UMG 96-PQ-L, 24 … 90 V AC, 24 … 90 V DC, TT-Net, TN-Net – Expandable modular power analyzer
AKM RM-E-125, with measuring device UMG 96RM-E – max. outgoing current 125 A
Janitza 60.00.101 — AKM RM-E-125, with measuring device UMG 96RM-E – max. outgoing current 125 A.
Continuous monitoring of the energy supply quality on the busbar optimizes availability of the installation. The tap-off units for busbar systems provide an ideal overview of your consumption.
General features
Measuring device UMG 96RM-E or UMG 806 (depending on type)
Current measurement 3-phase and direct measurement of the neutral conductor current
Fault current measurement type A with integrated differential current transformer CT-AC RCM 35N
Measurement of box internal temperature with PT100 sensor
Power output fused with NH fuses (max. current depending on type)
Communication: 1x RJ45 (Ethernet), 2x M12 (Modbus)
Type tested according to DIN EN 61439
Freely selectable cable outlet direction simplifies installation
Display can be rotated by 180° for laterally correct display
Easy bus installation due to master-slave structures
Cost and IP address saving networking via RS485
Option DI: Pulse input for additional measurements
Optional digital input for recording any process variables (e.g. compressed air or water)
Measured values are standardized and temporarily stored in the AKM
Option RCM plus: Extended residual current measurement
Detection of pulsating fault currents up to 20 kHz (type B+) according to IEC 62020
Alternative to insulation measurement in TN-S systems and thus reduced testing effort on fixed electrical installations within the scope of DGUV V3
Option DI: Pulse input for additional measurements
Optional digital input for recording any process variables (e.g. compressed air or water)
Measured values are standardized and temporarily stored in the AKM
PartnerPLC supplies new, surplus and discontinued Janitza parts — request a quote for price, condition and lead time.
| Janitza item no. | 60.00.101 |
| Product family | AKM |
| Type | 125 |
| Version | With measuring device UMG 96RM-E – max. outgoing current 125 A |
| Product group | Busbar tap-off units |
| Lifecycle | Active |
| Interfaces | Ethernet, RS485 |
| Protocols | Modbus RTU, Modbus Gateway, Modbus TCP/IP |
No matching specifications
Official documents from Janitza, downloaded directly from the manufacturer.
60.00.101 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 60.00.101 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 60.00.101, subject to availability and destination.