Siemens 6EP4136-0HA00-0AY0
SITOP CAS1600 1.3 Ah 24 V DC 1.3 Ah LiCAP capacitor module with maintenance- free sealed supercapacitors for…
- MPN
- 6EP4136-0HA00-0AY0
- Category
- SITOP CAS1600 capacitor modules
Request a Quote
- 1We check stock, condition and lead time
- 2You get a written quote by email
- 3Approve it and we ship — in-stock parts within 1 business day
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- 100% positive eBay feedback
- Ships via
What is the Siemens 6EP4136-0HA00-0AY0?
SITOP CAS1600 1.3 Ah 24 V DC 1.3 Ah LiCAP capacitor module with maintenance- free sealed supercapacitors for SITOP UPS1600
Specifications
General information
| Technical Product Detail Page | https://i.siemens.com/1P6EP4136-0HA00-0AY0 |
| product brand name | SITOP |
| product type designation | CAS1600 |
| product designation | Capacitor module 1.3 Ah LiCap |
| type of battery | maintenance-free lithium capacitors |
| product version | expansion/capacity module |
electrical data
| end-of-charge voltage at DC — at -10 °C recommended | 28.8 V |
| end-of-charge voltage at DC — at 0 °C recommended | 28.8 V |
| end-of-charge voltage at DC — at 10 °C recommended | 28.8 V |
| end-of-charge voltage at DC — at 20 °C recommended | 28.8 V |
| end-of-charge voltage at DC — at 30 °C recommended | 28.8 V |
| end-of-charge voltage at DC — at 40 °C recommended | 28.8 V |
| end-of-charge voltage at DC — at 50 °C recommended | 28.8 V |
| end-of-charge voltage at DC — at 60 °C recommended | 28.8 V |
output
| battery capacity | 1.3 A·h |
| output current rated value | 40 A |
| output current in buffering mode maximum | 40 A |
| peak current | 120 A; 1x 120 A for 30 ms/1x 60 A for 5 s per minute |
| charging current maximum | 40 A |
| output voltage at DC rated value | 24 V |
| design of the mains power cut bridging-connection | 70 s/40 A |
| number of parallel-switched equipment resources for increasing the power | 4 |
interfaces
| communication function | Yes |
protection and monitoring
| design of short-circuit protection | 50A / 32V Maxi flat fuse |
| design of the overload protection | overpressure valve |
| display version for normal operation | Three-color: green = Buffer ready; yellow = Buffer endangered; red = Buffer not possible |
safety
| operating resource protection class | Class III |
| protection class IP | IP20 |
standards, specifications, approvals
| certificate of suitability — CE marking | Yes |
| certificate of suitability — UL approval | Yes; cULus (UL 61010-1 3rd Ed., UL 61010-2-201 2nd Ed.), File E143289 |
| certificate of suitability — UKCA marking | Yes |
| certificate of suitability — EAC approval | No |
| certificate of suitability — Regulatory Compliance Mark (RCM) | Yes |
| type of certification CB-certificate | Yes |
standards, specifications, approvals hazardous environments
| certificate of suitability — IECEx | No |
| certificate of suitability — ATEX | No |
| certificate of suitability — ULhazloc approval | No |
| certificate of suitability — CCC for hazardous zone according to GB standard | No |
| certificate of suitability — FM registration | No |
standards, specifications, approvals marine classification
| shipbuilding approval | Yes |
| Marine classification association — American Bureau of Shipping Europe Ltd. (ABS) | in preparation |
| Marine classification association — Det Norske Veritas (DNV) | in preparation |
| Marine classification association — Lloyds Register of Shipping (LRS) | No |
| Marine classification association — Nippon Kaiji Kyokai (NK) | No |
standards, specifications, approvals Environmental Product Declaration
| Environmental Product Declaration | Yes |
| global warming potential [CO2 eq] — total | 107.3 kg |
| global warming potential [CO2 eq] — during manufacturing | 95 kg |
| global warming potential [CO2 eq] — during operation | 8.1 kg |
| global warming potential [CO2 eq] — after end of life | 1.78 kg |
ambient conditions
| ambient temperature — during operation | -30 ... +65 °C |
| ambient temperature — during transport | -30 ... +70 °C |
| ambient temperature — during storage | -30 ... +70 °C |
| relative temporary capacity loss at 20 °C in a month typical | 1.5 % |
| installation altitude at height above sea level maximum | 4 000 m |
service life
| service life of energy storage — typical | Reduction of capacity to 80% of the original capacity (according to EUROBAT) - Attention: 80% capacity does not mean 80% of the buffer time; the buffer time is even shorter due to the increase in internal resistance at the end of life |
| service life of energy storage — at 10 °C typical | 15 a |
| service life of energy storage — at 20 °C typical | 15 a |
| service life of energy storage — at 30 °C typical | 15 a |
| service life of energy storage — at 40 °C typical | 12 a |
| service life of energy storage — at 50 °C typical | 7 a |
| service life of energy storage — at 60 °C typical | 3 a |
connection method
| type of electrical connection | screw terminal |
| type of electrical connection — for UPS module | 1 screw terminal each for 0.5 ... 16 mm² for + CAS and - CAS |
| type of electrical connection — for control circuit and status message | 1 screw terminal each for 0.2 ... 2.5 mm² |
mechanical data
| width × height × depth of the enclosure | 225 × 156 × 135 mm |
| installation width × mounting height | 225 mm × 256 mm |
| required spacing — top | 50 mm |
| required spacing — bottom | 50 mm |
| required spacing — left | 0 mm |
| required spacing — right | 0 mm |
| fastening method | can be screwed onto flat surface (keyhole mounting for hooking in to M4 screws) |
| fastening method — DIN-rail mounting | No |
| fastening method — S7 rail mounting | No |
| fastening method — wall mounting | Yes |
| net weight | 6 kg |
| number of cells | 8 |
accessories
| product component included | accessory kit with 2x FKS fuse 50 A, power connector, signal connector |
further information internet links
| internet link — to website: Industry Mall | https://mall.industry.siemens.com |
| internet link — to web page: selection aid TIA Selection Tool | https://www.siemens.com/tstcloud |
| internet link — to web page: power supplies | https://siemens.com/sitop |
| internet link — to website: CAx-Download-Manager | https://www.siemens.com/cax |
| internet link — to website: Industry Online Support | https://support.industry.siemens.com |
additional information
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
security information
| security information | Siemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under https://www.siemens.com/cert. (V4.7) |
No matching specifications
Downloads & documentation
Official documents from Siemens, downloaded directly from the manufacturer.
Data sheets & manuals
6EP4136-0HA00-0AY0: frequently asked questions
When can 6EP4136-0HA00-0AY0 be shipped?
6EP4136-0HA00-0AY0 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 6EP4136-0HA00-0AY0 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 6EP4136-0HA00-0AY0 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 6EP4136-0HA00-0AY0, subject to availability and destination.