Frequency control relay, Harmony Control Relays, 5A, 1CO+1CO, 120…277V AC
Current control relay, Harmony Control Relays, 5A, 2CO, overcurrent or undercurrent detection, 0.15…15A, 24…240V AC DC
This Harmony RM35-JA relay allows monitoring of current control in single phase networks. This modular multi function single phase current control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC.
| Range of product | Harmony Control Relays |
| Relay type | Current control relay |
| Product or component type | Current control relay |
| Relay name | RM35JA |
| Relay monitored parameters | Overcurrent or undercurrent detection |
| Time delay type | Adjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault, Adjustable 1...20 s, 0 + 10 % Ti- inhibition time delay upon startup |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 5 A AC/DC |
| Maximum power consumption in VA | 3.5 VA AC |
| Measurement range | 150 mA...15 A current AC/DC |
| Utilisation category | AC-12 conforming to IEC 60947-5-1, AC-13 conforming to IEC 60947-5-1, AC-14 conforming to IEC 60947-5-1, AC-15 conforming to IEC 60947-5-1, DC-12 conforming to IEC 60947-5-1, DC-13 conforming to IEC 60947-5-1, DC-14 conforming to IEC 60947-5-1 |
| Contacts type and composition | 2 C/O |
| Reset time | 1500 ms time delay |
| Maximum switching voltage | 250 V AC/DC |
| Supply voltage limits | 20.4…264 V AC/DC |
| operating voltage tolerance | - 15 % + 10 % Un |
| Maximum power consumption in W | 0.6 W DC |
| Control circuit frequency | 40...70 Hz +/- 10 % |
| Resistance across terminals | 0.005 Ohm at E3-M terminals, 0.015 Ohm at E2-M terminals, 0.05 Ohm at E1-M terminals |
| Output contacts | 2 C/O |
| nominal output current | 5 A |
| Maximum measuring cycle | 30 ms measurement cycle as true rms value |
| Hysteresis | 5…50 % of threshold setting |
| delay at power up | 0.3 s |
| Measurement accuracy | +/- 10 % of the full scale value |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit, +/- 2 % for time delay |
| Measurement error | 0.05 %/°C with temperature variation, 1 by volt over the whole range with voltage variation |
| Polarity | No DC |
| Threshold setting | 10...100 % |
| Marking | CE : EMC 89/336/EEC, CE : 73/23/EEC |
| Overvoltage category | III conforming to IEC 60664-1 |
| Insulation resistance | > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5, > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1, > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5, > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1, > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5, > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1 |
| [Ui] rated insulation voltage | 250 V conforming to IEC 60664-1 |
| Insulation | Between supply and measurement |
| Operating position | Any position without derating |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end, Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end, Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end, Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (green) for power ON, LED (yellow) for relay ON |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Operating rate | <= 360 operations/hour full load |
| [Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz, non self-powered |
| Safety reliability data | MTTFd = 296.8 years, B10d = 270000 |
| Contacts material | Cadmium free |
| Width | 35 mm |
| Control type | Without test button |
| Net weight | 0.13 kg |
| Immunity to microbreaks | 50 ms |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4, Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3, Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
| Standards | IEC 60255-6 |
| Product certifications | GL, UL, GOST, C-Tick, CSA |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| Vibration resistance | 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6, 1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60255-21-1 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529, IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5, 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1 |
| Non-dissipating shock wave | 4 kV conforming to IEC 60255-5, 4 kV conforming to IEC 60664-1, 4 kV conforming to IEC 61000-4-5 |
| Package 1 | 1 PCE, 9.500 cm × 8.000 cm × 4.500 cm (L × W × H), 136.000 g |
| Package 2 | 48 S03, 40.000 cm × 30.000 cm × 30.000 cm (L × W × H), 7.291 kg |
Official documents from Schneider Electric, downloaded directly from the manufacturer.
RM35JA32MW is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for RM35JA32MW and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for RM35JA32MW, subject to availability and destination.

Frequency control relay, Harmony Control Relays, 5A, 1CO+1CO, 120…277V AC

Current control relay, Harmony Control Relays, 5A, 2CO, 2…500mA, 24…240V AC DC

Current control relay, Harmony Control Relays, 5A, 2CO, 0.15…15A, 24…240V AC DC

Current control relay, Harmony Control Relays, 8A, 2CO, 150mA…15A, 380…415V AC




Harmony, 3 phase supply control relay, range 220 to 480 VAC, sequence, phase failure, phase imbalance, voltage