B&R 8I64T200750.00X-1
ACOPOSinverter X64, 3x 200-240 V, 7.5 kW, integrated brake chopper, shield plate included in delivery
- MPN
- 8I64T200750.00X-1
Request a Quote
- 1We check stock, condition and lead time
- 2You get a written quote by email
- 3Approve it and we ship — in-stock parts within 1 business day
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- 100% positive eBay feedback
- Ships via
What is the B&R 8I64T200750.00X-1?
ACOPOSinverter X64, 3x 200-240 V, 7.5 kW, integrated brake chopper, shield plate included in delivery, X2X Link interface
Specifications
Motor power
| Specified on nameplate | 7.5 kW ; 10 HP |
Mains connection
| Max. mains current with optional mains choke – At 200 VAC | 29.0 A |
| Max. mains current with optional mains choke – At 240 VAC | 25.2 A |
| Max. mains current – At 200 VAC | 46.8 A (note: Typical value for 4-pin motor and a max. clock frequency of 4 kHz, without mains choke for the max. assumed short circuit current (lsc).) |
| Max. mains current – At 240 VAC | 40.9 A (note: Typical value for 4-pin motor and a max. clock frequency of 4 kHz, without mains choke for the max. assumed short circuit current (lsc).) |
| Mains input voltage | 3x 200 VAC -15% to 240 VAC +10% |
| Frequency | 50 to 60 Hz ±5% |
| Apparent power (at 240 VAC) | 16.2 kVA |
| Max. assumed short-circuit current (Isc); (short-circuit current at connection point) | 22 kA (note: Add a line choke if the short-circuit current (lsc) exceeds the values in the table.) |
| Power dissipation at max. output current | 388 W |
| Integrated EMC filter | No |
Line-conducted and radiated emissions
| With add-on filter – Motor cable length per IEC/EN 61800-3 ; Cat. C1 environment 1 (public power network) | - (note: For shielded motor cables) |
| With add-on filter – Motor cable length per IEC/EN 61800-3 ; Cat. C2 environment 1 (public power network) | ≤5 m (note: For shielded motor cables) |
| With add-on filter – Motor cable length per IEC/EN 61800-3 ; Cat. C3 environment 2 (industrial power system) | ≤5 m (note: For shielded motor cables) |
| With add-on filter | 8I0FT047.200-1 |
Motor connection
| Derating of continuous output current depending on ambient temperature – Clock frequency 4 kHz | No derating (up to 50°C) |
| Derating of continuous output current depending on ambient temperature – Other clock frequencies | The derating curves are included in the installation instructions, which can be downloaded from www.br-automation.com. |
| Derating of continuous output current depending on installation elevation – Starting at 1000 m above sea level | 1%, per 100 m |
| Max. continuous output current (In) – At 240 VAC | 33 A |
| Nominal clock frequency – Min. | 2 kHz |
| Nominal clock frequency – Max. | 16 kHz |
| Braking torque – With braking resistor | 100% of the nominal motor torque continuously, up to 150% for 60 s |
| Braking torque – Without braking resistor (typical value) | 30% of the nominal motor torque |
| Max. motor cable length – Shielded cable | 50 m |
| Max. motor cable length – Non-shielded cable | 100 m |
| Max. transient current for 60 s | 49.5 A |
| Output frequency range | 0.5 to 500 Hz |
| Nominal clock frequency | 4 kHz |
| Short-term overload torque (typical value) | 170 to 200% of the nominal motor torque |
| Motor control profiles | Standard profile (voltage/frequency ratio - V/f characteristic curve); Power profile (flux vector control without encoder); Pump/Fan profile (quadratic characteristic curve Kn²) ; Energy-saving profile (especially for ventilation) |
| Main protective functions of inverter | Thermal protection against overheating ; Protection against short circuits between motor phases ; Protection against mains phase failure, for 3-phase power supply ; Protection against motor phase failures ; Overcurrent protection between motor output phases and ground ; Overvoltage and undervoltage protection for mains supply |
