EtherCAT Terminal, 4-channel analog output, multi-function, ±10 V, ±20 mA, 16 bit, single-ended, 10 ksps, push-in
EtherCAT Terminal, 2-channel communication interface, serial, RS232/RS422/RS485, push-in
The ED6012 EtherCAT Terminal enables the connection of serially communicating devices to the automation system. Extensive parameterization options allow flexible adaptation to different communication requirements. The following parameters, among others
| Number of channels | Total | 2 |
| Internal communication protocol | EtherCAT |
| Number of channels | 2 |
| Interfaces | RS232, RS422, RS485 |
| Protocol | variable |
| Transmission type | half or full duplex |
| Data transfer medium | copper |
| Device type | master, slave |
| Process data scope | 256 byte |
| Transmission rate | 300...921,600 baud |
| Data buffer | Receiving | 4 kbyte |
| Data buffer | Sending | 4 kbyte |
| Number of devices | max. 32 |
| Device | Supply voltage | 5 V DC |
| Device | Supply current | 0.1 A |
| Termination resistor | termination: 120 Ω, switchable, bias/fail-safe: 1 kΩ, switchable |
| Cable length | Point-to-point | max. 1200 m |
| ID switch | no |
| Connection technology | push-in |
| Distributed clocks | yes |
| Distributed clocks | Precision | 1 µs |
| Distributed clocks | Scope | 64 bit |
| Timestamp | yes |
| Timestamp | Precision | typ. 10 µs |
| Timestamp | Resolution | 1 ns |
| Oversampling | no |
| Electronics | Supply voltage | via E-bus |
| E-bus | Current consumption | typ. 190 mA |
| Power contacts | Input voltage | max. 24 V DC (+20%) |
| Power contacts | Current carrying capacity | max. 10 A DC |
| Power contacts | Current consumption | – |
| Power contacts | Output voltage | corresponds to Power contacts | Input voltage |
| Electrical isolation | Channel/channel | functional, 707 V DC type test |
| Electrical isolation | Channel/bus | functional, 707 V DC type test |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Relative humidity | 95%, no condensation |
| Installation position | variable |
| Vibration resistance | conforms to EN 60068-2-6 |
| Shock resistance | conforms to EN 60068-2-27 |
| EMC immunity | conforms to EN 61000-6-2 |
| EMC emission | conforms to EN 61000-6-4 |
| Markings | CE |
| Approvals | UL (in preparation) |
| Weight | 60 g |
| Protection rating | IP20 |
| Material | polycarbonate |
| Dimesnions | Width (single) | 15 mm |
| Dimensions | Width (lined up) | 12 mm |
| Dimensions | Height | 100 mm |
| Dimensions | Depth | 65 mm |
| Installation | Terminal/back wall | DIN rail, 35 mm (EN 60715) |
| Installation | Terminal/terminal | double slot and key connection |
| Plug-in wiring level | no |
| Connection cross-section | Solid wire | 0.08…1.5 mm² |
| Connection cross-section | Stranded wire | 0.25…1.5 mm² |
| Connection cross-section | With ferrule | 0.14…0.75 mm² |
| Connection cross-section AWG | Solid wire | AWG28…16 |
| Connection cross-section AWG | Stranded wire | AWG22…16 |
| Connection cross-section AWG | With ferrule | AWG26…19 |
| Stripping length | 8…9 mm |
| Power contact | "+" (left) | yes |
| Power contact | "+" (rechts) | yes |
| Power contact | "-" (left) | yes |
| Power contact | "-" (right) | yes |
| Power contact | "⏚" (left) | no |
| Power contact | "⏚" (right) | no |
| Insertion lock for power contact “⏚” | yes |
ED6012 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for ED6012 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for ED6012, subject to availability and destination.

EtherCAT Terminal, 4-channel analog output, multi-function, ±10 V, ±20 mA, 16 bit, single-ended, 10 ksps, push-in


EtherCAT Terminal, 2-channel encoder interface, incremental, 5 V DC (DIFF RS422, TTL, open collector), 5 MHz, push-in, 2 x AB/1 x ABC

EtherCAT Terminal, 1-channel communication interface, serial, RS232/RS422/RS485, push-in



EtherCAT Terminal, 2-channel motion interface, stepper motor, 48 V DC, 3 A, push-in, with incremental encoder, 5 V DC

EtherCAT Terminal, 1-channel motion interface, servomotor, 48 V DC, 4.5 A, push-in, OCT