Schneider Electric TM168D23CHL101 – Base Built - in Display M168 - 23 IO - Preprogrammed for Small Chillers
Discontinued by Schneider Electric — we can still source the original TM168D23CHL101 (new, used or refurbished, subject to availability). Request a quote below.
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Modicon M168 |
| Lifecycle | Discontinued |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
| Country of origin | IT |
| UPC / EAN | 3595864109404 |
| Datasheet | Manufacturer datasheet ↗ |
Shipping & availability
Can I still buy the TM168D23CHL101 now that it is discontinued?
Yes. Schneider Electric has discontinued the TM168D23CHL101, but sourcing discontinued parts is what PartnerPLC specialises in — new old stock, used and refurbished units. Request a quote and we'll confirm availability, condition and lead time.
When can TM168D23CHL101 be shipped?
TM168D23CHL101 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up TM168D23CHL101 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for TM168D23CHL101 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for TM168D23CHL101, subject to availability and destination.
Schneider Electric TM168D23CHL101 — Base Built - in Display M168 - 23 IO - Preprogrammed for Small Chillers (Modicon M168). Discontinued by Schneider Electric. PartnerPLC sources discontinued and surplus Schneider Electric automation parts — request a quote for price, condition and lead time.
Specifications
Main
| Range of product | Modicon M168 logic controller |
| Product or component type | Base controller |
| Product specific application | Air cooled chiller |
| Variant | Ready to use without PC |
| Communication port protocol | Modbus |
| Input/output number | 23 |
| Input/output number | 7 discrete input; 5 configurable analog input; 8 discrete output; 1 dedicated PWM output; 2 configurable analog output |
Complementary
| Discrete input number | 7 |
| Discrete input logic | Sink or source (positive/negative) |
| Discrete input voltage | 24 V |
| Discrete input voltage type | AC/DC |
| Sensor power supply | 4.4…5 V DC; 18…36 V DC |
| Voltage state 1 guaranteed | > 15 V for discrete input |
| Voltage state 0 guaranteed | <= 10 V for discrete input |
| Input impedance | Discrete input: <= 10 kOhm |
| Network frequency | 50...60 Hz +/- 3 Hz discrete input |
| Discrete output number | 5 (8 mA); 3 (5 mA) |
| Contacts type and composition | 7 NO for discrete output; 1 C/O for discrete output |
| Minimum load | 10 mA at 12 V |
| Discrete output current | 8 mA for relay output; 5 mA for relay output |
| Load current | 8 A at 5...30 V DC; 8 A at 24...250 V AC; 5 A at 5...30 V DC; 5 A at 24...250 V AC |
| Mechanical durability | 10000000 cycles for relay output |
| Electrical durability | 120000 cycles DC-12 braking current: 8 A at 30 V, 2 A; 6000 cycles DC-13 braking current: 8 A at 24 V, 2 A 300 ms; 300000 cycles AC-12 braking current: 8 A at 250 V, 2.5 A; 6000 cycles AC-15 braking current: 8 A at 250 V, 3 A, cos phi = 0.3; 120000 cycles DC-12 braking current: 5 A at 30 V, 2 A; 200000 cycles DC-13 braking current: 5 A at 24 V, 1 A 48 ms; 300000 cycles AC-12 braking current: 5 A at 250 V, 2.5 A; 50000 cycles AC-15 braking current: 5 A at 250 V, 3 A, cos phi = 0.4 |
| Operating rate in Hz | 10 Hz - off load for discrete output 8 mA; 0.1 Hz - operating current for discrete output 8 mA; 20 Hz - off load for discrete output 5 mA; 0.1 Hz - operating current for discrete output 5 mA |
| Response time | 10 ms on closing for discrete output 8 mA; 5 ms on opening for discrete output 8 mA; 8 ms on closing for discrete output 5 mA; 4 ms on opening for discrete output 5 mA |
| Analogue input number | 5 |
| Analogue input type | Voltage at 0...10 V or 0...5 V ratio - resolution: 0.01 V; Current at 0...20 mA/4...20 mA - resolution: 0.01 mA; Temperature probe at -50...+120 °C - resolution: 0.1 °C temperature probe: NTC; Temperature probe at -50...+150 °C - resolution: 0.1 °C temperature probe: PTC; Temperature probe at -100...+200 °C - resolution: 0.5 °C temperature probe: Pt 1000 |
| Analogue output number | 2 |
| Analogue output type | Voltage 0...10 V - resolution: 0.01 V; Current 0-20 mA or 4-20 mA - resolution: 0.05 mA |
| Load impedance ohmic | >= 1000 Ohm voltage; 40...300 Ohm current |
