Line/motor choke - 2 mH - 17 A - 3 phases - 75 W - for variable speed drive
Passive filter, Altivar, 23A, 400V, 50Hz, for variable speed drive
Schneider Electric passive filter, Altivar, 23A, 400V, 50Hz, for variable speed drive, manufacturer part number VW3A46104. Sourced on request from PartnerPLC — contact us to check availability, condition and lead time.
| Product or component type | Passive filter |
| Product specific application | Reduction of current harmonics |
| Range compatibility | Altivar 61, Altivar Process ATV900, Altivar Process ATV600, Altivar 71 |
| [Us] rated supply voltage | 400 V +/- 10 % |
| power supply frequency | 50 Hz +/- 2 % |
| Quantity per drive | 1 filter per drive for variable speed drive ATV61W motor: 11 kW/15 hp, 1 filter per drive for variable speed drive ATV61H motor: 11 kW/15 hp, 1 filter per drive for variable speed drive ATV71H motor: 11 kW/15 hp, 1 filter per drive for variable speed drive ATV71P motor: 11 kW/15 hp, 1 filter per drive for variable speed drive ATV71W motor: 11 kW/15 hp, 1 filter per drive for variable speed drive ATV630 wall mount, motor: 11 kW/15 hp, 1 filter per drive for variable speed drive ATV650 wall mount, motor: 11 kW/15 hp, 1 filter per drive for variable speed drive ATV930 wall mount, motor: 11 kW/15 hp, 1 filter per drive for variable speed drive ATV950 wall mount, motor: 11 kW/15 hp |
| [In] rated current | 22 A for input, 23 A for output |
| Network number of phases | 3 phases |
| THDI | 10 % for variable speed drive ATV61W motor: 11 kW/15 hp, 16 % for variable speed drive ATV61H motor: 11 kW/15 hp, 16 % for variable speed drive ATV71H motor: 11 kW/15 hp, 16 % for variable speed drive ATV71P motor: 11 kW/15 hp, 16 % for variable speed drive ATV71W motor: 11 kW/15 hp, 10 % for variable speed drive ATV630 motor: 11 kW/15 hp, 10 % for variable speed drive ATV650 motor: 11 kW/15 hp, 10 % for variable speed drive ATV930 motor: 11 kW/15 hp, 10 % for variable speed drive ATV950 motor: 11 kW/15 hp |
| Max current | 1.5 x nominal current (duration = 60 s) |
| Efficiency | 98 % |
| Thermal losses | 206 W |
| Cos phi | 1 (150 % of line current), 0.85 (75 % of line current), 0.99 (100 % of line current) |
| Electrical connection | X1-1...X2-3 terminal, connection capacity: 0.5...10 mm², A, B terminal, connection capacity: 2.5 mm² |
| Electrical insulation class | Class F |
| Net weight | 22 kg |
| IP degree of protection | IP20, IP55 (enclosure mounting) |
| Vibration resistance | 2 mm peak to peak (f= 5…13.2 Hz) conforming to IEC 60068-2-6, 0.7 gn (f= 13.2…150 Hz) conforming to IEC 60068-2-6 |
| Relative humidity | 5…85 % without condensation |
| Ambient air temperature for operation | 45…60 °C (with current derating 3 % per °C), 5…45 °C (without current derating) |
| Ambient air temperature for storage | -25…55 °C storage in original packaging, -25…65 °C during transport |
| Operating altitude | <= 1000 m without current derating, > 1000...4000 m with current derating 5 % per 1000 m |
| Standards | IEC 61000-3-4, G5/4 engineering recommendation, IEC 61000-2-2, IEC 61000-3-2, IEC 61000-3-12, IEC 61000-2-4 |
| Package 1 | 1 PCE, 60.000 cm × 40.000 cm × 56.000 cm (L × W × H), 27.500 kg |
| Package 2 | 2 P06, 80.000 cm × 60.000 cm × 75.000 cm (L × W × H), 64.900 kg |
Official documents from Schneider Electric, downloaded directly from the manufacturer.
VW3A46104 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for VW3A46104 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for VW3A46104, subject to availability and destination.

Line/motor choke - 2 mH - 17 A - 3 phases - 75 W - for variable speed drive

Line/motor choke - 1 mH - 31 A - 3 phases - 90 W - for variable speed drive

Line/motor choke - 0.5 mH - 60 A - 3 phases - 94 W - for variable speed drive