| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 3P |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (I<sub>th</sub>) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1050 A |
| Rated Operational Current AC-1 (I<sub>e</sub>) | (1000 V) 40 °C 1000 A, (1000 V) 55 °C 875 A, (1000 V) 70 °C 720 A, (690 V) 40 °C 1050 A, (690 V) 55 °C 875 A, (690 V) 70 °C 720 A |
| Rated Operational Current AC-3 (I<sub>e</sub>) | (415 V) 55 °C 750 A, (440 V) 55 °C 750 A, (500 V) 55 °C 750 A, (690 V) 55 °C 650 A, (1000 V) 55 °C 300 A, (380 / 400 V) 55 °C 750 A, (220 / 230 / 240 V) 55 °C 750 A |
| Rated Operational Current DC-1 (I<sub>e</sub>) | (110 V) 1-Pole, 40 °C 1050 A, (110 V) 2 Poles in Series, 40 °C 1050 A, (220 V) 3 Poles in Series, 40 °C 1050 A, (600 V) 3 Poles in Series, 40 °C 1050 A, (850 V) 3 Poles in Series, 40 °C 1050 A |
| Rated Operational Current DC-3 (I<sub>e</sub>) | (110 V) 1-Pole, 40 °C 1050 A, (110 V) 2 Poles in Series, 40 °C 1050 A, (220 V) 3 Poles in Series, 40 °C 1050 A, (600 V) 3 Poles in Series, 40 °C 1050 A |
| Rated Operational Current DC-5 (I<sub>e</sub>) | (110 V) 1-Pole, 40 °C 1050 A, (110 V) 2 Poles in Series, 40 °C 1050 A, (220 V) 3 Poles in Series, 40 °C 1050 A, (600 V) 3 Poles in Series, 40 °C 1050 A |
| Rated Operational Power AC-3 (P<sub>e</sub>) | (415 V) 425 kW, (440 V) 450 kW, (500 V) 520 kW, (690 V) 600 kW, (1000 V) 400 kW, (380 / 400 V) 400 kW, (220 / 230 / 240 V) 220 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Short-Circuit Protective Devices | gG Type Fuses 1000 A |
| Rated Short-time Withstand Current Low Voltage (I<sub>cw</sub>) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1300 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 4500 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 7000 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 6400 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 3500 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 7500 A, cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 7000 A |
| Rated Insulation Voltage (U<sub>i</sub>) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V, acc. to UL/CSA 600 V |
| Rated Impulse Withstand Voltage (U<sub>imp</sub>) | Main Circuit 8 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour, (AC-2 / AC-4) 60 cycles per hour, (AC-3) 300 cycles per hour |
| Mechanical Durability | 3 million |
| Maximum Mechanical Switching Frequency | 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (U<sub>c</sub>) | 50 Hz 100 ... 250 V, 60 Hz 100 ... 250 V, DC Operation 100 ... 250 V |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 38.3 V·A, Holding at Max. Rated Control Circuit Voltage 50 Hz 4.6 W, Holding at Max. Rated Control Circuit Voltage 60 Hz 38.3 V·A, Holding at Max. Rated Control Circuit Voltage 60 Hz 4.6 W, Holding at Max. Rated Control Circuit Voltage DC 4.3 W, Pull-in at Max. Rated Control Circuit Voltage 50 Hz 1229 V·A, Pull-in at Max. Rated Control Circuit Voltage 60 Hz 1229 V·A, Pull-in at Max. Rated Control Circuit Voltage DC 1292 V·A, Pull-in at Max. Rated Control Circuit Voltage DC 1292 W |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 67 W, at Rated Operating Conditions AC-3 per Pole 34 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 50 ... 70 ms, Between Coil De-energization and NO Contact Opening 53 ... 73 ms, Between Coil Energization and NC Contact Opening 45 ... 115 ms, Between Coil Energization and NO Contact Closing 50 ... 120 ms |
| Connecting Capacity Main Circuit | Bar 52 mm², Bar 50 mm², Rigid Al-Cable 3x185 mm², Rigid Cu-Cable 3x185 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm², Flexible 1x0.75 ... 2.5 mm², Flexible 2x0.75 ... 2.5 mm², Solid 2 x 1 ... 4 mm², Stranded 1 x 1 .... 4 mm², Stranded 2 x 1 .... 4 mm² |
| Connecting Capacity | Bar 52 mm², Rigid Al-Cable 3x185 mm², Rigid Cu-Cable 3x185 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Connecting Terminals (delivered in open position) Main Poles | M 3.5 (+,-) pozidriv 2 screw with cable clamp |
| Recommended Screw Driver | Main Circuit M12, Control Circuit Pozidriv 2, Control Circuit M3.5 |
| Tightening Torque | Cable Lug 45 N·m, Main Circuit 45 N·m |
| Terminal Type | Main Circuit: Bars |
| Suitable for Product Class | Block ContactorsBlock Contactors |
| Product Name | Block Contactor |