Bosch Rexroth R911406090
FIELD BUS MODULE XB-EC-12
- MPN
- R911406090
- Category
- XB Bus Couplers
Request a Quote
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- Ships via
- 100% positive eBay feedback
What is the Bosch Rexroth R911406090?
The bus coupler XB-EC-12 connects the EtherCAT network and the ctrlX I/O system.
It supplies the connected I/O modules with the logic voltage UL and peripheral voltage UP. The voltages and currents fed in are measured internally and applied to the process data.
For the integration into the parent system, the respective ESI files are available. These files are available for download at www.boschrexroth.com/electrics.
Specifications
Specifications
| Connection type | Push-in |
| Width [mm] | 23.3 |
| Height [mm] | 105 |
| Depth [mm] | 99 |
| International protection code | IP20 |
| Protection class | III |
| Backplane-Bus | Standard-EtherCAT über LVDS |
| EMC resistance | EN 61000-6-2 and EN 61000-6-4 |
| Bit width, input data in the process data image (including fill bits) | 10 bytes |
| Maximum power dissipation in the module [W] | 2.64 |
| Inverse polarity protection up to [V] | 50 |
| Channel LEDs | Display status of Power supply |
| Post-assembly position | Vertical, on a horizontal support rail |
| Electrical isolation | 1200 V DC UP to UL, 707 V DC UP/UL to FE, both tested for 60 s;(not evaluated by UL) |
| Fuse protection (UP) | No internal fuse protection. The operator has to provide protection against overload by an external fuse. |
| Fuse protection (UL) | Internal with a protective fuse |
| Transient protection | Present, suppressor diodes, pulse load up to 1500 W |
| Maximum number of modules per station | 30 |
| Power input UP | Typ. 0.12 W (without I/O modules), 192 W max. (complete system with I/O modules) |
| Power input UL | 1.64 W max. (without I/O modules), 72 W max. (complete system with I/O modules) |
| Current requirement UL | Max. 60 mA (without I/O modules), 3 A max. (complete system with I/O modules) |
| Current requirement Up | Typ. 7 mA (without I/O modules), 8 A max. (complete system with I/O modules) |
| Nominal voltage (UL/UP) | DC 24 V (19.2 V to 30 V, including tolerance and residual ripple) PELV/SELV (safety extra-low voltage) |
| Overvoltage category | 2 |
| Voltage dips at power supply interfaces | PS1 <1 ms, evaluation criterion A |
| Overvoltage protection UL and UP | Present, fuses can trigger in case of overvoltage |
| Supply voltage LEDs | At the connection point to signal the applied voltage |
| Conductor cross-section | AWG: 18 ... 16; Flexible: 0.75-1.5 mm²; rigid: 0.75-1.5 mm² |
| Permissible air humidity (storage) [%] | 10-95 |
| Permissible air humidity (transport) [%] | 10-95 |
| Ambient temperature (storage and transport) [°C] | -40-70 |
| Ambient temperature during operation | 2,000 m to 3,000 m: -25 °C to +50 °C; 3,000 m to 4,000 m: -25 °C to +45 °C; 4,000 m to 5,000 m: -25 °C to +40 °C; Up to 2,000 m: -25 °C to +55 °C |
| Maximum operating altitude [m] | 5000 |
| Contamination level | 2, no condensation |
| Weight [kg] | 0.18 |
R911406090: frequently asked questions
When can R911406090 be shipped?
R911406090 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up R911406090 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for R911406090 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for R911406090, subject to availability and destination.
More Bosch Rexroth parts