What is the Pepperl Fuchs KFD2-STC5-Ex1.H?

1-channel isolated barrier

24 V DC supply (Power Rail)

Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources

Output 4 mA ... 20 mA current sink/current source

Terminals with test points

High field voltage 17 V DC

Up to SIL 2 (SC 3) acc. to IEC/EN 61508

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 4 mA ... 20 mA current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 18 ... 30 V DC, Field device: 2-wire transmitter

Specifications

General specifications

Order code (Pepperl+Fuchs part number)239217
Signal typeAnalog input
LifecycleActive (current Pepperl+Fuchs product)

Functional safety related parameters

Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3

Supply

ConnectionPower Rail or terminals 14+, 15-
Rated voltage18 ... 30 V DC Ur
Ripplewithin the supply tolerance
Power dissipation≤ 1 W at maximum load
Power consumption≤ 1.6 W at maximum load

Input

Connection sidefield side
Connectionterminals 1+, 2-, 3
Input signal4 ... 20 mA
Open circuit voltage/short-circuit currentterminals 1+, 3: 24 V / 25 mA
Input resistancemax. 265 Ω terminals 2-, 3 , max. 330 Ω terminals 1+, 3
Available voltage≥ 17 V at 20 mA ; ≥ 21 V at 4 mA , terminals 1+, 3

Output

Connection sidecontrol side
Connectionterminals 7+, 8-, 9- (sink) terminals 7-, 8+, 9+ (source) see additional information
Load0 ... 800 Ω
Output signal4 ... 20 mA (overload > 25 mA)
Ripplemax. 50 µA rms
External supply (loop)2 ... 30 V DC If the external voltage is > 19 V, a load ≥ ((V - 19) / 0.02) Ω is required. V represents the value of the external voltage. The internal 250 Ω resistor at terminal 9 can be used as a load.

Transfer characteristics

Deviationat 20 °C (68 °F), 4 ... 20 mA≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Influence of ambient temperature≤ 0.25 µA/K
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Settling time500 µs
Rise time/fall time100 µs

Galvanic isolation

Output/power supplyfunctional insulation, rated insulation voltage 50 V AC

Indicators/settings

Display elementsLED
Labelingspace for labeling at the front

Directive conformity

Electromagnetic compatibility: Directive 2014/30/EUEN 61326-1:2013 (industrial locations)

Conformity

Electromagnetic compatibilityNE 21:2012 EN 61326-3-2:2008
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012

Ambient conditions

Ambient temperature-20 ... 60 °C (-4 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions

Mechanical specifications

Degree of protectionIP20
Connectionscrew terminals
Massapprox. 200 g
Dimensions20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) (W x H x D) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001

Data for application in connection with hazardous areas

EU-type examination certificateCML 17 ATEX 2029X
MarkingII (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Supply: Maximum safe voltage250 V (Attention! The rated voltage can be lower.) Um
Equipmentterminals 1+, 3-
Voltage27.2 V Uo
Current93 mA Io
Power633 mW Po
Internal capacitance5 nF Ci
Internal inductance0 mH Li
Equipmentterminals 2-, 3
Voltage30 V Ui
Current115 mA Ii
Power1 W Pi
Voltage2 V Uo
Current8.5 mA Io
Power1.1 mW Po
Equipmentterminals 1+, 2 / 3-
Voltage27.2 V Uo
Current115 mA Io
Power782 mW Po
Internal capacitance5 nF Ci
Internal inductance0 mH Li
Output: Maximum safe voltage250 V (Attention! The rated voltage can be lower.) Um
CertificateCML 17 ATEX 3028X
MarkingII 3G Ex ec IIC T4 Gc
Galvanic isolation: Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Galvanic isolation: Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Directive conformity: Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN IEC 60079-11:2024

International approvals

UL approvalE106378
Control drawing116-0439 (cULus)
IECEx approval: IECEx certificateIECEx CML 17.0015X
IECEx approval: IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc

General information

Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

KFD2-STC5-Ex1.H: frequently asked questions

When can KFD2-STC5-Ex1.H be shipped?

KFD2-STC5-Ex1.H is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up KFD2-STC5-Ex1.H in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for KFD2-STC5-Ex1.H and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-STC5-Ex1.H, subject to availability and destination.

More Pepperl Fuchs parts

Pepperl Fuchs KFD2-STC5-2 – SMART Transmitter Power Supply
Pepperl Fuchs
KFD2-STC5-2

SMART Transmitter Power Supply

Pepperl Fuchs KFD2-STC5-Ex1 – SMART Transmitter Power Supply
Pepperl Fuchs
KFD2-STC5-Ex1

SMART Transmitter Power Supply

Pepperl Fuchs KFD2-STC5-Ex2 – SMART Transmitter Power Supply
Pepperl Fuchs
KFD2-STC5-Ex2

SMART Transmitter Power Supply

Pepperl Fuchs KFD2-UFC-1.D – Frequency Converter with Trip Values
Pepperl Fuchs
KFD2-UFC-1.D

Frequency Converter with Trip Values

Pepperl Fuchs KFD2-UFC-Ex1.D – Frequency Converter with Trip Values
Pepperl Fuchs
KFD2-UFC-Ex1.D

Frequency Converter with Trip Values

Pepperl Fuchs KFD2-UFT-2.D – Frequency Converter with Direction and Synchronization Monitor
Pepperl Fuchs
KFD2-UFT-2.D

Frequency Converter with Direction and Synchronization Monitor

Pepperl Fuchs KFD2-STC5-Ex1.HPrice and lead time confirmed within 1 business day
Request a Quote