B&R X20DC4395
I/O module, 2 SSI absolute encoders 24 V
- MPN
- X20DC4395
- Category
- Counter functions
Request a Quote
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- Ships via
What is the B&R X20DC4395?
24 VDC encoder inputs
SSI, ABR, AB or event counters for inputs
Pulse width modulation for outputs
24 VDC and GND for encoder supply
This module is a multifunctional counter module. It can be connected to two SSI encoders, two ABR encoders, four AB encoders or eight event counters. Four outputs are available for pulse width modulation. The functions can also be mixed.
Specifications
Short description
| I/O module | 2 SSI absolute encoders 24 V, 2 ABR incremental encoders 24 V, 4 AB incremental encoders 24 V, 8x event counter or 4x pulse width modulation, time measurement, relative timestamp |
General information
| Diagnostics – Module run/error | Yes, using LED status indicator and software |
| Diagnostics – Outputs | Yes, using LED status indicator and software (output state) |
| Power consumption – Bus | 0.01 W |
| Power consumption – Internal I/O | 1.5 W |
| Certifications – CE | Yes |
| Certifications – UKCA | Yes |
| Certifications – CRA (Cyber Resilience Act) | In preparation |
| Certifications – ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X |
| Certifications – UL | cULus E115267; Industrial control equipment |
| Certifications – HazLoc | cCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5 |
| Certifications – DNV | Temperature: B (0 to 55°C); Humidity: B (up to 100%); Vibration: B (4 g); EMC: B (bridge and open deck) |
| Certifications – CCS | Yes |
| Certifications – LR | ENV1 |
| Certifications – KR | Yes |
| Certifications – ABS | Yes |
| Certifications – BV | EC33B ; Temperature: 5 - 55°C; Vibration: 4 g; EMC: Bridge and open deck |
| Certifications – KC | Yes |
| Input voltage | 24 VDC -15% / +20% |
| B&R ID code | 0x1CC5 |
| Status indicators | I/O function per channel, operating state, module status |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| Type of signal lines | Shielded lines must be used for all signal lines. |
Incremental encoders
| Quantity | 4 |
| Encoder inputs | 24 V, asymmetrical |
| Counter size | 16/32-bit |
| Input frequency | Max. 100 kHz |
| Evaluation | 4x |
| Encoder power supply | Module-internal, max. 600 mA |
| Overload characteristics of encoder power supply | Short-circuit proof, overload-proof |
SSI absolute encoder
| Quantity | 2 |
| Encoder inputs | 24 V, asymmetrical |
| Counter size | 32-bit |
| Max. transfer rate | 125 kbit/s |
| Encoder power supply | Module-internal, max. 600 mA |
| Coding | Gray/Binary |
| CLK: Output current | Max. 100 mA |
| Overload characteristics of encoder power supply | Short-circuit proof, overload-proof |
Event counters
| Input filter – Hardware | ≤2 µs |
| Input filter – Software | - |
| Switching threshold – Low | <5 VDC |
| Switching threshold – High | >15 VDC |
| Quantity | 8 |
| Nominal voltage | 24 VDC |
| Signal form | Square wave pulse |
| Evaluation | Each edge, cyclic counter |
| Input frequency | Max. 100 kHz |
| Input current at 24 VDC | Approx. 1.3 mA |
| Input resistance | 18.4 kΩ |
| Insulation voltage between channel and bus | 500 V eff |
| Counter frequency | 200 kHz |
| Counter size | 16/32-bit |
Edge detection / Time measurement
| Counter frequency – Internal | 8 MHz, 4 MHz, 2 MHz, 1 MHz, 500 kHz, 250 kHz, 125 kHz, 62.5 kHz |
| Possible measurements | Gate time, period duration, edge offset for various channels |
| Measurements per module | Up to 9 |
| Measurements per channel | Up to 2 |
| Signal form | Square wave pulse |
| Counter size | 16-bit |
| Measurement type | Continuous or triggered |
Digital outputs
| Pulse width modulation – Period duration | 41.6 µs to 1.36 s (note: Dead time when switching between push and pull: Max. 1.5 µs.) |
| Pulse width modulation – Factor for period duration | n/48000 s, n = 2 to 65535 (note: Dead time when switching between push and pull: Max. 1.5 µs.) |
