient temperature during operation — max. | 40 °C; 40 °C horizontal or 30 °C vertical at max. voltages and max. specifications |
| Ambient temperature during operation — horizontal installation, min. | -20 °C; No condensation |
| Ambient temperature during operation — horizontal installation, max. | 60 °C; at rated voltages, 50 % of max. specification and alternate IO active |
| Ambient temperature during operation — vertical installation, min. | -20 °C; No condensation |
| Ambient temperature during operation — vertical installation, max. | 50 °C; at rated voltages, 50 % of max. specification and alternate IO active |
| Ambient temperature during storage/transportation — min. | -40 °C |
| Ambient temperature during storage/transportation — max. | 70 °C |
| Air pressure acc. to IEC 60068-2-13 — Operation, min. | 540 hPa |
| Air pressure acc. to IEC 60068-2-13 — Operation, max. | 1 140 hPa |
| Air pressure acc. to IEC 60068-2-13 — Storage/transport, min. | 540 hPa |
| Air pressure acc. to IEC 60068-2-13 — Storage/transport, max. | 1 140 hPa |
| Altitude during operation relating to sea level — Installation altitude, min. | -1 000 m |
| Altitude during operation relating to sea level — Installation altitude, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Relative humidity — Operation, max. | 95 %; no condensation |
| Vibrations — Vibration resistance during operation acc. to IEC 60068-2-6 | 3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz |
| Vibrations — Operation, tested according to IEC 60068-2-6 | Yes |
| Shock testing — tested according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
| Pollutant concentrations — SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free |
Configuration
| Programming — Programming language — LAD | Yes |
| Programming — Programming language — FBD | Yes |
| Programming — Programming language — SCL | Yes |
| Know-how protection — User program protection/password protection | Yes |
| Know-how protection — Copy protection | No |
| Know-how protection — Block protection | Yes |
| Access protection — protection of confidential configuration data | Yes |
| Access protection — Protection level: Write protection | Yes |
| Access protection — Protection level: Read/write protection | Yes |
| Access protection — Protection level: Complete protection | Yes |
| Access protection — User administration | Yes; device-wide and centralized |
| Access protection — Number of users | 100 |
| Access protection — Number of groups | 100 |
| Access protection — Number of roles | 50 |
| Cycle time monitoring — can be set | Yes |
Dimensions
| Width | 70 mm |
| Height | 125 mm |
| Depth | 100 mm |
Weights
| Weight, approx. | 373 g |
No matching specifications
Downloads & documentation
Official documents from Siemens, downloaded directly from the manufacturer.
Data sheets & manuals
6ES7212-1BG50-0XB0: frequently asked questions
When can 6ES7212-1BG50-0XB0 be shipped?
6ES7212-1BG50-0XB0 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 6ES7212-1BG50-0XB0 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 6ES7212-1BG50-0XB0 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 6ES7212-1BG50-0XB0, subject to availability and destination.
More Siemens parts