What is the Pepperl Fuchs KFD2-ER-Ex1.W.LB?

1-channel isolated barrier

24 V DC supply (Power Rail)

Level sensing input

Adjustable range 1 kΩ ... 150 kΩ

Relay contact output

Fault relay contact output

Adjustable time delay up to 10 s

Minimum/maximum control

Line fault detection (LFD)

1-channel isolated barrier, 24 V DC supply (Power Rail), Level sensing input, Adjustable range 1 kΩ ... 150 kΩ, Relay contact output, Fault relay contact output, Adjustable time delay up to 10 s, Minimum/maximum control, Line fault detection (LFD), Housing width: 20 mm, Number of channels: 1-channel, Conductivity measurement, Min./max. control, Time delay, Rated voltage: 20 ... 30 V DC, Signal: Resistance, Line fault detection, Type: 2 x relay (change-over contact), Fault indication output

Specifications

General specifications

Order code (Pepperl+Fuchs part number)217732
Signal typeDigital Input
LifecycleActive (current Pepperl+Fuchs product)

Supply

ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 30 V DC Ur
Rated current30 ... 40 mA Ir

Input

Connection sidefield side
Connectionterminals 1 (mass), 2 (min), 3 (max)
Control inputmin./max. control system: terminals 1, 2, 3 on/off control system: terminals 1, 3
Response sensitivity1 ... 150 kΩ , adjustable via potentiometer

Output

Connection sidecontrol side
Connectionterminals 7, 8, 9; 10, 11, 12
Switching powermax. 192 W , 2000 VA
Outputsignal ; relay
Contact loading253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Time constant for signal damping0.5 s, 2 s, 5 s, 10 s

Galvanic isolation

Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Indicators/settings

Display elementsLEDs
Control elementsDIP switch potentiometer
Configurationvia DIP switches via potentiometer
Labelingspace for labeling at the front

Directive conformity

Electromagnetic compatibility: Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EUEN 61010-1:2010

Conformity

Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001

Ambient conditions

Ambient temperature-20 ... 60 °C (-4 ... 140 °F)

Mechanical specifications

Degree of protectionIP20
Connectionscrew terminals , max. 2.5 mm2
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001

Data for application in connection with hazardous areas

EU-type examination certificateDMT 00 ATEX E 033
MarkingII (1)G [EEx ia] IIC [circuit(s) in zone 0/1/2]
Input[EEx ia] IIC
Voltage10 V Uo
Current2.5 mA Io
Power6 mW Po
Supply: Maximum safe voltage40 V DC (Attention! Um is no rated voltage.) Um
Output: Contact loading253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Galvanic isolation: Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EUEN 60079-0:2012+A11:2013, EN 60079-11:2012

General information

Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

KFD2-ER-Ex1.W.LB: frequently asked questions

When can KFD2-ER-Ex1.W.LB be shipped?

KFD2-ER-Ex1.W.LB is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up KFD2-ER-Ex1.W.LB in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for KFD2-ER-Ex1.W.LB and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-ER-Ex1.W.LB, subject to availability and destination.

More Pepperl Fuchs parts

Pepperl Fuchs KFD2-EB2.SP – Power Feed Module
Pepperl Fuchs
KFD2-EB2.SP

Power Feed Module

Pepperl Fuchs KFD2-GS-1.2W – Current/Voltage Trip Value
Pepperl Fuchs
KFD2-GS-1.2W

Current/Voltage Trip Value

Pepperl Fuchs KFD2-GUT-1.D – Temperature Converter with Trip Values
Pepperl Fuchs
KFD2-GUT-1.D

Temperature Converter with Trip Values

Pepperl Fuchs KFD2-GUT-Ex1.D – Temperature Converter with Trip Values
Pepperl Fuchs
KFD2-GUT-Ex1.D

Temperature Converter with Trip Values

Pepperl Fuchs KFD2-ER-Ex1.W.LBPrice and lead time confirmed within 1 business day
Request a Quote