Siemens 6AG1231-5PA30-5XB0

SIPLUS S7-1200 SB 1231 1AI RTD based on 6ES7231-5PA30-0XB0 with conformal coating, -40…+60 °C

MPN
6AG1231-5PA30-5XB0
Price and lead time confirmed within 1 business day
Request a Quote
  1. 1We check stock, condition and lead time
  2. 2You get a written quote by email
  3. 3Approve it and we ship — in-stock parts within 1 business day

A real person replies, typically within 1 business day — see our privacy policy.

  • 12-month warranty (new) · 3-month (used/refurbished)
  • 30-day returns, no restocking fee on unused parts
  • 100% positive eBay feedback
  • Ships via

Have spare Siemens parts? We buy surplus →

What is the Siemens 6AG1231-5PA30-5XB0?

SIPLUS S7-1200 SB 1231 1AI RTD based on 6ES7231-5PA30-0XB0 with conformal coating, -40…+60 °C, start up -25 °C, SIPLUS S7-1200, analog input, SB 1231RTD, 1 AI RTD, Pt100 and Pt1000

Specifications

General information

Product type designationSB 1231, AI 1x16 bit RTD
based on6ES7231-5PA30-0XB0

Supply voltage

Rated value (DC)24 V

Input current

Current consumption, typ.5 mA
from backplane bus 5 V DC, typ.20 mA

Power loss

Power loss, typ.0.5 W

Analog inputs

Number of analog inputs1; Resistance thermometer
permissible input voltage for current input (destruction limit), max.±35 V
Technical unit for temperature measurement adjustableDegrees Celsius/degrees Fahrenheit
Input ranges — VoltageYes
Input ranges — CurrentNo
Input ranges — ThermocoupleNo
Input ranges — Resistance thermometerYes; Platinum (Pt)
Input ranges — ResistanceYes; 150 Ω, 300 Ω, 600 Ω
Input ranges (rated values), voltages — 80 mV to +80 mV — Input resistance (-80 mV to +80 mV)>= 10 MOhm
Input ranges (rated values), resistance thermometer — Pt 100Yes
Input ranges (rated values), resistance thermometer — Pt 100 — Input resistance (Pt 100)100 Ω
Input ranges (rated values), resistance thermometer — Pt 1000Yes
Input ranges (rated values), resistance thermometer — Pt 1000 — Input resistance (Pt 1000)1 000 Ω
Input ranges (rated values), resistance thermometer — Pt 200Yes
Input ranges (rated values), resistance thermometer — Pt 200 — Input resistance (Pt 200)200 Ω
Input ranges (rated values), resistance thermometer — Pt 500Yes
Input ranges (rated values), resistance thermometer — Pt 500 — Input resistance (Pt 500)500 Ω
Input ranges (rated values), resistors — 0 to 150 ohmsYes
Input ranges (rated values), resistors — 0 to 300 ohmsYes
Input ranges (rated values), resistors — 0 to 600 ohmsYes
Thermocouple (TC) — Temperature compensation — ParameterizableNo

Analog outputs

Number of analog outputs0
Cable length — shielded, max.100 m; shielded, twisted pair

Analog value generation for the inputs

Measurement principleintegrating
Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max.15 bit; + sign
Integration and conversion time/resolution per channel — Integration time, parameterizableNo
Integration and conversion time/resolution per channel — Interference voltage suppression for interference frequency f1 in Hz85 dB at 10 / 50 / 60 / 400 Hz

Errors/accuracies

Temperature error (relative to input range), (+/-)25 °C ±0.1%, up to 55 °C ±0.25% total measurement range
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency — Common mode interference, min.120 dB

Interrupts/diagnostics/status information

AlarmsYes
Diagnostics functionYes; Can be read out
Alarms — Diagnostic alarmYes
Diagnoses — Wire breakYes
Diagnostics indication LED — for status of the inputsYes
Diagnostics indication LED — for maintenanceYes