| Absolute accuracy error | -5 %...+2 % of full scale 1...5 kOhm for analog output voltage; +/- 2 % of full scale > 5 kOhm for analog output voltage; +/- 3 % of full scale for analog output current; +/- 0.5 % of full scale for analog input |
| LSB value | 10 mV for analog output voltage; 0.02 mA for analog output current; 0.07 °C for analog input NTC; 0.5 °C for analog input Pt 1000; 5 mV for analog input voltage; 0.01 mA for analog input current |
| Communication service | Open collector synchro on AC power supply |
| Protection type | Reverse polarity protection for analog input voltage; Overload protection for analog output voltage; Reverse polarity protection for power supply |
| [Us] rated supply voltage | 20...40 V DC; 24 V AC |
| Supply voltage limits | 20.4…27.6 V |
| Network frequency | 50/60 Hz |
| Network frequency limits | 47…63 Hz |
| Immunity to microbreaks | 10 ms |
| Maximum power consumption in W | 22 W |
| Power consumption in VA | 30 VA at 24 V |
| Memory capacity | 544 kB |
| Realtime clock | With clock, clock drift <= 30 s/month |
| Data backed up | Date and hour internal battery, 3 days autonomy |
| Number of port | 1 Modbus RJ45 slave 1.2...57.6 kbit/s; 1 Modbus RJ45 master/slave 1.2...57.6 kbit/s; 1 expansion bus terminal block master/slave |
| Electrical connection | Analog input (AI1 to AI5, GND, +5 V, 24 V) : 9 1 removable screw terminal block; Discrete input (DI1 to DI7, COM) : 8 1 removable screw terminal block; Fan output (FAN+, FAN-) : 2 1 removable screw terminal block; Expansion bus (+24 V, GND, CAN-, CAN+) : 5 1 removable screw terminal block; Power supply (L/+, N/-) : 2 1 removable screw terminal block; Discrete output (NO1 to NO3, COM 1-2, COM 3) : 5 1 removable screw terminal block; Discrete output (NO4 to NO7, COM 6-7, COM 4-5) : 6 1 removable screw terminal block; Discrete output (NO8, NC8, COM8) : 3 1 removable screw terminal block; Analog output (AO1, AO2, GND) : 3 1 removable screw terminal block |
| Maximum cable distance between devices | 2 twisted pair cables: <1000 m for expansion bus; <30 m for power supply; <100 m for embedded sensor PS; <100 m for analog input; <100 m for relay digital output; <30 m for configurable analog output; <1 m for PWM analog output; <1000 m for SL1 bus; <1000 m for SL2 bus; <100 m for isolated digital input; <100 m for no isolated digital input; USB: <3 m for PC programming tool; TTL: <3 m for PC programming tool; <30 m for supply for remote display |
| Display type | Integrated LCD display |
| Local signalling | 1 LED (green) for PWR; 1 LED (green) for RUN; 1 LED (red) for alarm status; 1 LED (red) for expansion bus; 1 LED (red) for user |
| Mounting support | 35 mm symmetrical DIN rail |
| Width | 179 mm |
| Height | 129.19 mm |
| Depth | 61.5 mm |
| Net weight | 0.576 kg |
Environment
| Standards | EN/IEC 60730-1; EN/IEC 61000-6-1; EN/IEC 61000-6-3 |
| Product certifications | CSA 60730-1; UL 60730-1A |
| Marking | CE |
| Ambient air temperature for operation | -10…55 °C conforming to UL; -10…60 °C |
| Ambient air temperature for storage | -30…70 °C |
| Relative humidity | 5…95 % without condensation |
| IP degree of protection | IP20; IP40 front face: |
| Pollution degree | 2 |
| Overvoltage category | III |
| Operating altitude | 0...2000 m |
| Storage altitude | 0…3048 m |
| Vibration resistance | 3.5 mm constant amplitude (f = 5…8.4 Hz); 1 gn constant amplitude (f = 8.4…150 Hz) |
| Shock resistance | 15 gn for 11 ms |
Downloads & documentation
Official documents from Schneider Electric, downloaded directly from the manufacturer.
Data sheets & manuals
| Product data sheet TM168D23CHL101 |
More Schneider Electric parts
Available on requestM168 electronic expansion valve driver module with expansion bus port
Available on requestM168 electronic expansion valve driver module w expansion bus and Mod bus port
Available on requestBase Built - in Display M168 - 23 IO - Preprogrammed for Air Handling Units
Available on requestBase Built - in Display M168 - 23 IO - BMS connectivity
Available on requestBase Built - in Display M168 - 23 IO - BMS connectivity - for Small Chillers
Available on requestBase Built-in Display M168 - 23 IO - Solution - BMS connectivity
Available on requestBase Built-in Display M168 - 23 IO - Solution
Available on requestM168 electronic expansion valve driver module with built - in Display