Pepperl Fuchs VBA-2E-KE5-IJL/UJL
AS-Interface analog module
- MPN
- VBA-2E-KE5-IJL/UJL
- Category
- Modules
Request a Quote
- 1We check stock, condition and lead time
- 2You get a written quote by email
- 3Approve it and we ship — in-stock parts within 1 business day
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- 100% positive eBay feedback
- Ships via
What is the Pepperl Fuchs VBA-2E-KE5-IJL/UJL?
Housing with push-in connection technology and mechanically coded terminal blocks
Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
Sensors can be supplied either from the AS-Interface or external auxiliary voltage, as preferred
Function indicator for the bus, external auxiliary voltage, internal sensor supply, and inputs
Switch cabinet module, 2 analog Inputs
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 288595 |
| Node type | Standard node |
| AS-Interface specification | V3.0 |
| Required gateway specification | ≥ V2.1 |
| UL File Number | E223772 |
| MTBF | 154 a |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Indicators/operating means
| LED FAULT | Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault |
| LED INT | Internal input supply active; LED green |
| LED PWR | AS-Interface voltage; green LED Green: voltage OK Flashing green: address 0 or peripheral error |
| LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| LED IN | status of input signal; LED yellow off: not active on: signal within measuring range flashing: signal outside of measuring range |
Electrical specifications
| Auxiliary voltage (output) | 20 ... 30 V DC PELV UAUX |
| Rated operating voltage | 26.5 ... 31.6 V from AS-Interface Ue |
| Rated operating current | ≤ 70 mA (without sensors) / max. 200 mA Ie |
| Protection class | III |
| Current consumption | IAUX ≤ 650 mA |
| Surge protection | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) |
Input
| Number/Type | 2 analog inputsCurrent: 0 ... 20 mA/4 ... 20 mAvoltage: 0 ... 10 V |
| Supply | From AS-Interface (switch setting INT, default setting) or from auxiliary voltage UAUX (switch setting AUX) |
| Current loading capacity | ≤ 100 mA from AS-Interface; overload and short-circuit resistant ≤ 600 mA From auxiliary voltage UAUX (AUX switch position) , overload and short-circuit protected |
| Input resistance | current input: max. 70 Ω voltage input: 100 kΩ |
| Accuracy | 0.1 % of input signal range at 25 °C (298 K) |
| Resolution | 15 Bit |
| Temperature influence | 0.0025 %/K of input signal range |
Output
| Temperature influence | 1 µA/K or 0,3 mV/K |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 62026-2:2013 |
Standard conformity
| Degree of protection | EN 60529:2000 |
| Fieldbus standard | EN 62026-2:2013 |
| Emitted interference | EN 61000-6-4:2007 |
| AS-Interface | EN 62026-2:2013 |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
Programming instructions
| Profile | S-7.3.D |
| IO code | 7 |
| ID code | 3 |
| ID1 code | F |
| ID2 code | D |
| Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. |
| Parameter bits (programmable via AS-i) | function |
| P0 | 50/60 Hz filterP0=1, enabledP0=0, disabled |
| P1 | projecting of the 2nd channel P1=1, channel 2 is projected P1=0, channel 2 is not projected |
| P2 | Indication of the peripheral fault by exceeding measuring rangeP2=1, peripheral fault is reportedP2=0, peripheral fault is not reported |
| P3 | P3=1, normal operating mode P3=0, both channels in current mode and without recognition of wire breakage |
Ambient conditions
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity | 85 % , non-condensing |
| Climatic conditions | For indoor use only |
| Altitude | ≤ 2000 m above MSL |
| Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
| Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Pollution degree | 2 |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | Removable push-in terminalsrated connection capacity:rigid: 0.20 mm2 ... 1.5 mm2flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 |
| Material: Housing | PA 66-FR |
| Mass | 110 g |
| Dimensions: Height | 100 mm |
| Dimensions: Width | 18.9 mm |
| Dimensions: Length | 124 mm |
| Mounting | DIN mounting rail |
| Note | Max. length of jumpers = 5 cm |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
VBA-2E-KE5-IJL/UJL: frequently asked questions
When can VBA-2E-KE5-IJL/UJL be shipped?
VBA-2E-KE5-IJL/UJL is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up VBA-2E-KE5-IJL/UJL in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for VBA-2E-KE5-IJL/UJL and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for VBA-2E-KE5-IJL/UJL, subject to availability and destination.
More Pepperl Fuchs parts