Fieldbus Box, 4-channel analog output, PROFIBUS, current, 0/4…20 mA, 16 bit, single-ended, M12, integrated T-connector
Fieldbus Box, 4-channel analog output, DeviceNet®, current, 0/4…20 mA, 16 bit, single-ended, M12
The IP4112 analog output module generates analog output signals in the range from 0/4 to 20 mA. The power is supplied to the process level with a resolution of 15 bits (default), and is electrically isolated. If the input is transmitted without an
| Number of channels | 4 analog outputs |
| Number of outputs | 4 |
| Output connections | M12, screw type |
| Signal current | 0/4…20 mA |
| Nominal voltage | 24 V DC |
| Load | 500 Ω |
| Resolution | 15 bit, configurable to 16 bit |
| Conversion time | 4 ms |
| Measurement error/uncertainty | ±0.1% (relative to full scale value) |
| Actuator supply | from the auxiliary voltage UP |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Bit width in the process image | output: 4 x 16 bit data, optional: 4 x 8 bit control/status |
| Electrical isolation | control voltage/fieldbus: 500 V, control voltage/inputs or outputs: according to I/O type |
| Current consumption from US (without sensor current) | see documentation |
| Extension modules | – |
| Digital peripheral signals | according to I/O type |
| Analog peripheral signals | according to I/O type |
| Configuration | via KS2000 or the controller (explicit messaging) |
| Data transfer rates | automatic detection up to 500 kbaud |
| Bus interface | 1 x M12 plug, 5-pin |
| Data transfer medium | shielded copper cable, with power supply, typ. 2 x 2 x 0.25 mm² |
| Power supply | control voltage: 24 V DC (-15%/+20%); load voltage: according to I/O type |
| Box supply current | 45 mA + current consumption of sensors, max. 0.5 A |
| Auxiliary power current | according to I/O type |
| Distance between stations | 500 m 250 m 100 m |
| Operating modes | bit strobe, polling, cyclic, change of state (COS) |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
| Approvals/markings | CE, UL |
| Dimensions (W x H x D) | 30 mm x 175 mm x 26.5 mm |
| Material | PA6 (polyamide) |
| Installation | 2 fixing holes 3.5 mm diameter for M3 |
IP4112-B520 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for IP4112-B520 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for IP4112-B520, subject to availability and destination.

Fieldbus Box, 4-channel analog output, PROFIBUS, current, 0/4…20 mA, 16 bit, single-ended, M12, integrated T-connector

Fieldbus Box, 4-channel analog output, Interbus, current, 0/4…20 mA, 16 bit, single-ended, M12

Fieldbus Box, 4-channel analog output, CANopen, current, 0/4…20 mA, 16 bit, single-ended, M12

Fieldbus Box, 4-channel analog output, CANopen, current, 0/4…20 mA, 16 bit, single-ended, M12, integrated T-connector

Fieldbus Box, 4-channel analog output, DeviceNet®, current, 0/4…20 mA, 16 bit, single-ended, M12, integrated T-connector

Fieldbus Box, 4-channel analog output, Modbus, current, 0/4…20 mA, 16 bit, single-ended, M12

Fieldbus Box, 4-channel analog output, RS485, current, 0/4…20 mA, 16 bit, single-ended, M12

Fieldbus Box, 4-channel analog output, RS232, current, 0/4…20 mA, 16 bit, single-ended, M12