Yes, using LED status indicator and software (output error status)
Power consumption – Bus
0.1 W (Rev. <L0: 0.16 W)
Power consumption – Internal I/O
0.49 W
Certifications – CE
Yes
Certifications – UKCA
Yes
Certifications – CRA (Cyber Resilience Act)
In preparation
Certifications – ATEX
Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X
Certifications – UL
cULus E115267; Industrial control equipment
Certifications – HazLoc
cCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5
Certifications – KC
Yes
B&R ID code
0x1B9C
Status indicators
I/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]Mechanical and electrical configuration" in the X20 system user's manual.">
+1 (Rev. <L0: +1.6) (note: Number of outputs x R DS(on) x Nominal output current 2 . For a calculation example, see section)
Digital outputs
Switching delay – 0 → 1
<300 µs (note: At loads ≤ 1 kΩ)
Switching delay – 1 → 0
<300 µs (note: At loads ≤ 1 kΩ)
Switching frequency – Resistive load
Max. 500 Hz (note: At loads ≤ 1 kΩ)
Switching frequency – Inductive load
See section "Switching inductive loads".
Variant
Current-sourcing FET
Nominal voltage
24 VDC
Switching voltage
24 VDC -15% / +20%
Nominal output current
2 A
Total nominal current
8 A (Rev. <H0: 4 A)
Connection type
3-wire connections
Output circuit
Source
Output protection
Thermal shutdown in the event of overcurrent or short circuit (see value "Short-circuit peak current"); Internal freewheeling diode for switching inductive loads (see section "Switching inductive loads")
Actuator power supply
0.5 A in total for output-independent actuator power supply
Diagnostic status
Output monitoring with 10 ms delay
Leakage current when the output is switched off
5 µA
R DS(on)
60 mΩ (Rev. <L0: 100 mΩ)
Peak short-circuit current
<4 A (Rev. <H0: <12 A)
Switch-on in the event of overload shutdown or short-circuit shutdown
Approx. 10 ms (depends on the module temperature)
Braking voltage when switching off inductive loads
Typ. 50 VDC
Insulation voltage between channel and bus
500 V eff
Additional functions
Outputs can be connected in parallel to increase the output current.
Actuator power supply
Power consumption – Actuator power supply
Max. 12 W (note: The power consumption of the sensors connected to the module is not permitted to exceed 12 W.)
Voltage
Module power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 500 mA
Max. 2 V
Short-circuit proof
Yes
Electrical properties
Electrical isolation
Channel isolated from bus; Channel not isolated from channel and I/O power supply
Operating conditions
Mounting orientation – Horizontal
Yes
Mounting orientation – Vertical
Yes
Installation elevation above sea level – 0 to 2000 m
No limitation
Installation elevation above sea level – >2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529
IP20
Ambient conditions
Temperature – Horizontal mounting orientation
-25 to 60°C
Temperature – Vertical mounting orientation
-25 to 50°C
Temperature – Derating
See section "Derating".
Temperature – Storage
-40 to 85°C
Temperature – Transport
-40 to 85°C
Relative humidity – Operation
5 to 95%, non-condensing
Relative humidity – Storage
5 to 95%, non-condensing
Relative humidity – Transport
5 to 95%, non-condensing
Mechanical properties
Note
Order 1x terminal block X20TB12 separately.; Order 1x bus module X20BM11 separately.
Bus modules — The bus module is the base for all X20 24 VDC I/O modules; The internal I/O supply is interconnected; Manual node number assignment; Indepe…
Bus modules — Bus module for 24 VDC I/O modules; The internal I/O power supply is connected through. The bus module is the base for all 24 VDC I/O module…
Terminal blocks — Tool-free wiring with push-in technology; Simple wire release using lever; Ability to label each terminal; Plain text labeling also possibl…
Downloads & documentation
Official documents from B&R, downloaded directly from the manufacturer.
X20DO4332 is in stock and typically ships within 1 business day via UPS, DHL or FedEx, worldwide.
Can I pick up X20DO4332 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — alongside standard UPS, DHL and FedEx shipping, express (next-day) delivery is available at checkout for in-stock items like X20DO4332.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for X20DO4332, subject to availability and destination.