UMG 96-PQ-L, 90 … 277 V AC, 90 … 250 V DC, TT-Net, TN-Net – Expandable modular power analyzer
UMG 800 – Modular expandable energy analyzer
Janitza 52.38.002 — UMG 800 – Modular expandable energy analyzer.
The UMG 800 records all necessary energy data in a space-saving, cost-effective way. The potential applications are practically endless. From individual feeder measurements to power quality analyzes to establishing complete measuring systems – the UMG 800 can be customized to meet your requirements (e.g. in data centers, production plants or distribution substation).
Basic data
Size of 2 sub-units
300 V CAT III
Measuring accuracy: Voltage 0.2 %
4 GB data memory
High sampling frequency (51.24 kHz)
1024 samples for voltage measurement
Effective values of half waves 10 ms
Peripherals
RS-485
2 x Ethernet
USB A
Communication
OPC UA
NTP
Modbus TCP/IP Gateway for up to 31 slaves
Gridded averages
Saves critical 200 ms min/max values in order to recognize load peaks at an early stage and avoid costly downtime
Gridded or sliding average values: Recognize trends in good time and make decisions to ensure sustainable energy consumption
Modularity
Expand with up to 13 modules
Up to 96 current measurement inputs
Up to 182 digital inputs
Up to 100 m bridging of measurement points via a connector module
Webserver
Integrated web server for ease of commissioning and configuration
Convenient, remote monitoring, diagnostics, and maintenance
Measuring groups
With virtual meters - create and combine measured variables and measurement groups – totally without additional hardware
Use virtual parameters and reduce hardware costs considerably (savings of up to 25% per measurement channel)
Monitor and analyze energy consumption and power over several modules – even for 3- and 4-phase applications
USB connection
Convenient and safe fault analysis directly on site via a connectable external display
Quick commissioning Quickly and easily upload device configurations and updates via USB
PartnerPLC supplies new, surplus and discontinued Janitza parts — request a quote for price, condition and lead time.
| Janitza item no. | 52.38.002 |
| Product family | UMG 800 |
| Product group | Energy analyzers |
| Lifecycle | Active |
| Certifications | UL certified |
| Supply voltage DC | 24 V DC, PELV |
| Harmonics V / A | 1st – 63rd |
| Memory size | 4 GB |
| Interfaces | RS485, Ethernet, USB |
| Protocols | Modbus RTU, Modbus TCP/IP, OPC UA, Modbus Gateway |
No matching specifications
Official documents from Janitza, downloaded directly from the manufacturer.
52.38.002 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 52.38.002 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 52.38.002, subject to availability and destination.

UMG 96-PQ-L, 90 … 277 V AC, 90 … 250 V DC, TT-Net, TN-Net – Expandable modular power analyzer

UMG 96-PQ-L, 24 … 90 V AC, 24 … 90 V DC, TT-Net, TN-Net – Expandable modular power analyzer

UMG 96-PQ-L, 90 … 277 V AC, 90 … 250 V DC, IT-Net – Expandable modular power analyzer