Ambient conditions

Free fall — Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation — min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
Ambient temperature during operation — max.60 °C; = Tmax
Ambient temperature during operation — vertical installation, min.-40 °C; = Tmin; Startup @ -25 °C
Ambient temperature during operation — vertical installation, max.50 °C; = Tmax
Ambient temperature during storage/transportation — min.-40 °C
Ambient temperature during storage/transportation — max.70 °C
Altitude during operation relating to sea level — Installation altitude above sea level, max.5 000 m
Altitude during operation relating to sea level — Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity — With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance — Coolants and lubricants — Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Resistance — Use in stationary industrial systems — to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
Resistance — Use in stationary industrial systems — to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
Resistance — Use in stationary industrial systems — to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Resistance — Use on ships/at sea — to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
Resistance — Use on ships/at sea — to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
Resistance — Use on ships/at sea — to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Resistance — Usage in industrial process technology — Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Resistance — Usage in industrial process technology — Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Resistance — Remark — Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating — Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Conformal coating — Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Conformal coating — Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Conformal coating — Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A

Connection method

required front connectorYes

Mechanics/material

Enclosure material (front) — plasticYes

Dimensions

Width38 mm
Height62 mm
Depth21 mm

Weights

Weight, approx.35 g

Downloads & documentation

Official documents from Siemens, downloaded directly from the manufacturer.

Data sheets & manuals

6AG1231-5PA30-5XB0: frequently asked questions

When can 6AG1231-5PA30-5XB0 be shipped?

6AG1231-5PA30-5XB0 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up 6AG1231-5PA30-5XB0 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for 6AG1231-5PA30-5XB0 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 6AG1231-5PA30-5XB0, subject to availability and destination.

More Siemens parts

Siemens 6AG1223-3BD30-5XB0 – SIPLUS S7-1200 SB 1223 I/O based on 6ES7223-3BD30-0XB0 with conformal coating, -40…+60 °C, start up -25 °C
Siemens
6AG1223-3BD30-5XB0

SIPLUS S7-1200 SB 1223 I/O based on 6ES7223-3BD30-0XB0 with…

Siemens 6AG1231-4HF32-4XB0 – SIPLUS S7-1200 SM 1231 8AI based on 6ES7231-4HF32-0XB0 with conformal coating, -20…+60 °C
Siemens
6AG1231-4HF32-4XB0

SIPLUS S7-1200 SM 1231 8AI based on 6ES7231-4HF32-0XB0 with…

Siemens 6AG1231-5ND32-4XB0 – SIPLUS S7-1200 SM 1231 4AI based on 6ES7231-5ND32-0XB0 with conformal coating, -20…+60 °C, analog input
Siemens
6AG1231-5ND32-4XB0

SIPLUS S7-1200 SM 1231 4AI based on 6ES7231-5ND32-0XB0 with…

Siemens 6AG1231-5PD32-2XB0 – SIPLUS S7-1200 SM 1231 RTD based on 6ES7231-5PD32-0XB0 with conformal coating, -40…+70 °C, start up -25 °C
Siemens
6AG1231-5PD32-2XB0

SIPLUS S7-1200 SM 1231 RTD based on 6ES7231-5PD32-0XB0 with…

Siemens 6AG1231-5PD32-4XB0 – SIPLUS S7-1200 SM 1231 based on 6ES7231-5PD32-0XB0 with conformal coating, -20…+60 °C, analog input
Siemens
6AG1231-5PD32-4XB0

SIPLUS S7-1200 SM 1231 based on 6ES7231-5PD32-0XB0 with…

Siemens 6AG1232-4HB32-4XB0 – SIPLUS S7-1200 SM 1232 2AQ based on 6ES7232-4HB32-0XB0 with conformal coating, -20…+60 °C
Siemens
6AG1232-4HB32-4XB0

SIPLUS S7-1200 SM 1232 2AQ based on 6ES7232-4HB32-0XB0 with…

Siemens 6AG1232-4HD32-2XB0 – SIPLUS S7-1200 SM 1232 based on 6ES7232-4HD32-0XB0 with conformal coating, -40…+70 °C, start up -25 °C
Siemens
6AG1232-4HD32-2XB0

SIPLUS S7-1200 SM 1232 based on 6ES7232-4HD32-0XB0 with…

Siemens 6AG1231-5PA30-5XB0Price and lead time confirmed within 1 business day
Request a Quote