Keyence KV-N8EXR
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Programmable Logic Controller |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
| Weight | 0.23 kg |
Shipping & availability
When can KV-N8EXR be shipped?
KV-N8EXR is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KV-N8EXR in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KV-N8EXR and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KV-N8EXR, subject to availability and destination.
Expansion I/O unit,16-point type, Screw Terminal Block, Input 8 points, relay output 8 points. KV-N8EXR. Series: Programmable Logic Controller. Series code: KV-X series
Specifications
Specifications
| Model Name | Expansion I/O unit,16-point type, Screw Terminal Block, Input 8 points, relay output 8 points |
| Model Code | KV-N8EXR |
| Series Title | Programmable Logic Controller |
| Series Code | KV-X series |
| Data Sheet URL | https://www.keyence.com/download/download/confirmation/?dlSeriesId=WS_157158&dlModelId=PM_0848EXR&dlSiteId=1&dlLanguageId=en-US&dlLangType=en-US |
| CAD URL | https://www.keyence.com/products/controls/plc-building-block-type/kv-x/downloads/?mode=cd&modelId=PM_0848EXR |
| Manuals URL | https://www.keyence.com/products/controls/plc-building-block-type/kv-x/downloads/?mode=ma&modelId=PM_0848EXR |
| Model | KV-N8EXR |
| Expansion input unit - External connection method | Terminal block |
| Expansion input unit - Input Points | 8 |
| Expansion input unit - Input terminals | 24 VDC mode, 5 VDC mode |
| Expansion input unit - Maximum input voltage | 26.4 VDC |
| Expansion input unit - Input rated voltage | 5.3 mA |
| Expansion input unit | 1 mA |
| Expansion input unit - Minimum ON voltage | 19 V |
| Expansion input unit - Maximum OFF current | 1.5 mA |
| Expansion input unit - Maximum OFF voltage | 1.5 V |
| Expansion input unit - Common method | 8 points/1 common (1 terminal) *1 |
| Expansion input unit - Input time constant (four-level switching) | 25 μs : 10 μs300 μs : 240 μs1 ms : 1 ms10ms : 10 ms |
| Expansion input unit - Input impedance | 4.3 kΩ |
| Expansion output unit - Output Points | 8 |
| Expansion output unit - External connectionmethod | Relay |
| Expansion output unit - Rated load | 250 VAC/30 VDC, 2 A |
| Expansion output unit - Leakage current (when output is OFF) | − |
| Expansion output unit - ON resistance | 50 mΩ or less |
| Expansion output unit - Common method | 4 points/1 common (2 terminals) *1*2 |
| Expansion output unit - Response time | 10 ms or less |
| Expansion output unit - Relay life | Electrical: 100000 cycles or more (20 cycles/minute)Mechanical: 20000000 cycles or more |
| Expansion output unit - Relay replacement | Impossible |
| Internal current consumption | 60 mA or less |
| Weight | Approx. 230 g |