| Pulse width modulation – Pulse duration | 0 to 100% (note: Dead time when switching between push and pull: Max. 1.5 µs.) |
| Pulse width modulation – Resolution for pulse duration | 0.1% (note: Dead time when switching between push and pull: Max. 1.5 µs.) |
| Switching delay – 0 → 1 | <2 µs |
| Switching delay – 1 → 0 | <2 µs |
| Switching frequency – Resistive load | Max. 24 kHz |
| Switching frequency – Inductive load | See section "Switching inductive loads". |
| Quantity | 4 |
| Variant | Push / Pull / Push-Pull |
| Nominal voltage | 24 VDC |
| Switching voltage | 24 VDC -15% / +20% |
| Nominal output current | 0.1 A |
| Total nominal current | 0.4 A |
| Output circuit | Sink or source |
| Output protection | Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads |
| Actuator power supply | Module-internal, max. 600 mA |
| Diagnostic status | Output monitoring |
| Leakage current when the output is switched off | Max. 25 µA |
| Residual voltage | <0.9 V at 0.1 A nominal current |
| Peak short-circuit current | <10 A |
| Switch-on in the event of overload shutdown or short-circuit shutdown | Approx. 10 ms (depends on the module temperature) |
| Braking voltage when switching off inductive loads | Switching voltage + 0.6 VDC |
| Insulation voltage between channel and bus | 500 V eff |
Electrical properties
| Electrical isolation | Bus isolated from encoder and output ; Output not isolated from output and encoder ; Encoder not isolated from encoder |
Operating conditions
| Mounting orientation – Horizontal | Yes |
| Mounting orientation – Vertical | Yes |
| Installation elevation above sea level – 0 to 2000 m | No limitation |
| Installation elevation above sea level – >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature – Horizontal mounting orientation | -25 to 60°C |
| Temperature – Vertical mounting orientation | -25 to 50°C |
| Temperature – Derating | - |
| Temperature – Storage | -40 to 85°C |
| Temperature – Transport | -40 to 85°C |
| Relative humidity – Operation | 5 to 95%, non-condensing |
| Relative humidity – Storage | 5 to 95%, non-condensing |
| Relative humidity – Transport | 5 to 95%, non-condensing |
Mechanical properties
| Note | Order 1x terminal block X20TB12 separately.; Order 1x bus module X20BM11 separately. |
| Pitch | 12.5 +0.2 mm |
Accessories
Required accessories (order separately)
| X20BM15 | Bus modules — The bus module is the base for all X20 24 VDC I/O modules; The internal I/O supply is interconnected; Manual node number assignment; Indepe… |
| X20BM11 | Bus modules — Bus module for 24 VDC I/O modules; The internal I/O power supply is connected through. The bus module is the base for all 24 VDC I/O module… |
| X20TB12 | Terminal blocks — Tool-free wiring with push-in technology; Simple wire release using lever; Ability to label each terminal; Plain text labeling also possibl… |
Downloads & documentation
Official documents from B&R, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
Certificates (16)
- 2226379 CSA Certificate of Compliance X20 X67
- 64331_A1 BV Certificate of Compliance X20
- ABS Certificate of Product Design Assessment - X20 IO Series
- CCS Type Approval Certificate - X20
- E115267 UL Certificate of Compliance X20
- EU Data Act - X20 IO - Connected Product Information Notice
- EU Declaration ATEX X20
- EU Declaration of conformity PLC X20
- FTZU 09 ATEX 0083X
- KR Type Approval Certificate MIL39390-AC003 (X20 System)
- Lloyds Register (X20 only)
- RINA Type Approval Certificate - X20 / Power Panel T30
- Safe cutoff of potential groups
- TAA00000BJ DNV Type Approval Certificate X20
- UK Declaration PLC X20
- X20, X67 KC certificates
X20DC4395: frequently asked questions
When can X20DC4395 be shipped?
X20DC4395 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up X20DC4395 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for X20DC4395 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for X20DC4395, subject to availability and destination.
More B&R parts