B&R X20cAO4632
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Analog outputs |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can X20cAO4632 be shipped?
X20cAO4632 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up X20cAO4632 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for X20cAO4632 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for X20cAO4632, subject to availability and destination.
4 analog outputsEither current or voltage signal possible16-bit digital converter resolution The module is equipped with 4 outputs with 16-bit, including sign, digital converter resolution. It is possible to select between the current and voltage signal using different terminals.
Specifications
Specifications
| I/O module | 4 analog outputs ±10 V or 0 to 20 mA |
| B&R ID code | 0xD575 |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Channel type | Yes, using software |
| Bus | 0.01 W |
| Internal I/O | 1.8 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV | Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV | EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
| Output | ±10 V or 0 to 20 mA, via different terminal connections |
| Voltage | Max. 0.11%, from 10 MΩ → 1 kΩ, resistive |
| Current | Max. 0.5%, from 1 Ω → 600 Ω, resistive |
| Conversion time | 50 µs for all outputs |
| Settling time on output change over entire range | 500 µs |
| Switch on/off behavior | Internal enable relay for startup |
| Gain | ±0.09% |
| Offset | ±0.045% |
| Output protection | Short-circuit proof |
| Short-circuit proof | Current limiting ±40 mA |
| Output filter | First-order low-pass filter / cutoff frequency 10 kHz |
| Nonlinearity | <0.005% |
| Insulation voltage between channel and bus | 500 Veff |
| Electrical isolation | Channel isolated from bus Channel not isolated from channel |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | See section "Derating". |
| Starting temperature | Yes, -40°C |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | Up to 100%, condensing |
| Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20cBM11 separately. |
| Pitch | 12.5+0.2 mm |