Keyence KV-NC4AD
A/D Conversion unit,4-point type. . Series: Programmable Logic Controller. Series code: KV-X series
- MPN
- KV-NC4AD
- Category
- Programmable Logic Controller
Request a Quote
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- Ships via
What is the Keyence KV-NC4AD?
A/D Conversion unit,4-point type. KV-NC4AD. Series: Programmable Logic Controller. Series code: KV-X series
Specifications
Specifications
| Model Name | A/D Conversion unit,4-point type |
| Model Code | KV-NC4AD |
| Series Title | Programmable Logic Controller |
| Series Code | KV-X series |
| Data Sheet URL | https://www.keyence.com/download/download/confirmation/?dlSeriesId=WS_157158&dlModelId=PM_084C4AD&dlSiteId=1&dlLanguageId=en-US&dlLangType=en-US |
| CAD URL | https://www.keyence.com/products/controls/plc-building-block-type/kv-x/downloads/?mode=cd&modelId=PM_084C4AD |
| Manuals URL | https://www.keyence.com/products/controls/plc-building-block-type/kv-x/downloads/?mode=ma&modelId=PM_084C4AD |
| Model | KV-NC4AD |
| Conversion speed | 80 μs/channel*1 |
| Conversion | A/D conversion |
| Points | 4 (single end) |
| Range/resolution - Voltage | 1/8000 2.5 mV |
| Range/resolution | 1/4000 2.5 mV |
| Range/resolution - Current | 1/4000 5 μA |
| Conversion precision - Voltage | ±0.3% of F.S. (at 25°C ±5°C 77°F ±9°F)±0.5% of F.S. (at 0 to 55°C 32 to 131°F) |
| Conversion precision | ±0.3% of F.S. (at 0 to 55°C 32 to 131°F) |
| Conversion precision - Current | ±0.4% of F.S. (at 25°C ±5°C 77°F ±9°F)±0.6% of F.S. (at 0 to 55°C 32 to 131°F) |
| Input resistance - Voltage | 5 MΩ |
| Input resistance - Current | 250 Ω |
| Absolute maximum input - Voltage | ±15 V |
| Absolute maximum input - Current | ±30 mA |
| Isolation method - Between analog input | Isolated (photocoupler, transformer) |
| Isolation method - Between analogu input channels | No isolation |
| Minimum load resistance | − |
| Special functions | Input range switching,temperature fluctuation compensation enabling/disabling,channel skip, scaling, special data offset, peak-/bottom-hold,zero clip, zero shift, comparator,averaging (time-specified, count-specified, moving average),disconnection detection, |
KV-NC4AD: frequently asked questions
When can KV-NC4AD be shipped?
KV-NC4AD is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KV-NC4AD in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KV-NC4AD and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KV-NC4AD, subject to availability and destination.