| Motor protection | Thermal protection integrated in the inverter by continuous calculation of the l²t value |
Brake chopper
| Integrated dynamic brake transistors | Yes |
| Operating ratio for dynamic brake transistors | The dynamic brake transistor is designed to tolerate the following values: ; -Nominal motor power continuously ; -150% of the nominal motor power for 60 s |
| Min. resistance value (external) | 8 Ω |
Available internal power supplies
| Output voltage – Max. output current | 100 mA |
| Output voltage | 24 VDC (min. 19 V, max. 30 V) |
Interfaces
| Type | X2X and CANopen |
| Min. cycle time | 400 µs |
Digital inputs
| Electrical isolation – Input - ACOPOSinverter | Yes |
| Electrical isolation – Input - Input | No |
| Quantity | 4 (2 can be used as counters) |
| Nominal voltage | 24 VDC |
| Input circuit | Source or sink |
| Sampling time | <4 ms |
| Input impedance | 12.1 kΩ |
Counter input
| Quantity | 2 (digital inputs - can be used as counters) |
| Counter frequency | 10 kHz |
| Counter size | 32-bit |
Digital outputs
| Quantity | 1 |
| Nominal voltage | 24 VDC |
| Output circuit | Source |
| Nominal output current | 0.5 A |
Relay outputs
| Switching capacity – With resistive load (cos φ = 1 and L/R = 0 ms) | 2 A for 250 VAC or 30 VDC |
| Switching capacity – With inductive load (cos φ = 0.4 and L/R = 7 ms) | 1.5 A for 250 VAC or 30 VDC |
| Switching capacity – Min. | 10 mA for 5 VDC |
| Electrical isolation – Output - ACOPOSinverter | Yes |
| Electrical isolation – Output - Output | No |
| Quantity | 1 |
| Variant | 1 NO contact |
| Nominal voltage | 30 VDC / 250 VAC |
| Response time (max.) | <8 ms |
Operating conditions
| Installation elevation above sea level | 0 to 1000 m |
| Degree of protection per EN 60529 | IP31 and IP41 on the upper part and ; IP21 on the terminals |
| Ambient temperature | -10 to 50°C |
| Max. ambient temperature | Up to +60°C (note: With reduction and removal of the top cover of the inverter. For possible mounting types and derating curves, see the installation manual available for download from www.br-automation.com.) |
| Relative humidity per IEC 60068-2-3 | 5 to 95%, non-condensing ; No dripping water |
| Maximum installation elevation | Up to 2000 m (note: From 1000 to 2000 m, current reduced by 1% per 100 m) |
| Max. pollution degree per IEC/EN 61800-5-1 | 2 (non-conductive pollution) |
| Ambient conditions per IEC 60721-3-3 | Class 3C3 and 3S2 |
| Operating position | Vertical mounting orientation ±10% |
Ambient conditions
| Temperature – Storage | -25 to 70°C |
Mechanical properties
| Dimensions – Width | 180 mm |
| Dimensions – Height | 232 mm |
| Dimensions – Depth | 172 mm |
| Weight | 4.7 kg |
No matching specifications
Accessories
Optional accessories (3)
| 8I0BR015.000-1 | Braking resistors — Braking resistor ohmic value: 15 Ω continuous braking power: 1.00 kW degree of protection (IP): IP20 |
| 8I0FT047.200-1 | Optional EMC filters — 47 A EMC filter for ACOPOSinverter P76 and P74new (3-phase 380-500 V, 5.5-7.5 kW). |
| 8I0CT030.000-1 | Optional line chokes — Mains choke 3-phase, 30 A, 50/60 Hz for ACOPOSinverter |
Downloads & documentation
Official documents from B&R, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
Certificates (1)
8I64T200750.00X-1: frequently asked questions
When can 8I64T200750.00X-1 be shipped?
8I64T200750.00X-1 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 8I64T200750.00X-1 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 8I64T200750.00X-1 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 8I64T200750.00X-1, subject to availability and destination.